2
PRODUCT SUMMARY
The 560 / 570 Series battery powered smoke detectors offer two
solutions:
• 560 Series for stand-alone applications,
• 570 Series incorporating a tamper switch is for use with a
radio transmitter to a control panel.
The operation of the 560 / 570 Series detectors are identical
except for the silence and test:
• The 570 Series cannot be silenced using the Silence / Test
button.
• The 570 Series does not issue an alarm beep at the end of
a test sequence.
• The 570 Series will transmit a tamper fault when removed
from its base.
INSTALLING THE DETECTOR
In addition to the local Fire Protection Standards, use the
following location guidelines to optimise performance and reduce
the chance of false alarms from the detector:
• Locate ceiling-mounted smoke detectors in the centre of a
room or hallway at least 10 cm (4 inches) from any walls or
partitions.
• Locate wall-mounted smoke detectors so the top of the
detector is 10 –30 cm (4 to 12 inches) below the ceiling.
• Locate away from air conditioners, radiators and any other
ventilation sources that may interfere with smoke entering
the detector.
• DO NOT mount the detector on removable ceiling panels as
the removal of these panels will render the detector
inoperable.
To install a detector
1. If you are using the detector/base lock, remove the two
knockouts
on the mounting base. (See Figure )
2. Slide the battery compartment cover away from the detector
to unsnap it and lift it off. See Figure
:
Tab
Slot
Battery compartment
3. Observing proper polarity, insert two 3V-lithium batteries into
the detector battery compartment and replace the battery
compartment cover.
4. Remove the red plastic dust cover from the detector. The
detector is shipped with a dust cover for protection on
construction sites with dusty environments.
5. Using the two screws and anchors provided, mount the base.
6. Attach the detector to the mounting base as follows:
- Line up the raised tab on the lip of the detector with the
slot on the lip of the mounting base. (See Figure
)
- Insert the smoke detector into the base and turn
clockwise approximately 15 degrees. It should snap
firmly into place.
Important: The detector cannot be attached to the mounting
base if no batteries are installed.
7. Test the detector (See Smoke Testing the Detector).
SMOKE TESTING THE DETECTOR
Replace the batteries as described in Replacing the Batteries
below.
Test smoke detectors in place annually using canned aerosol
simulated smoke. Follow the instructions on the canned smoke.
The detector LED remains on and the alarm sounds a temporal
rhythm until the Test/Silence button is pressed. The detector
automatically resets when smoke is no longer present.
THE TEST/SILENCE BUTTON
The Test/Silence button on the detector performs these three
functions:
Testing: Press the Test/Silence button for 2 seconds. The
detector performs a sensitivity test and, in the case of the 560
Series, a sounder test.
Silence alarm (560 Series only): Press to silence the sounder
during an alarm. After a few minutes, the sounder and alarm
resume if smoke is still present.
Silence trouble chirp: Press to silence a trouble chirp. The
trouble chirp resumes after 24 hours if the trouble condition is not
corrected.
TESTING THE DETECTOR SENSITIVITY
The smoke detector provides a sensitivity level test mode that
allows you to check the smoke detector sensitivity using the
Test/Silence button and the LED indicator on the detector as
follows:
1. Press the Test/Silence button on the smoke detector for 2
seconds. Once the test starts, the alarm LED flashes one to
nine times.
2. Count the number of times the LED flashes and use the
following table to determine the status of the smoke detector
sensitivity and what action to take, if any.
Flashes Obscuration
%/m
(approx.)
Indication Action
1 N/A Unserviceable
hardware fault
detected
Reset the unit
and rerun
sensitivity test. If
the error
persists, replace
the unit.
2, 3 N/A Detector is not
sensitive
enough
Clean the unit.
Reset it and
rerun the
sensitivity test. If
the error
persists, replace
the unit.
4 0.95 %/m
5 0.79 %/m
6 0.64 %/m
7 0.49 %/m
Detector is
within normal
sensitivity
range
N/A
8, 9 N/A Detector is too
sensitive
Verify that the
smoke
chambers are
snapped down
correctly. Clean
the unit and
replace the
smoke chamber.
After the flashes, if the sensitivity is within limits and all
other tests pass, the 560 Series will go into alarm, sound its
sounder, and reset after 5 seconds; the 570 Series will
remain silent.
If the sensitivity is not within limits, or an unserviceable
hardware fault has been detected, the smoke detector LED
extinguishes until the detector is serviced.
REMOVING THE DETECTOR
To remove the detector from the mounting base, hold the
detector and turn it counter-clockwise approximately 15 degrees.
The smoke detector will snap out of the mounting base.
To remove the detector from the mounting base when the
detector/base lock is used, insert a small screwdriver into the
locking tab slot on the side of the base and press in while
simultaneously turning the detector counter-clockwise 15
degrees. (See Figure
)
UNDERSTANDING THE LED
The LED on the detector indicates the status of the detector as
follows: