Cumberland Farm Hand Heat Zone Owner's manual

  • Hello! I have analyzed the Hired-Hand user manual for the Farm Hand Heat Zone Environmental Controller models 6607-1596 and 6607-1595. This manual provides detailed information about the installation, operation, and maintenance of the controller, which is used for temperature control in poultry houses. The controller monitors up to four heating zones and supports different types of brooders. I am ready to answer any questions you might have about its functions or settings.
  • What is the purpose of the Farm Hand Heat Zone Controller?
    How many zones can the Farm Hand Heat Zone controller manage?
    What are the three settings on the Zone Control Switches?
    What if the display flashes 'LnE'?
Part No. 4801-5129 rev 6/04 Owners Manual Farm Hand Heat Zone
Farm Hand Heat Zone
4 Stage Environmental Controller
Hired Hand, Inc.
1733 Co Rd 68
PO Box 99
Bremen, AL 35033
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone Table of Contents
Table of Contents
Section Title Page
1. Ratings and Specifications .............................................................................................................................1
2. Warnings ........................................................................................................................................................1
3. Limited Warranty ...........................................................................................................................................1
4. Introduction ....................................................................................................................................................2
5. Day to Day Operating Instructions.................................................................................................................3
5.1 Face Pad Description..............................................................................................................................3
5.2 Checking/Adjusting Temperatures.........................................................................................................3
5.3 Using the Heat Zone controller over local or HH.Net connections........................................................4
6. Program Mode................................................................................................................................................5
6.1 Zone Parameters .....................................................................................................................................5
6.1.1 Temperature Units (P1) ..................................................................................................................5
6.1.2 Stage On Points (P4) ......................................................................................................................5
6.1.3 Stage Off Points (P5)......................................................................................................................6
6.2 PC Compatible Network Parameters ......................................................................................................6
6.3 Sensor Calibration ..................................................................................................................................6
7. Controller Installations and Setup ..................................................................................................................6
7.1 Tools Required .......................................................................................................................................6
7.2 Installation Instructions ..........................................................................................................................7
8. Maintenance ...................................................................................................................................................7
8.1 Sensor Calibration ..................................................................................................................................7
8.2 Removing and Replacing a Relay Strip..................................................................................................7
9. Wiring Diagrams ............................................................................................................................................9
9.1 Connecting directly to Farm Manager over the HH.Net ......................................................................10
9.2 Observing the Status LEDs ..................................................................................................................11
9.3 Connecting to an SCS™ over a Local Network Connection................................................................12
9.4 Connecting Ignition to an HSI Infrared Brooder..................................................................................13
9.5 Connecting Ignition to a Zone Infrared Brooder..................................................................................14
9.6 Connecting the Temperature Sensors ...................................................................................................15
9.7 Connecting AC Power..........................................................................................................................16
10. Program Reference ...................................................................................................................................17
10.1 Error Codes...........................................................................................................................................17
10.1.1 Sensor Errors ................................................................................................................................17
10.1.2 Possible Solutions.........................................................................................................................18
10.1.3 Local Network Errors ...................................................................................................................18
11. Temperature vs. Sensor Resistance Table ................................................................................................19
12. Program Parameter Listing.......................................................................................................................20
13. Error Code Listing....................................................................................................................................20
14. Program Data Sheet..................................................................................................................................21
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 1
1. Ratings and Specifications
115 VAC for Model #6607-1596 (HSI model)
115/230 VAC for Model #6607-1595 depending on wiring options (Zone model)
50/60 Hz
12 Amperes @ 120 VAC for Model # 6607-1596 - (HSI model)
4 Stages with 24 VAC output. @ 10Amperes total load between all stages
for Model # 6607-1595 – (Zone model)
Room must be kept between 122°F/50°C and 32°F/0°C.
2. Warnings
Warning!
Before connecting power to the machine, be sure to check the correct
wiring for either 120 or 240 volts.
Warning!
When this controller is used in a life support heating and ventilation
system where failure could result in loss or injury, the user should provide
adequate back-up, or accept the risk of such loss or injury!
3. Limited Warranty
All products are warranted to be free from defects in material and workmanship for a period of one
year from the date of purchase if installed and used in strict accordance with the installation
instructions. Liability is limited to the sale price of any products proved to be defective or, at
manufacturers option, to the replacement of such products upon their return. No products are to be
returned to the manufacturer, until there is an inspection and/or a return-goods authorization (RGA)
number is issued.
All complaints should be directed first to the authorized distributor who sold the product. If
satisfaction is not obtained or the name of the distributor is not known, write the manufacturer that
appears below, directed to the attention of Customer Service Manager.
This limited warranty is expressly in lieu of any and all representations and warranties expressed or
implied, including any implied warranty of merchantability or fitness for a particular purpose. The
remedy set forth in this limited warranty shall be the exclusive remedy available to any person. No
person has authority to bind the manufacturer to any representation or warranty other than this limited
warranty. The manufacturer shall not be liable for any consequential damages resulting from the use of
our products or caused by any defect, failure or malfunction of our products. (Some areas do not allow
the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion
may not apply to you.)
This warranty gives you specific legal rights and you may also have other rights that vary from area to
area.
Warrantor:
Hired-Hand, Inc.
1733 Co. Rd. 68
PO Box 99
Bremen, AL 35033
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 2
4. Introduction
The Farm Hand Heat Zone Controller is a four stage environmental controller intended for temperature
control of poultry houses equipped with heaters that will operate from either 24 VAC or 120 VAC
ignition. The examples used in this manual show HSI and Zone brooders, although the Heat Zone
controller is not limited to these models.
A typical installation of the Farm Hand Heat Zone controller that can control up to four brooder heat
zones is illustrated below. This example shows half house brooding with eight brooders in each of the
four Heat Zones. Temperature sensors are placed in the center area of each zone. As noted below
Sensor 1 should be placed in the center of Zone 1, Sensor 2 in the center of Zone 2, etc. The Farm
Hand Heat Zone controller monitors the temperature of each zone and controls the ignition of the
brooders to maintain each zone temperature within the limits as established by the user. The Zone
controller can be used in conjunction with the Vent Master 24 or be connected to the Hired Hand Farm
Manager network.
ON AUTO
ON AUTO
Zone 1
Zone 2
Zone 3
Zone 4
4
3
(Zona 1)
(Zona 2)
(Zona 3)
(Zona 4)
R
4501-6074
Directions
Plac ing s witch in t he pos ition will p revent t he zone from op eratin g.
Placing switch in the position will cause the zone to r un continuously.
Plac ing s witch in t he pos ition will op erate bas ed on the cont roller.
OFF
ON
AUTO
Farm Hand
Heat Zone
Room Temp
Target Temp
Zone Temps
(Temperatura Cuarto)
(Temeratura Optima)
(Temeratura Z ona) (Modo)
ON AUTO
ON AUTO
2
1
OFF
Farm Hand Heat Zone Controller
Zone
Control
Switches
Zone Status
Indicators
Main
Display Indicators
Control Buttons
Example of Half House Brooding with Four Heat Zones.
(
Ei
g
ht Brooders in each Zone.
)
ZONE 1
SENSOR 1
SENSOR 3
ZONE 3
Center Curtain
Brooder ZONE 4
ZONE 2
SENSOR 2
SENSOR 4
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 3
Zone 1
Zone 2
Zone 3
Zone 4
(Zona 1)
(Zona 2)
(Zona 3)
(Zona 4)
Zone Status
Indicators
ON AUTO
ON AUTO
4
3
4501-6074
ON AUTO
ON AUTO
2
1
OFF
Zone Control
Switches
There are two models of the Farm Hand Heat Zone controller. Model # 6607-1596 (120 VAC) works
with Hot Surface Ignition (HSI) types of brooders and provides 120 volts for ignition. The 120 volts
is supplied from an external power supply as illustrated in the wiring diagram is Section 9.4. Model #
6607-1595 (24 VAC) works with Zone brooders and provides 24 volts for ignition. See Sections 9.4
and 9.5 for wiring diagrams.
For additional information on installing and connecting brooders, refer to Hired-Hand Zone Brooder
Owners Manual # 4801-5107 or Hired-Hand HSI Owners Manual # 4801-5121.
5. Day to Day Operating Instructions
This section of the manual describes the day to day operation of the Farm Hand Heat Zone controller.
5.1 Face Pad Description
The Heat Zone Controller has three regions on
the face pad. First is the main display area.
This section includes the main display, and
three green LED’s which tell what the display is
indicating. If the green light beside “Room
Temperature” is lit, then the display is showing
the average inside temperature of the heated
area of your building. Later in this manual you
will learn how to view the other two parameters.
Just to the right of the main display is the control button region. This region has three buttons, Mode,
Plus (+), and Minus (-). The Mode button is the primary user operated button on the controller. It has
two functions: First, when you press the button you will step through Room Temperature, Target
Temperature and Zone Temperatures. (All of these are shown on the display.). Second, the mode
button allows you to go into program mode. To do this, press and hold the mode button for five
seconds, until you see “P1” in the display. This P1 will alternate with the actual setting of Parameter
P1. (See Section 6 “Program Mode” for more information.)
The Plus and Minus buttons are used to adjust settings (Target Temperature, for
example). If you press the Plus (+) button, the setting will increase, and when
you press the Minus (-) button, the setting will decrease.
Below the main display are four zone status indicators. This red light will be lit if
the stage is on.
Finally, the Farm Hand Heat Zone Controller has
a three position switch for each one of the four
zones. The Zone Control Switches will control the heaters based upon the
settings as follows:
ON – In this position the brooder runs continuously. The brooder can
not be turned off by the Heat Zone Controller.
OFF – In the “OFF” position the Heat stage will not run. The brooder
can not be turned on by the Heat Zone Controller.
AUTO – The stage is under control of the Farm Hand Heat Zone
Controller.
5.2 Checking/Adjusting Temperatures
To view the average temperature of the heated area of your house, look at the display. When a control
button has not been pressed with in the last minute, the display will automatically show “Room
Temperature”. To see the Target Temperature, press the button labeled “Mode”. When this button is
pressed, watch the green LED’s beside the main display. Whichever LED is lighted determines the
+
Room Temp
Target Temp
Zone Temps
( Temperatura Cuarto)
( Temeratura Optima)
( Temeratura Zona) (Modo)
Main Display Area
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 4
parameter you are viewing. You can easily see “Room Temperature”, “Target Temperature and all
four Zone Temperatures. These three temperatures are defined as:
Room Temperature = The average of the four zone sensors located inside the house.
Target Temperature = The temperature the system tries to maintain.
Zone Temperature = The temperature of each of the four zones.
To adjust the Target Temperature, press the mode button until the LED beside Target Temp is lighted,
then use the Plus (+) button to raise the value, or the Minus (-) button to lower the value. When you
are finished setting a new value, either press the mode button again, or wait a few seconds and the
system will return to normal operation.
To view the zone temperatures press the mode button until the LED beside Zone Temps is lighted. Note
also the Zone 1 LED will light indicating the Zone 1 temperature is being shown in the display indicator.
Continue to press the Mode button to step through all four of the Zone temperature readings.
The chart below shows the sequence of parameters will be shown in the display as the mode button is
pressed.
5.3 Using the Heat Zone controller over local or HH.Net connections
The Farm Hand Heat Zone controller has the capability to operate with other network
compatible controllers over the HH.Net or over a local network connection. Two examples
are shown in the Wiring diagrams. The Heat Zone can be connected to the Vent Master over
a local network connection. (See Section 9.3 for a wiring diagram.) The Vent Master can
then control the Target Temperature. Programming parameter P40 of the Heat Zone
controller is the Network Address. This must be set to zero (0) when operating with the Vent
Master.
Heat Zone Controller
(
Parameter Selection Se
q
uence
)
Room
Temperature Zone 1
Temperature
Zone 3
Temperature
Zone 2
Temperature
Zone 4
Temperature
Target
Temperature
For Zone Temperatures, both
the Zone Temps LED and
the Zone LED will be
Zone 1
Zone 2
Zone 3
Zone 4
(Zona 1)
(Zona 2)
(Zona 3)
(Zona 4)
+
Room Temp
Target Temp
Zone Temps
(Temperatura Cuarto)
(Temeratura Optima)
(Temeratura Zona)
(Modo)
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 5
The Heat Zone can also be connected directly a personal computer running the Farm Manager
software. See Section 9.1 for a wiring diagram. In this case the Network Address of the Heat
Zone must be between eight (8) and 32 and be unique as required. For additional information
on the HH.Net and Farm Manager see Hired Hand document Number 4801-5049.
When connected to a local network or to the HH.Net, there are two LEDs on the Heat Zone
circuit board that indicate the status of communications. The Receive LED is lighted red
when receiving data over the network connection. (Note: This LED may appear to be on
continuously. The Transmit LED is lighted red when transmitting to a Master controller or
the Farm Manager. See Section 9.2 for the location of these LEDs.
6. Program Mode
Settings that are usually set up once per growout, or maybe even just for summer or winter are referred
to as program parameters and are accessed by taking the controller to program mode. Some examples
of these settings are Zone On points and Off points and Sensor Calibration. To get to program mode,
press and hold the “Mode” button for five seconds. When the controller has entered program mode,
the main display will flash between “P1” and the value of this parameter.
The “P1” is known as a parameter number. All the program items for the controller have a parameter
number assigned to them. The numbers are listed in the section called “Program Reference” in the
back of this manual with a short description of each parameter.
When in the program mode, the current parameter is changed by using the Plus (+) and Minus (-)
buttons as needed. When you have finished with the current setting, press the “Mode” button to move
to the next parameter. Look at the zone status indicators. If the light for zone 1 is lit, the parameter
being programmed is for zone 1. To go to zone 2, continue to press the mode button until the zone 2
indicator LED is lit.
6.1 Zone Parameters
The following parameters are used to program each zone on the Farm Hand Heat Zone
Controller. Through these parameters, the user has complete control over the operation of
each stage. The following section explains each parameter.
P1 = Metric or English Units
P4 = Zone On Point
P5 = Zone Off Point
6.1.1 Temperature Units (P1)
The zone parameter (P1) sets the type of temperature units displayed in the indicator.
P1 options are as follows:
ON = Metric
Temperature is displayed in degrees Celsius.
OFF = English
Temperature is displayed in degrees Fahrenheit.
6.1.2 Stage On Points (P4)
The On Point setting is the temperature at which a stage turns on. (i.e. the
temperature at which an ignition signal is transmitted by the controller. The On
Point settings for the Heat Zone controller will always be less than the target
temperature.
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 6
6.1.3 Stage Off Points (P5)
The Off Point setting is the temperature at which a the ignition to a brooder turns off.
6.2 PC Compatible Network Parameters
This option requires Hired-Hand’s Farm Manager Software. The controller has three
functions which are used to set it up on the Hired-Hand PC compatible inter-controller
network (HH.Net). These are:
P40 - HH.Net Address
HH.Net allows you to connect up to 32 controllers on a single communications port of your
personal computer (PC). In order for the computer to recognize the communications from the
controllers, each controller must have a unique address. There are two restrictions on the
address of the Heat Zone controller depending on how it is connected in the HH.Net. If the
Heat Zone is connected to the Vent Master, the address of the Heat Zone must be set to zero.
When connected directly in the HH.Net the address must be between eight (8) and 32 and be
unique as required. For example, If you have two Heat Zone Controllers, and two Power
Vents you would need to set the first Heat Zone Controller to address 8, the second Heat
Zone Controller to address 9, the first Power Vent to address 1, and the second Power Vent to
address 2. (You do not have to address the controllers in any particular physical order.)
P41 - Version Number
This is not settable. It is the version of the controller software.
P42 - Controller Type
This is not settable. It is a unique number that allows the network software (Farm Manager)
to know the type of controller.
6.3 Sensor Calibration
The Heat Zone Brooder Controller has 4 sensors that may be calibrated. The parameter(s) for
calibration are PSX with X being the sensor number. The sensor temperature reading is
alternately displayed along with the parameter number. You should never attempt to calibrate
a sensor more than 8 degrees. If a temperature reading that is that far out of range, it
indicates that there is a problem that should be corrected.
PS1 - Calibrate Sensor 1
This reading can be changed by pressing the + or - button until the desired
reading is displayed.
PS2 - Calibrate Sensor 2
This reading can be changed by pressing the + or - button until the desired
reading is displayed.
PS3 - Calibrate Sensor 3
This reading can be changed by pressing the + or - button until the desired
reading is displayed.
PS4 - Calibrate Sensor 4
This reading can be changed by pressing the + or - button until the desired
reading is displayed.
7. Controller Installations and Setup
7.1 Tools Required
Mini Screwdriver
Wire Strippers
Standard Screwdriver
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 7
7.2 Installation Instructions
1. Unpack system, and check that all components are present.
1 Farm Hand Heat Zone Controller
1 Installation Kit
4 Temperature Sensors
1 Manual
2. Hang Farm Hand Heat Zone Controller with four screws and the plastic mounting
brackets included.
3. Make sure all power supplies are disconnected before breaking any wires, or
reaching into the enclosure.
4. Open the Heat Zone Controller and find all connections. Refer to wiring diagrams in
back of this manual.
5. Run sensors out to locations inside the house. Be sure that the sensors are in a safe
location, free from any temperature influences (direct sunlight, water, etc.) Use care
when securing sensor wires so that you do not cut the wire. Any short, or break in
the wire will cause improper sensor operation.
6. Connect each sensor to its appropriate terminals inside the enclosure. (See the wiring
diagram in Section 9.6 of this manual.)
7. Connect wires from stage terminals to the brooders. See Section 9.4 for wiring to an
HSI brooder or Section 9.5 for wiring to a Zone brooder.
8. Connect the wires for either 120Vor 240V power to the terminals specified in the
wiring diagram in Section 9.7.
8. Maintenance
8.1 Sensor Calibration
Check the calibration of your sensors at least once per quarter. You will need to have two people.
One at the sensor with a trusted thermometer, and one at the controller to set the sensor to the proper
setting.
8.2 Removing and Replacing a Relay Strip
The Heat Zone Controller is equipped with removable relay strips for easy maintenance and
replacement.
1) Remove electrical power from the Heat Zone Board.
Mounting Tab
Mounting Tab
RELAY STRIP
Main Circuit Board
Rela
y
s
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 8
Note: In step 2, it very important to remove electrical power
from the circuits connected to the relay board, since
external equipment may back-feed voltage through the
rela
y
board!
CAUTION !
2) Remove power from the equipment connected to the relay strip to be replaced.
3) Unplug the Stage harness cables from the relay board.
4) Use needle nose pliers to pinch the tops of the mounting tabs to release the relay strip.
5) Verify that the replacement relay strip is of the Normally Open (N.O.) type. Fail-Safe types
of relay strips are not recommended in heating. See the insert below that describes how to
recognize the two types of relay strips.
6) Install new relay strip by pressing evenly near the mounting tabs.
7) Re-install the stage harness cables.
FAIL-SAFE
strips are labeled at the
top of the board.
When replacing any
Relay Strip be sure to
verify the type.
NORMALLY OPEN
(N.O.)
strips are labeled at the
bottom of the board.
Inset
(Top)
(Bottom)
HEAT
COOL 3
COOL 2
COOL 1
RPK
COOL 3
COOL 2
COOL 1
HEAT
FAIL-SAFE RELAY STRIP
COOL 3
COOL 2
COOL 1
HEAT
B Crider
N.O.RELAY STRIP
WHAT ARE FAIL-SAFE RELAY STRIPS ?
There are two types of Relay Strips. The Normally Open (N.O.) strip
requires a signal from the controller board in order to energize a stage
of ventilation. Should power be removed from the controller, the
N
ormally Open Relay board would not be able to energize a ventilator.
On the other hand, the Fail-Safe relay strip would close each of the
relays in the strip resulting in energizing the ventilators in case of a
controller power failure.
NOTE: Fail-Safe relay strips are NOT recommended for
heating (brooder) applications!
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 9
9. Wiring Diagrams
Power Supply
Stage 1Stage 2Stage 3Stage 4
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
120V (L2)
Hot (L1)
240V (L2)
L1
L2
GND
L1
L2
L1
L2
L1
L2
Power Supply
Transformer
(Type depends
on Model)
Farm Hand Heat Zone Controller
Circuit
B
oa
r
d
Terminal
Strip
Zone
Control
Switches
N.O. Relay
Strip
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 10
9.1 Connecting directly to Farm Manager over the HH.Net
Router
RS-232 Twisted Pair Cable
Up to 32 Nodes
To
Equipment
To
Equipment
To
Equipment
To
Equipment
To Rest of Network
IBM Compatible with Win '95 O/S
Farm Manager Network
Node
0
Node
1
Node
2
Node
3
Farm Hand Controller
Farm Hand Controller
Farm Hand Controller
Farm Hand Controller
The Farm Hand Heat Zone
Controller can be connected
directly to the HH.Net just like
any Farm Hand Network
compatible controller. The
Network address for the Heat
Zone must be set using Program
Parameter P40 to a unique
address between 8 and 32. See
the Farm Manager Software
manual Part No. 4801-5049.
Farm Hand Heat Zone Controller
Inset A
Zone
Controller
Inset A
Pos (+) - Red
Ne
g
(
-
)
- Black
NC - Green
To Other
Controllers
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 11
9.2 Observing the Status LEDs
Farm Hand Heat Zone Controller
Circuit Board
Inset A
There are two Status LEDs on the circuit board. They
indicate:
Receive – Red when receiving data over the network
connection. (Note: This LED may appear to be on
continuously.
Transmit - Red when transmitting to a Master controller
or the Farm Mana
g
er.
NET STATUS
RECEIVETRANSMIT
Inset A
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 12
9.3 Connecting to an SCS™ over a Local Network Connection
SCS 16 Stage
SCS 16 Stage
w/Back-Up
To Master
Controller
Pos (+) - Red
Neg (-) – Black
NC- Green
Inset A
Inset B
Inset A Inset B
SCS™ circuit board
Heat Zone
Controller
+
ON AUTO
ON AUTO
Zone 1
Zone 2
Zone 3
Zone 4
4
3
(Zona 1)
(Zona 2)
(Zona 3)
(Zona 4)
R
4501-6074
Directions
Placing switch in the position will prevent the zone from operating.
Placing switch in the position will cause the zone to run continuously.
Placing switch in the position will operate based on the controller.
OFF
ON
AUTO
Farm Hand
Heat Zone
Room Temp
Targ et Tem p
Zone Temps
(Temperatura Cuarto)
(Temeratura Optima)
(Temeratura Zona) (Modo)
ON AUTO
ON AUTO
2
1
OFF
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 13
9.4 Connecting Ignition to an HSI Infrared Brooder
NOTE: For information on proper grounding and electrical connections refer
to Hired-Hand Brooder Manual #4801-5121
Warning: Do not connect more than 12 amps of load to a single stage!
Electrical
Enclosure
HSI Infrared Brooder
Terminal Strip inside HSI
Electrical Enclosure
Terminal Strip inside Heat
Zone Controller
To Breaker
Hot
L1
NW H I T E
B L A C K
B L A C K & B R O W N
B R O W N & W H I T E
O R A N G E
G R E E N
Y E L L O W
Earth
Power Supply
Stage 1Stage 2Stage 3Stage 4
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
120V
(L2)
Hot
(L1)
240V
(L2)
L1L2
GND
L1L2L1L2L1L2
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 14
9.5 Connecting Ignition to a Zone Infrared Brooder
NOTE: For additional information on electrical connections refer to Hired-
Hand Brooder Manual #4801- 5107.
Inset A
Zone Infrared Brooder
Inset A
Terminal Strip inside Heat
Zone Controller
24 VAC
Power Supply
Stage 1Stage 2Stage 3Stage 4
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
120V
(L2)
Hot
(L1)
240V
(L2)
L1L2
GND
L1L2L1L2L1L2
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 15
9.6 Connecting the Temperature Sensors
Inset A
Farm Hand Heat Zone Controller Circuit Board
Inset A
Sensor 1
Sensor 2 Sensor 3
Sensor 4
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 16
9.7 Connecting AC Power
To Breaker
Terminal Strip inside Heat Zone Controller
GROUND
HOT
NEUTRAL
240 Volt Source
To Breaker
Terminal Strip inside Heat Zone Controller
GROUND
HOT
NEUTRA
L
120 Volt Source
Power Supply
Stage 1 Stage 2 Stage 3 Stage 4
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
120V
(L2)
Hot
(L1)
240V
(L2)
L1 L2
GND
L1 L2 L1 L2 L1 L2
Power Supply
Stage 1 Stage 2 Stage 3 Stage 4
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
120V
(L2)
Hot
(L1)
240V
(L2)
L1 L2
GND
L1 L2 L1 L2 L1 L2
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 17
10. Program Reference
Program Parameters
P1 – Temperature Units The zone parameter (P1) sets the type of temperature units
displayed in the indicator.
ON = Metric - Temperature is displayed in degrees Celsius.
OFF = English - Temperature is displayed in degrees
Fahrenheit.
P4 – On Point The temperature at which a stage will turn on.
P5 – Off Point The temperature at which a stage will turn off.
P40 – HH.Net Address Unique setting for controllers along a single network wire pair.
Only used with the PC compatibility feature using Hired-
Hand’s Farm Manager software.
P41 – Software Version This is the version of the software for the controller. This value
is not settable.
P42 -- Controller Setup This is a number that identifies the type of controller (4 Stage
Controller) to the Farm Manager Software (PC compatible)
PS1 - Calibrate Sensor 1 The temperature the controller reads from Sensor 1. This
setting is used only when calibrating sensors. Press the +
and/or - buttons until the correct reading is seen in the main
display. (See Sensor Calibration)
PS2 - Calibrate Sensor 2 The temperature the controller reads from Sensor 2. This
setting is used only when calibrating sensors. Press the +
and/or - buttons until the correct reading is seen in the main
display. (See Sensor Calibration)
PS3 - Calibrate Sensor 3 The temperature the controller reads from Sensor 3. This
setting is used only when calibrating sensors. Press the +
and/or - buttons until the correct reading is seen in the main
display. (See Sensor Calibration)
PS4 - Calibrate Sensor 4 The temperature the controller reads from Sensor 4. This
setting is used only when calibrating sensors. Press the +
and/or - buttons until the correct reading is seen in the main
display. (See Sensor Calibration)
10.1 Error Codes
10.1.1 Sensor Errors
If the controller is displaying an “E1”, or “E2”, etc. the controller has recorded an
error. The controller records errors from sensor readings, and from the local
network if connected. To diagnose a controller problem, look up the error on the
table (under “Error Codes”) and look across the table to find the components that
have failed. (Items with an “x” have failed according to the controller.)
Part No. 4801-5129 rev 6-04 Farm Hand Heat Zone 18
Error Sensor 1 Sensor 2 Sensor 3 Sensor 4
Code Description Error Error Error Error
E1 Sensor 1 Error X
E2 Sensor 2 Error X
E3 Sensor 1 & 2 Error XX
E4 Sensor 3 Error X
E5 Sensor 1 & 3 Error XX
E6 Sensor 2 & 3 Error XX
E7 Sensor 1, 2 & 3 Error XXX
E8 Sensor 4 Error X
E9 Sensor 1 & 4 Error XX
E10 Sensor 2 & 4 Error XX
E11 Sensor 1, 2 & 4 Error XX X
E12 Sensor 3 & 4 Error XX
E13 Sensor 1, 3 & 4 Error XXX
E14 Sensor 2, 3 & 4 Error XXX
E15 Sensor 1, 2, 3 & 4 Error XXXX
Note: If a sensor is in error the display will show "- - -" and the actual temperature
loaded into the sensors register will be 130 F. This insures that the heat stage will
not be allowed to operate until the sensor is corrected.
10.1.2 Possible Solutions
Sensor Error
If any of the sensors are bad try the following:
Reset the controller by taking power away at the breaker, or unplugging it.
Determine which sensor is bad, then check the connection inside the controller door.
Determine which sensor is bad, then check the sensor that is hanging in the house to
make sure that it has not been damaged.
Check the wire going to the sensor(s) to be sure there are no staples through the
wires.
Replace the bad sensor.
10.1.3 Local Network Errors
If the display flashes “LnE” it indicates that there is a Local Network Error. If you
are attached to the Vent Master 24 via the Local Network connection there is a
communications problem. Report this problem to your local dealer.
If you are using the Heat Zone as a stand-alone controller with no Local Network
Connection, you can disable this error code by setting P40 to an address between 8
and 32.
/