Eaton CurrentWatch EGF Series Owner's manual

Type
Owner's manual

This manual is also suitable for

WARNING!
IN ORDER TO AVOID ELECTRIC SHOCK OR OTHER POSSIBLE INJURY:
• DO NOT USE THIS PRODUCT FOR HUMAN SAFETY APPLICATIONS. IT
WAS NOT DESIGNED, TESTED, OR RECOMMENDED FOR THIS USE.
• DO NOT USE THIS PRODUCT IN HAZARDOUS LOCATIONS (E.G.
EXPLOSIVE ATMOSPHERES). IT WAS NOT DESIGNED, TESTED, OR
RECOMMENDED FOR THIS USE.
• ENSURE THE PRODUCT IS PROPERLY WIRED TO THE CORRECT POWER
SUPPLY FOR THE APPLICATION. REFER TO THE SPECIFICATIONS AND
WIRING DIAGRAMS IN THIS PUBLICATION.
Models Covered In This Publication
Catalog Number Description
EGF1SPDTDE050 120 VAC, SPDT Form C, 50 mA Setpoint, Normally De-Energized
EGF1SPDTNE050 120 VAC, SPDT Form C, 50 mA Setpoint, Normally Energized
Catalog Number Description
EGF1SPDTDE100 120 VAC, SPDT Form C, 100 mA Setpoint, Normally De-Energized
EGF1SPDTNE100 120 VAC, SPDT Form C, 100 mA Setpoint, Normally Energized
EGF1SPDTDET3 120 VAC, SPDT Form C, 5/10/30 mA Setpoint, Normally
De-Energized
EGF1SPDTNET3 120 VAC, SPDT Form C, 5/10/30 mA Setpoint, Normally
Energized
EGF2SPDTDE050 24 VAC/DC, SPDT Form C, 50 mA Setpoint, Normally
De-Energized
EGF2SPDTNE050 24 VAC/DC, SPDT Form C, 50 mA Setpoint, Normally Energized
EGF2SPDTDE100 24 VAC/DC, SPDT Form C, 100 mA Setpoint, Normally
De-Energized
EGF2SPDTNE100 24 VAC/DC, SPDT Form C, 100 mA Setpoint, Normally Energized
EGF2SPDTDET3 24 VAC/DC, SPDT Form C, 5/10/30 mA Setpoint, Normally
De-Energized
EGF2SPDTNET3 24 VAC/DC, SPDT Form C, 5/10/30 mA Setpoint, Normally
Energized
CurrentWatch™ EGF Series Ground Fault Sensors
120V AC or 24V AC/DC, SPDT Form C
Relay with Auto-Reset
Instructions Publication P51924
Effective July 2017
Supersedes March 2014
Instruction Leaflet
Montageanweisung
Notice d’installation
Instrucciones de montaje
Istruzioni per il montaggio
安装
Инструкция по монтажу
Montagehandleiding
Montagevejledning
Οδηγίες εγκατάστασης
Instruções de montagem
Monteringsanvisning
Asennusohje
Návod k montáži
Paigaldusjuhend
Szerelési utasítás
Montāžas instrukcija
Montavimo instrukcija
Instrukcja montażu
Navodila za montažo
Návod na montáž
Монтажни инструкции
Instrucţiuni de montaj
Upute za montažu
Electric current! Danger to life!
Only skilled or instructed persons may
carry out the following operations.
Lebensgefahr durch elektrischen Strom!
Nur Elektrofachkräfte und elektrotechnisch
unterwiesene Personen dürfen die im Folgenden
beschriebenen Arbeiten ausführen.
Tension électrique dangereuse !
Seules les personnes qualifiées et averties doivent
exécuter les travaux ci-après.
¡Corriente eléctrica! ¡Peligro de muerte!
El trabajo a continuación descrito debe ser realizado
por personas cualificadas y advertidas.
Tensione elettrica: Pericolo di morte!
Solo persone abilitate e qualificate possono eseguire
le operazioni di seguito riportate.
触电
只允许专业人员和受过专业训练的人员进行下列工作。
Электрический ток! Опасно для жизни!
Только специалисты или проинструктированные
лица могут выполнять следующие операции.
Levensgevaar door elektrische stroom!
Uitsluitend deskundigen in elektriciteit en
elektrotechnisch geïnstrueerde personen is het
toegestaan, de navolgend beschreven
werkzaamheden uit te voeren.
Livsfare på grund af elektrisk strøm!
Kun uddannede el-installatører og personer der
e instruerede i elektrotekniske arbejdsopgaver,
må udføre de nedenfor anførte arbejder.
en
de
fr
es
it
zh
ru
nl
da
Προσοχή, κίνδυνος ηλεκτροπληξίας!
Οι εργασίες που αναφέρονται στη συνέχεια θα
πρέπει να εκτελούνται μόνο από ηλεκτρολόγους
και ηλεκτροτεχνίτες.
Perigo de vida devido a corrente eléctrica!
Apenas electricistas e pessoas com formação
electrotécnica podem executar os trabalhos
que a seguir se descrevem.
Livsfara genom elektrisk ström!
Endast utbildade elektriker och personer som
undervisats i elektroteknik får utföra de arbeten
som beskrivs nedan.
Hengenvaarallinen jännite!
Vain pätevät sähköasentajat ja opastusta saaneet
henkilöt saavat suorittaa seuraavat työt.
Nebezpečí úrazu elektrickým proudem!
Níže uvedené práce smějí provádět pouze
osoby s elektrotechnickým vzděláním.
Eluohtlik! Elektrilöögioht!
Järgnevalt kirjeldatud töid tohib teostada ainult
elektriala spetsialist vői elektrotehnilise
instrueerimise läbinud personal.
Életveszély az elektromos áram révén!
Csak elektromos szakemberek és elektrotechnikában
képzett személyek végezhetik el a következőkben leírt
munkákat.
Elektriskā strāva apdraud dzīvību!
Tālāk aprakstītos darbus drīkst veikt tikai
elektrospeciālisti un darbam ar elektrotehniskām
iekārtām instruētās personas!
el
pt
sv
fi
cs
et
hu
lv
Pavojus gyvybei dėl elektros srovės!
Tik elektrikai ir elektrotechnikos specialistai gali
atlikti žemiau aprašytus darbus.
Porażenie prądem elektrycznym stanowi
zagrożenie dla życia!
Opisane poniżej prace mogą przeprowadzać tylko
wykwalifikowani elektrycy oraz osoby odpowiednio
poinstruowane w zakresie elektrotechniki.
Življenjska nevarnost zaradi
električnega toka!
Spodaj opisana dela smejo izvajati samo
elektrostrokovnjaki in elektrotehnično poučene osebe.
Nebezpečenstvo ohrozenia života
elektrickým prúdom!
Práce, ktoré sú nižšie opísané, smú vykonávat’
iba elektroodborníci a osoby s elektrotechnickým
vzdelaním.
Опасност за живота от електрически ток!
Операциите, описани в следващите раздели,
могат да се извършват само от
специалисти-електротехници и инструктиран
електротехнически персонал.
Atenţie! Pericol electric!
Toate lucrările descrise trebuie efectuate numai
de personal de specialitate calificat şi de persoane
cu cunoştiinţe profunde în electrotehnică.
Opasnost po život uslijed električne struje!
Radove opisane u nastavku smiju obavljati samo
stručni električari i osobe koje su prošle
elektrotehničku obuku.
lt
pl
sl
sk
bg
ro
hr
490031420
Introduction
The CurrentWatch™ EGF Series is a family of
ground fault (earth leakage) sensors. Ground
fault sensors help protect people, products,
and processes from damage by ground fault
conditions by monitoring all current-carrying
conductors in grounded single- and three-
phase delta or wye systems.
The EGF Series with mechanical outputs are
available in solid-core housings with a choice
of Normally Energized or Normally De-Energized SPDT relays. All
mechanical models can be ordered with a fixed setpoint or with a
“tri-set” option, which provides three factory-set, field adjustable
setpoints.
ote:N This manual only covers EGF Series models with SPDT relays (listed
in the table on page 1). For installation manuals covering other models in the
EGF Series family, please contact Eaton’s Sensor Application Engineers.
Quick Install Guide
The below steps can be followed to quickly install a CurrentWatch
EGF Series switch.
1. Run all current carrying conductors through sensor window,
using an auxiliary current transformer if conductors do not fit.
2. Mount the sensor to a surface if needed.
3. Connect output and power wiring:
a. Use up to 14 AWG copper wires,
b. Ensure power and load matches those shown on the sensor
label.
4. Test the unit:
a. Pressing the “TEST” button will test the sensor’s internal
circuits,
b. CAUTION: The output and any connected loads will
switch during the test process.
Installation
Considerations for all EGF Series sensors…
Run wire to be monitored through the aperture (opening) in the
switch body, making sure all wires are oriented so that current
flows in the same direction (see “Principal of Operation” section
on this page).
These sensors can be located in the same environment as
motors, contactors, heaters, pull-boxes, and other electrical enclo-
sures.
Mounting can be done in any position or hung directly on a wire
with a wire tie.
Be sure to leave at least one in. (25.4 mm) distance between sen-
sor and other magnetic devices.
Connect power and output wiring using up to 14 AWG copper
wire and tightening terminals to 4.5 in.-lbs / 0.51 N·m maximum
torque.
Principle of Operation
Under normal conditions, the current in one wire of a two wire load
is equal in strength but opposite in sign to the current in other wire.
The two wires create magnetic fields that cancel, a condition known
as “Zero Sum Current.” If any current leaks to ground (Ground Fault),
the two currents become unbalances and there is a net resulting
magnetic field. The EGF Series sensor detects this minute field and
change the output state. This concept extends to 3- phase systems
such as 3-wire Delta and to 4-wire Wye.
Power
Output
Power
Interupt
A
B
C
N
3 W
ye Power
3 Load
Power
Output
Power
Interupt
HOT
NEUT
1 Power
1 Load
Power
Output
Power
Interupt
A
B
3 Power
1 Load
Power
Output
Power
Interupt
A
B
C
3 Delta Power
3 Load
Wiring
Run all current carrying conductors through the sensor aperture in
the same direction. Connect power wiring to the sensor. Be sure
the power supply matches the power rating on the sensor label. Use
up to 14 AWG copper wire and tighten terminals to 4.5 in.-lbs / 0.51
N·m maximum torque. Connect output wiring to the sensor. Be sure
that the output load is less than or equal to the output rating on the
sensor label. Use up to 14 AWG copper wire and tighten terminals
to 4.5 in.-lbs / 0.51 N·m maximum torque.
Power
Output
G
X
Control Power
(Match Sensor Rating, See Label)
Setpoint Adjust
All Models Except Those Ending -T3:
Factory
calibrated and covered. Remove
cover, adjust and relabel if required.
Models Ending -T3:
Move jumper to select setpoint.
TEST
Power Status
R
1
2
3
4
5
Load
Contactor, Relay, Shunt Trip Breaker
(Do Not Exceed Rating, See Label)
Output Power
(Match Sensor Rating, See Label)
2
EATON www.eaton.com
CurrentWatch™ EGF Series Ground Fault Sensors
120V AC or 24V AC/DC, SPDT Form C
Relay with Auto-Reset
Instructions Publication P51924
Effective July 2017
Operation
To test operation, gently press the TEST button. This simulates a
fault and tests the internal switching circuits. The following operation
should be observed.
CAUTION: Any circuit connected to the sensor will be operated.
Normally Energized Models
Used for detecting ground faults and loss of control power.
Output
No Power
Control Power Applied
No Fault Fault Detected
Output LED Output LED Output LED
N.C. Closed Off Open Off Closed On
N.O. Open Off Closed Off Open On
Normally De-Energized Models
Used for detecting ground faults only.
Output
No Power
Control Power Applied
No Fault Fault Detected
Output LED Output LED Output LED
N.C. Closed Off Closed Off Open On
N.O. Open Off Open Off Closed On
Setpoint Adjustment
The EGF Series sensors are factory calibrated to trip at the setpoint
specified by the model number. While it is generally recommended
not to change this setpoint, it can be done by following the below
steps.
1. Connect control power and circuits. Run a conductor through the
aperture with current equal to your desired setpoint.
2. Adjust setpoint to maximum by first removing the setpoint cover.
Turn the adjustment pot five revolutions counter-clockwise to the
maximum (least sensitive) setpoint. The Status LED should be
off. The adjustment pot has a slip clutch so that you cannot feel
or damage the end point.
3. Dial in the new setpoint by slowly turning the pot clockwise until
the LED turns on. The sensor is now adjusted to trip at the cur-
rent that is passing through the aperture. Reset the sensor.
4. Relabel the sensor with a new setpoint. Use a label maker or
tape with a permanent marker.
Power Supply Notes
All low-current ground-fault sensors are sensitive devices that
require reasonable care in system design to avoid false trips caused
by high electrical noise levels. Keep in mind that the best way to
reduce noise in a system is to suppress it at its source.
Keep the sensor power isolated from noisy circuits.
Do not power the sensor with the same circuit that switches con-
tactors or other high current inductive loads.
System Grounding
Good design practice and code require that all AC power systems
be grounded. The EGF Series sensors are designed to work on
grounded AC power systems. They may not operate properly on
ungrounded systems.
Specications
Specification Value
Power Supply 120 VAC (Operates from 66-132)
24 VAC/DC (24 VAC ± 15%, 24 VDC ± 20%)
Voltage Range Up to 1,500 VAC (Monitored Circuit)
Power Consumption 2.5 W
Output SPTD Relay (Form C)
Output Rating 1.0 A @ 120 VAC
2.0 A @ 30 VDC
Response Time At 5% Over Setpoint: 150 ms
At 50% Over Setpoint: 100 ms
Setpoint Range Selectable by Model
Fixed Setpoints: 50, 100 mA
Adjustable Setpoints: 5, 10, 30 mA (By Jumper)
Setpoint Adjustment See “Setpoint Adjustment” Section
Frequency Range 50-400 Hz (Monitored Circuit)
Housing UL94 V0 Flammability Rated
Dimensions Case: 2.5 in. H x 2.8 in. W x 1.5 in. D (64 x 71 x 38 mm)
Aperture: 0.75 in. (19 mm)
LED Green = Power Supply Energized
Red = Relay Has Operated
Environmental Operating Temperature: +5 to +158°F (-15 to +70°C)
Humidity: 0-95% RH, Non-Condensing
Approvals UL Recognized, E313337
CE
RoHs Compliant
3
EATON www.eaton.com
Instructions Publication P51924
Effective July 2017
CurrentWatch™ EGF Series Ground Fault Sensors
120V AC or 24V AC/DC, SPDT Form C
Relay with Auto-Reset
Eaton Industries GmbH
Hein-Moeller-Straße 7-11,
53115 Bonn, Germany
Eaton Corporation
W126 N7250 Flint Drive
Menomonee Falls,
WI 53051, USA
Contact your regional Eaton oce for additional technical support
Eaton is a registered trademark of
Eaton Corporation.
All other trademarks are property
of their respective owners.
Americas – Asia Pacic Europe – Middle East – Africa
Eaton Corporation
Electrical Sector – Sensors
+1.800.426.9184
www.eaton.com/sensors
Eaton Industries GmbH
Electrical Sector EMEA
+49 (0) 180 5 223822
www.eaton.eu/sensors
© 2017 by Eaton
All Rights Reserved
Printed in USA
Publication No. P51924 / 004
July 2017
CurrentWatch™ EGF Series Ground Fault Sensors
120V AC or 24V AC/DC, SPDT Form C
Relay with Auto-Reset
Instructions Publication P51924
Effective July 2017
Eaton Industries GmbH
Hein-Moeller-Straße 7-11,
53115 Bonn, Germany
Eaton
W126 N7250 Flint Drive
Menomonee Falls,
WI 53051, USA
Eaton
Electrical Sector – Sensors
+1.800.426.9184
www.eaton.com/sensors
Eaton Industries GmbH
Electrical Sector EMEA
+49 (0) 180 5 223822
www.eaton.eu/sensors
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Contact your regional Eaton office for additional technical support
Americas – Asia Pacific Europe – Middle East – Africa
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Eaton CurrentWatch EGF Series Owner's manual

Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI