MULTIPLEX Beverage Conduit Owner Instruction Manual

Type
Owner Instruction Manual
Installation, Use & Care Manual
This manual is updated as new information and models are released.
Visit our website for the latest manual. www.manitowocfsg.com
America’s Quality Choice in Refrigeration
Beverage Conduit
Beer & Soda
Part Number EI211017 10/11
We reserve the right to make product improvements at any time.
Specifications and design are subject to change without notice.
Safety Notices
As you work on Manitowoc equipment, be sure to pay
close attention to the safety notices in this manual.
Disregarding the notices may lead to serious injury and/
or damage to the equipment.
Throughout this manual, you will see the following types
of safety notices:
Procedural Notices
As you work on Manitowoc equipment, be sure to read
the procedural notices in this manual. These notices
supply helpful information which may assist you as you
work.
Throughout this manual, you will see the following types
of procedural notices:
NOTE: Text set off as a Note provides you with simple,
but useful, extra information about the procedure you
are performing.
Read These Before Proceeding:
NOTE: SAVE THESE INSTRUCTIONS.
!
Warning
Text in a Warning box alerts you to a potential
personal injury situation. Be sure to read the
Warning statement before proceeding, and work
carefully.
!
Caution
Text in a Caution box alerts you to a situation in
which you could damage the equipment. Be sure to
read the Caution statement before proceeding, and
work carefully.
Important
Text in an Important box provides you with
information that may help you perform a procedure
more efficiently. Disregarding this information will not
cause damage or injury, but it may slow you down as
you work.
!
Caution
Proper installation, care and maintenance are
essential for maximum performance and trouble-free
operation of your Manitowoc equipment. Read and
understand this manual. It contains valuable care
and maintenance information. If you encounter
problems not covered by this manual, do not
proceed, contact Manitowoc. We will be happy to
provide assistance.
Important
Routine adjustments and maintenance procedures
outlined in this manual are not covered by the
warranty.
!
Warning
PERSONAL INJURY POTENTIAL
Do not operate equipment that has been misused,
abused, neglected, damaged, or altered/modified
from that of original manufactured specifications.
Part Number EI211017 10/11 i
Table of Contents
Section 1
General Information
Read This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Model Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Flame & Smoke Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Specification Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Shipping, Storage, & Relocation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Section 2
Installation
Pre-installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
REQUIRED TOOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
UNPACKING & INSPECTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Kitchen Equipment Installer Representative Responsibilities . . . . . . . . . . . 2-1
Other Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Installer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Routing Multiplex Conduit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
FLOOR CHASES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Sealing Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
OVERHEAD INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
How To Connect The Multiplex Conduit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Conduit Identification Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
COLOR AND NUMBER CODING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
TEEING INTO MULTIPLEX CONDUIT SODA SYSTEMS . . . . . . . . . . . . . 2-7
Soda Conduit Kit Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Beermaster Beer Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
FLOOR CHASES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
OVERHEAD INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
BASEMENT CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Connecting Beer Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Table of Contents (continued)
ii Part Number EI211017 10/11
Beermaster Conduit Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Beermaster Conduit Kit Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
INSTALLING THE CONDUIT KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
BEER RESTRICTOR LINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Section 3
Operation
Section 4
Maintenance
Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Periodic Maintenance Listed By Major Components . . . . . . . . . . . . . . . . . . 4-1
Periodic Maintenance Listed By Scheduled Frequency . . . . . . . . . . . . . . . 4-2
Cleaning & Sanitizing The Dispensing Valves & Product Lines . . . . . . . . . 4-3
Cleaning Equipment and Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Beverage System Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Bag-In-Box System Sanitation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Figal Beverage System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Shipping, Storage and Relocation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Section 5
Before Calling for Service
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Soda Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
No syrup or insufficient syrup in finished drink . . . . . . . . . . . . . . . . . . . . . . 5-1
No carbonated water or insufficient carbonated water in finished drink . . . 5-2
No water or insufficient water in finished drinks . . . . . . . . . . . . . . . . . . . . . 5-2
Beermaster Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Part Number EI211017 10/11 1-1
Section 1
General Information
Read This Manual
Manitowoc Beverage Systems developed this manual as
a reference guide for the owner/operator and installer of
this equipment. Please read this manual before
installation or operation of the machine. A qualified
service technician must perform installation and start-up
of this equipment.
If you cannot correct the service problem, call your
Manitowoc Beverage Systems (MBS) Service Agent or
Distributor. Always have your model and serial number
available when you call.
Your Service Agent ____________________________
Service Agent Telephone Number_________________
Your Local MBE Distributor ______________________
Distributor Telephone Number____________________
Model Number _______________________________
Serial Number ________________________________
Installation Date ______________________________
Unit Inspection
Thoroughly inspect the unit upon delivery. Immediately
report any damage that occurred during transportation to
the delivery carrier. Request a written inspection report
from a claims inspector to document any necessary
claim.
Model Numbers
This manual covers the following models:
DO Adhere to all National and Local Plumbing and
Electrical Safety Codes.
DO Turn “off” incoming electrical service switches
when servicing, installing, or repairing
equipment.
DO Check that all flare fittings are tight. This check
should be performed with a wrench to ensure a
quality seal.
DO Inspect pressure on Regulators before starting
up equipment.
DO Protect eyes when working around
refrigerants.
DO Use caution when handling metal surface
edges of all equipment.
DO Handle CO
2 cylinders and gauges with care.
Secure cylinders properly against abrasion.
DO Store CO
2 cylinder(s) in well ventilated areas.
DO NOT Exhaust CO
2 gas (example: beer pump)
into an enclosed area, including all types of
walk in coolers, cellars, and closets.
DO NOT Throw or drop a CO
2 cylinder. Secure the
cylinder(s) in an upright position with a chain.
DO NOT Connect the CO
2 cylinder(s) directly to the
product container. Doing so will result in an
explosion causing possible death or injury.
Best to connect the CO
2 cylinder(s) to a
regulator(s).
DO NOT Store CO
2 cylinders in temperature above
125°F (51.7°C) near furnaces, radiator or
sources of heat.
DO NOT Release CO
2 gas from old cylinder.
DO NOT Touch Refrigeration lines inside units, some
may exceed temperatures of 200°F (93.3°C).
NOTE: All utility connections and fixtures shall be sized,
installed and maintained in accordance with Federal,
State, and Local codes.
!
Warning
PERSONAL INJURY POTENTIAL
Do not operate equipment that has been misused,
abused, neglected, damaged, or altered/modified
from that of original manufactured specifications.
Beverage Conduit Models
MC095301, MC105301, MC105511, MC105521, MC105581,
MC125311, MC125511, MC125581, MC133301, MC135321,
MC145511, MC145351, MC145521, MC145551, MC165322,
MC175201, MC205501, MC205301, MC205311, MC245301,
MC245501, MC023341, MC043341, MC063341, MC073341,
MC083341, MC103341, MC123341, MC143341, MC163341,
MC193341, MC203341, MC043342, MC053342, MC063342,
MC073342, MC083342, MC103342, MC123342, MC143342,
MC163342, MC193342, MC203342
!
Caution
To Avoid Serious Injury: Read the following
warnings before beginning an installation. Failure to
do so may result in possible death or serious injury.
General Information Section 1
1-2
Part Number EI211017 10/11
Flame & Smoke Rating
INSUL-TUBE® Pipe Insulation in wall thickness of 1" (25
mm) and below has a flame spread rating of 25 or less
and a smoke development rating of 50 or less as tested
by ASTM E 84 Method of Testing entitled: Surface
Burning Characteristics of Building Materials. Duct/
Plenum Applications INSUL-TUBE® is acceptable for
duct/plenum applications, meeting requirements of
NFPA 90A.
Numerical flammability ratings alone may not define the
performance of products under actual fire conditions.
They are provided only for use in the selection of
products to meet limits specified, when compared to a
known standard.
Specification Compliance
ASTM C 534 Type 1 (Tubing)
ASTM D 1056-00-2C1
ASTM C 1534-02
New York City MEA 186-86-M Vol. IV
USDA Requirements
UL 94-5V Flammability Classification (Recognition
No. E147665)
ASTM E 84 1" 25/50-tested according to UL 723 and
NFPA 255
Complies with requirements of CAN/ULC S102-M88
NFPA No. 101 Class A Rating
Meets requirements of NFPA 90A Sect. 2.3.3 for
Supplementary Materials for Air Distribution
Systems.
Meets requirements of ASTM C 411 (Tested Method
of Hot Surface Performance of High Temperature
Thermal Insulation).
Meets requirements of UL 181 sections 11.0 and
16.0 (Mold Growth/Air Erosion)
MIL-P-15280, For T (Tubing)
Warranty Information
Consult your local MBS Distributor for terms and
conditions of your warranty. Your warranty specifically
excludes all beverage valve brixing, general
adjustments, cleaning, accessories and related
servicing.
Your warranty card must be returned to MBS to activate
the warranty on this equipment. If a warranty card is not
returned, the warranty period can begin when the
equipment leaves the MBE factory.
No equipment may be returned to MBS without a written
Return Materials Authorization (RMA). Equipment
returned without an RMA will be refused at the MBS
dock and returned to the sender at the sender’s
expense.
Please contact your local MBS distributor for return
procedures.
Shipping, Storage, & Relocation
Store conduit in 60°F (15.5°C) to 80°F (16.6°C)
environment.
- Keep in a cool, dry location.
- Do not expose to direct sunlight.
- Do not store conduit outside the original carton.
- Do not store conduit for more than one year.
- Do not store anything directly on top of conduit.
- Do not store in an enclosed location with high
aromatic compounds.
- Conduit warranty is 2 years from date of
manufacture as printed on the conduit.
If you have any questions or concerns, please contact
the MBE Service Department at 800-367-4233.
Part Number EI211017 10/11 2-1
Section 2
Installation
Pre-installation
REQUIRED TOOLS
Steel Fish Tape
Length of Rope
•Duct Tape
Approved Tubing Cutters
Razor Blade Knife
Tab Clamp Pliers
UNPACKING & INSPECTING
Carefully inspect the conduit immediately upon unpacking.
Inspect conduit for any damages that may have occurred
during shipping.
Before installing conduit, be sure conduit is proper length for
installation, contains the correct number of lines for
connection, and all lines are proper diameter.
LOCATION REQUIREMENTS
Equipment
1. Determine the location where the Tower/Dispenser
will be installed.
2. Locate the mounting template provided with the
installation kit.
3. Using the mounting template as a guide, punch out
the required holes in the counter top.
KITCHEN EQUIPMENT INSTALLER REPRESENTATIVE RESPONSIBILITIES
Prior to scheduling Multiplex Equipment installer, the following steps listed below must be completed:
1. Usable floor sewer drain.
2. Refer to electrical requirement chart for your model.
3. Usable potable water.
4. CO
2
Gas (bulk or bottled supply); minimum 3/8" line.
5. One 5 gallon (19 L) container or Bag-In-Box
container of each post mix syrup flavor.
NOTE: Do not schedule the authorized Multiplex Equipment Installer until all of the above have been completed. It will
only result in charge-backs to you for the unnecessary trips.
OTHER REQUIREMENTS
Conduit can be run through floor or ceiling chase.
60°F (15.6°C) minimum and 105°F (40.5°C)
maximum operating ambient conditions.
For indoor installation only.
Syrup supply can be located on stand or adjacent to
refrigeration unit.
Installer Instructions
These equipment instructions are intended to assist
qualified personnel in the unpacking, locating and the
initial operation of the Multiplex Beverage Equipment
and/or Post Mix Refrigeration Unit.
!
Warning
Carbon Dioxide (CO
2
) displaces oxygen. Exposure to a high
concentration of CO
2
gas causes tremors, which are followed
rapidly by loss of consciousness and suffocation. If a CO
2
gas
leak is suspected, particularly in a small area, immediately
ventilate the area before repairing the leak. CO
2
lines and
pumps must not be installed in an enclosed space. An
enclosed space can be a cooler or small room or closet. This
may include convenience stores with glass door self serve
coolers. If you suspect CO
2
may build up in an area, venting of
the BIB pumps and/or CO
2
monitors must be utilized.
Important
Recommend conduit to min 75°F ambient temperature
before installing for ease of installation.
Installation Section 2
2-2
Part Number EI211017 10/11
Routing Multiplex Conduit
FLOOR CHASES
Before pulling Multiplex conduit through a floor chase,
ensure the floor chase contains the following:
8" Minimum PVC Conduit
Wide Sweep Elbows with a minimum 2 ft (61 cm) radius
Chase openings should extend 6" (15.2 cm) above floor
Chase must be clean and dry, no foreign materials
Pulling Conduit Through Floor Chase
1. Determine the most convenient way of routing conduit,
starting at the end which offers adequate room for
installation. The conduit installation process requires the
assistance of two (2) qualified personnel.
2. Locate steel fish tape and route through chase opening.
Route fish tape through entire chase until it appears at
opposite end.
3. Locate an appropriate length of rope and tie to end of fish
tape (end that was routed through chase in step 2).
Approximately 2 ft (61 cm) from steel fish tape/rope
connection, secure a swab to rope (use mop heads or
bundle of rags for swab).
4. Pull end of fish tape from starting point through chase with
rope and swab. The swab will sweep clean any
construction materials, moisture, or debris that may exist
in floor chase.
5. After floor chase has been cleaned, remove steel
fish tape and swab from rope. Locate bundle of
Multiplex conduit and uncoil conduit to allow
unrestricted feed during installation process.
6. Locate rope through chase opening and connect to
proper end of Multiplex conduit.
NOTE: Multiplex conduit is designed to be pulled
through a chase in the direction of arrows printed on
conduit (refer to figure 2).
7. After rope has been connected, tape end of conduit,
including rope, and form conduit end to a point.
Tape will ensure that no contaminants enter conduit
tubes during installation.
8. Place pointed end of Multiplex conduit through
chase opening. While one person pushes the
conduit through chase, another person should be
pulling conduit through chase with rope on opposite
end.
9. Once conduit has been routed through chase, pull
enough conduit through openings to ensure an
adequate supply at each end of chase for
connections.
SEALING INSTRUCTIONS
Refrigeration Unit
Dispensing Tower
8” (20.5 cm)
PVC Conduit
6” (15.2 cm)
Wide Sweep Elbows
2 ft (61cm) Radius
Figure 1
!
Caution
All objects and moisture must be removed from floor
chase before conduit can be routed. It may be necessary
to repeat this process to ensure floor chase is clean.
Figure 2
Section 2 Installation
Part Number EI211017 10/11 2-3
Aerosol foam is to be used to fill the openings between the
conduit insulation and the inside diameter of the floor
chases. The purpose is to provide an air tight seal at the floor
level to prevent foreign matter from entering the chases.
Please read the manufacturer’s instructions carefully.
1. If the opening is too deep, insert a section of the excess
conduit insulation in the opening prior to using the foam
insulation.
2. Make sure all exposed carbonated water and syrup
lines are well insulated: towers to conduit; conduit
junctions, remote unit to conduit; drive thru junction.
3. Use aluminum foil (if used), and tape, packed in the
inner pack carton to insulate these connections.
4. Cut the conduit sections to fit like a glove over the
exposed lines and fittings.
NOTE: A little extra time spent doing a professional job
initially will eliminate a call back in several days to make
corrections.
OVERHEAD INSTALLATION
1. Determine the correct location for routing Multiplex
conduit. Be sure to avoid heat ducts, hoods, grills, or any
sharp objects that may exist above drop ceiling tile.
(refer to figure 3)
2. Unspool Multiplex conduit to allow unrestricted feed.
3. Conduit hangers should be spaced no more than 6 ft
centers.
4. Route conduit above ceiling tiles and connect to ceiling
and/or pipes using the appropriate conduit hangers. Be
sure conduit is suspended above ceiling tiles. Concern
should be given when determining appropriate method
of hanging conduit securely. Hangers must not crush or
pinch insulation. This will reduce cooling efficiency.
Once conduit has been routed, ensure an adequate supply
of conduit is provided at each end to make all connections.
!
Warning
Do not inject foam material directly on the connections where
the tubing connects to the barb fittings.
Refrigeration Unit
Dispensing Tower
Ceiling Tiles
Conduit Hangers
Roof
Conduit Shroud
6” (15.2 cm)x 6” (15.2 cm)
Minimum
Figure 3
Installation Section 2
2-4
Part Number EI211017 10/11
BASEMENT CONSTRUCTION
1. Uncoil Multiplex conduit to allow unrestricted feed
during installation process.
2. Route the conduit up basement wall and secure with
appropriate conduit hangers.
3. Conduit hangers should be spaced no more than 6 ft centers
4. Route conduit above ceiling tiles and connect to
ceiling and/or pipes using the appropriate conduit
hangers. Be sure conduit is suspended above
ceiling tiles. Concern should be given when
determining appropriate method of hanging conduit
securely. Hangers must not crush or pinch
insulation. This will reduce cooling efficiency.
Once conduit has been routed, ensure an adequate
supply of conduit is on hand to make all connections.
How To Connect The Multiplex Conduit
NOTE: Conduit lines should be long enough to allow
adequate work space when servicing equipment.
All Multiplex conduit syrup lines, carbonated water lines,
and the plain water line are coded for quick identification
and easy installation.
1. Locate the lines of Multiplex conduit routed at
refrigeration unit and dispensing tower.
2. Using an approved razor knife, cut Multiplex conduit
insulation by slicing along top side while peeling
insulation back at the same time.
3. For soda systems, connect each syrup line, carbonated
water line, and plain water line to the appropriate stainless
steel coil in refrigeration unit. For Glycol systems,
connect to bulkhead fittings.
NOTE: Stainless steel cooling coils in our refrigeration units
may contain either barb fittings or John Guest fittings,
depending on model. Before connecting conduit, identify
whether the conduit is thick wall or thin wall tubing (see
illustration). Thick wall tubing should only be used with barb
stem fittings. John Guest fittings can only be used with thin
wall tubing
Dispensing Tower
Conduit Hangers
Basement Ceiling
Refrigeration Unit
Figure 4
!
Caution
Don't crush or pinch conduit insulation with hangers.
!
Caution
Only an approved cutting tool should be used to cut
polyethylene tubing. Use a new blade so that the tubing will
not be crushed when cutting.
Razor KnifeButterfly Cutter
Figure 5
Thick Wall Tubing
1/2" x 0.083 W
3/8" x 0.062 W 1/4" x 0.062 W1/2" x 0.062 W
NOTE: Shown actuall size.
Figure 6
Section 2 Installation
Part Number EI211017 10/11 2-5
CONDUIT IDENTIFICATION CHART
When suspending Multiplex conduit with conduit hangers, the maximum allowable distance between hangers is 6 ft (1.82 m).
If ambient temperature of the conduit location is 90ºF (32.2ºC) or above, double insulated conduit must be utilized.
COLOR AND NUMBER CODING
Figure 7
I.D. Size of
Tube / Hose
Number Color Suggested Use Tab Clamp Size
1/4” Tube
S1 White Syrup 10.5
S2 Black
S3 Orange
S4 Red
S5 Blue
S6 Green
S7 Purple
S8 Brown
S9 Pink
S10 Yellow
S11 White
S12 Black
S13 Orange
S14 Red
S15 Blue
S16 Green
3/8” Tube
AF Red Water / Glycol 13.8
AR Red
BF Blue
BR Blue
S1 White Syrup / Beer 13.8
S2 Black
S3 Orange
S4 Red
S5 Blue
S6 Green
S7 Purple
S8 Brown
S9 Pink
S10 Yellow
S11 White
S12 Black
S13 Orange
S14 Red
S15 Blue
S16 Green
I.D. Size of
Tube / Hose
Number Color Suggested Use Tab Clamp Size
Installation Section 2
2-6
Part Number EI211017 10/11
Product suggestions for conduit tubing
Current conduit tubing is PTE lined. Therefore it is no
longer necessary to make sure pungent flavors are used
with specific tubing. Keeping with that process, when
connecting conduit to syrup boxes and valves, the best
flavor/tubing selection would be to utilize line number S1
for valve number 1, S2 for valve number 2, etc.
1/2” Tube
VS1 Orange
High Viscous
Syrup
17
VS2 Natural
VS3 Green
VS4 White
VS5 Black
VS6 Red
VS7 Blue
VS8 Purple
VS9 Brown
VS10 Pink
VS11 Yellow
VS12 Purple
1/2” Hose
AF Blue Water / Glycol 18.5
AR Blue
BF Yellow
BR Yellow
WF Black
WR Black
1/4” Tube
S1 White Syrup 10.5
S2 Black
S3 Orange
S4 Red
S5 Blue
S6 Green
S7 Purple
S8 Brown
S9 Pink
S10 Yellow
S11 White
S12 Black
S13 Orange
S14 Red
S15 Blue
S16 Green
I.D. Size of
Tube / Hose
Number Color Suggested Use Tab Clamp Size
3/8” Tube
AF Red Water / Glycol 13.8
AR Red
BF Blue
BR Blue
S1 White Syrup / Beer 13.8
S2 Black
S3 Orange
S4 Red
S5 Blue
S6 Green
S7 Purple
S8 Brown
S9 Pink
S10 Yellow
S11 White
S12 Black
S13 Orange
S14 Red
S15 Blue
S16 Green
1/2” Tube
VS1 Orange
High Viscous
Syrup
17
VS2 Natural
VS3 Green
VS4 White
VS5 Black
VS6 Red
VS7 Blue
VS8 Purple
VS9 Brown
VS10 Pink
I.D. Size of
Tube / Hose
Number Color Suggested Use Tab Clamp Size
Section 2 Installation
Part Number EI211017 10/11 2-7
FITTINGS
Barb Stem Fittings
1. Moisten barbed fittings with warm water.
2. Connect appropriate lines to barbed fittings and secure
with two (2) tab clamps. Tab clamps should be
staggered when connecting (refer to figure 7).
3. Once the end of each line has been cut, lubricate with
water and insert line into John Guest Fitting. Be sure the
tubing is inserted firmly through O-ring in John Guest
fitting.
4. Connect each syrup line, carbonated water line, and
plain water line to the appropriate connection in
dispensing tower. Secure with two (2) tab clamps. If
tower has barbs, a John Guest adapter stem should be
used when connecting to a conduit with John
John Guest Fittings
NOTE: Connections in dispensing towers may contain
either barb stem fittings or John Guest fittings. See
previous section for proper instruction.
TEEING INTO MULTIPLEX CONDUIT SODA SYSTEMS
1. Locate the section in main conduit where tee
connections are to be made. Measure a 12" (30.5
cm) area in the designated section.
2. Using a razor knife, cut a “X” pattern in designated
section as shown in figure 8. Peel back the ends of foam
insulation and identify each syrup line and water line
located in conduit. Be careful not to cut lines inside
conduit. Even a small “nick” will result in leaks.
3. Using a tubing cutter, cut each syrup line (one [1]
line at a time) in main conduit. Locate barbed tees in
conduit tee kit, connect to each syrup and water line.
Secure with two tab clamps (refer to figure 11).
4. Locate the section of tee conduit. Using a razor
knife, slice foam insulation in a straight line on top
side of conduit. Pull back foam insulation and locate
each syrup line (refer to figure 12).
5. Connect each syrup line in a tee conduit to the
appropriate barbed tee connected to the syrup lines
in the main conduit. Secure with two (2) tab clamps
(refer to figure 11). Be sure to tee line markings
corresponding to the main conduit markings.
Figure 7
Figure 8
1. Before inserting appropriate conduit lines to John
Guest fittings, ensure that the end of each line is
cut square at a 90° angle.
Figure 10
Figure 11
Figure 12
Installation Section 2
2-8
Part Number EI211017 10/11
6. Locate carbonated water lines in main conduit and
cut using tubing cutter. Locate barbed “Ell” fitting
provided in kit and connect to carbonated water
lines (refer to figure 13).
7. Connect the carbonated water lines in tee conduit to
the appropriate barbed ells connected to carbonated
water lines in main conduit. Secure with two tab
clamps (refer to figure 14).
NOTE: The number of carbonated water lines will vary
depending on the model of the refrigeration unit.
8. Pull the sliced sections of foam insulation back over
openings where connections were made. Using
cloth tape, tape over openings and seal air tight.
9. After ensuring there are no leaks at conduit
connections, wrap foam insulation tape around the
sliced sections and insulate the Multiplex conduit
completely. This is very important to prevent
condensation and loss efficiency.
10. Seal each chase opening by spraying foam
insulation into each end of chase opening. This will
reduce risk of contamination of conduit in chase.
Figure 13
Figure 14
Section 2 Installation
Part Number EI211017 10/11 2-9
SODA CONDUIT KIT DIAGRAMS
Single Circulation Pump - One Circuit
REFRIGERATION UNIT
CIRC.
PUMP
HEAT EXCHANGER
BLUE
TOWER 1
TOWER 2
BLUE
CONDUIT CONDUIT TEE
CARB
TANK
Figure 15
Single Circulation Pump - Two Circuit
REFRIGERATION UNIT
CIRC.
PUMP
HEAT EXCHANGER
CARB
TANK
CONDUIT CONDUIT TEE
TOWER 1
TOWER 2
BLUE
BLUE
YELLOW
YELLOW
Two Circulation Pump - Two Circuit
REFRIGERATION UNIT
CIRC.
PUMP
HEAT EXCHANGER
CARB
TANK
CIRC.
PUMP
HEAT EXCHANGER
CARB
TANK
CONDUIT CONDUIT TEE
TOWER 1
TOWER 2
BLUE
BLUE
YELLOW
YELLOW
Installation Section 2
2-10
Part Number EI211017 10/11
Beermaster Beer Conduit
INTRODUCTION
The following instructions will provide information for installing Multiplex/Multiplex Beer Conduit with your Beermaster System.
Areas which will be covered include routing the conduit for different bar set-ups, connecting the conduit at the Beermaster
Glycol Chiller, connecting the conduit at the beer cooler, and connecting the conduit at the dispensing stations.
FLOOR CHASES
Before pulling beer conduit through a floor chase, ensure the floor chase contains the following (see Figure 1)
6" (minimum) PVC conduit chase
Wide sweep elbows (2 ft radius)
Chase openings should extend 6" above floor
Chase must be clean and dry–no foreign materials
Pulling conduit through floor chase
1. Determine the most convenient way of routing conduit,
starting at the end which offers adequate room for
installation. The conduit installation process requires the
assistance of at least two (2) qualified personnel.
2. Route the steel fish tape through chase opening. Push
fish tape through entire chase until it appears at
opposite end.
3. Locate an appropriate length of rope and tie to end of
fish tape (end which was routed through chase in step
2). Approximately 2 ft from steel fish tape/rope
connection, secure a swab to rope (use mop heads or a
bundle of rags for swab).
4. Pull end of fish tape from starting point through chase
with rope and swab. The swab will clean any
construction materials, moisture, or debris that may exist
in floor chase. Continue to swab the chase until the
swab exits the chase clean and dry.
5. After floor chase has been cleaned, remove steel fish
tape and swab from rope. Locate bundle of beer conduit
and unspool conduit to allow unrestricted feed during
installation process.
6. Locate rope through floor chase opening and connect to
proper end of beer conduit.
NOTE: The beer conduit is designed to be pulled through
floor chase in the direction of arrows printed on conduit.
7. After rope has been connected, tape end of conduit,
including rope, and form conduit end to a point (see
Figure 2). Tape will ensure that no contaminants enter
conduit tubes during installation.
8. Place pointed end of the conduit through chase
opening. While one person pushes the conduit through
chase, another person should be pulling the conduit
through the chase with rope at the opposite end.
9. Once the conduit has been routed through the chase,
pull enough conduit through the openings to ensure an
adequate supply at each end of the chase for
connections.
Beermaster
Refrigeration Unit
Dispensing
Station
Beer Conduit
6” PVC
Conduit Chase
Wide Sweep Elbows
2 ft Radius
Walk-In Cooler
Figure 1
Figure 2
Section 2 Installation
Part Number EI211017 10/11 2-11
OVERHEAD INSTALLATION
Refer to Figure 3 for the following:
1. Determine the correct location for routing the beer
conduit. Be sure to avoid heat ducts, hoods, grills, or
any sharp objects that may exist above drop ceiling
tile.
2. Unspool the beer conduit to allow unrestricted feed.
3. Route the conduit above ceiling tiles and connect to
ceiling and/or pipes using the appropriate conduit
hangers. Be sure the conduit is suspended above
ceiling tiles, not lying on the tiles. Care should be
taken when determining appropriate method of
handing conduit securely. Hangers must not crush
or pinch insulation. This will reduce cooling
efficiency.
4. Once the conduit has been routed, ensure an
adequate supply of conduit is provided at each end
to make all connections.
BASEMENT CONSTRUCTION
Refer to Figure 4 for the following:
1. Unspool the beer conduit to allow unrestricted feed
during installation process.
2. Route the conduit up basement wall and secure with
appropriate conduit hangers.
3. After routing the conduit up the basement wall, route
conduit overhead on the basement ceiling. Connect
to the basement ceiling using appropriate conduit
hangers.
4. Once the conduit has been routed, ensure an
adequate supply of conduit is on hand to make all
connections.
Beermaster
Refrigeration Unit
Dispensing
Station
Beer Conduit
Conduit Hanger
Ceiling Tiles
Walk-In Cooler
Figure 3
Beermaster
Refrigeration Unit
Dispensing
Station
Beer Conduit
Conduit Hanger
Walk-In Cooler
Figure 4
Installation Section 2
2-12
Part Number EI211017 10/11
Connecting Beer Conduit
Before connecting the beer conduit at the walk-in beer
cooler and beer towers, ensure an adequate length of
conduit is being supplied to make proper connections.
1. Locate the lines of the beer conduit routed to the
Beermaster Glycol Chiller.
2. Using an approved cutting tool, cut the beer conduit
insulation along the top side while peeling insulation
back at the same time.
NOTE: Glycol circuit is a pair of lines; one blue and one
red. The blue line is the discharge or supply line. The red
line is the return line.
3. Locate the return glycol supply lines of the beer conduit
and connect to the corresponding John Guest fitting on
the Beermaster Glycol Chiller.
4. Locate the discharge glycol supply lines of the beer
conduit and connect to the corresponding John Guest
fitting on the Beermaster Glycol Chiller.
5. Locate the glycol lines in the main conduit. Connect the
glycol lines of the beer unit to walk-in cooler conduit to
the glycol lines of the main beer conduit.
6. Locate the beer and glycol supply lines at the
dispensing station. Connect each beer line, incoming
glycol line, and outgoing glycol line to the appropriate
John Guest fitting at the dispensing station.
Beermaster
Refrigeration Unit
Dispensing
Station
Beer Conduit to
Walk-in Cooler
Main Beer Conduit
Walk-In Cooler
Figure 5
!
Caution
Only an approved cutting tool should be used to cut
polyethylene tubing. The cutting tool should contain a
razor sharp cutting blade so that the tubing will not be
crushed when cutting. A razor blade knife or butterfly
tubing cutter is sufficient (see Figure 6). Multiplex packs a
butterfly cutter with each Beermaster Glycol Chiller.
Razor KnifeButterfly Cutter
Figure 6
Section 2 Installation
Part Number EI211017 10/11 2-13
Beermaster Conduit Kit
GENERAL
The following instructions will cover installation procedures required for properly connecting each component of the Beermaster
system. These instructions also contain the necessary information required for; calculating restrictor line length, required regulator
operating pressures and start up procedures. It is recommended that before proceeding with these instructions you ensure that
each of the following items have been properly installed. Items listed in suggested order of installation:
1. Glycol Chiller Unit
2. Dispensing Towers
3. Secondary Regulator Kits
4. Beer Conduit
5. High Pressure CO
2 Regulator Kit
6. Blender Kit or Beer Pumps
7. Air Compressor Kit, (optional)
8. Low CO
2 Alarm Kit.
Once the above items have been installed the following instructions can be completed.
NOTE: Your system may not include each item.
Kit contents
Four (4) and Seven (7) line conduit kits
Three (3) Return bends
Eight (8) Elbows
•29 Unions
Five (5) Tail pieces
Five (5) Beer nuts
One (1) 60 ft of PVC tape
One (1) 60 ft of foil
One (1) Spanner wrench
10 and 14 line conduit kits
Four (4) Return bends
15 Elbows
42 Unions
Eight (8) Tail pieces
Eight (8) Beer nuts
One (1) 60 ft of PVC tape
One (1) 60 ft of foil
One (1) Spanner wrench
Installation Section 2
2-14
Part Number EI211017 10/11
BEERMASTER CONDUIT KIT DIAGRAMS
Single Conduit, Two Beer System
Model 150 Refrigeration Unit
To Beer Keg
Walk-in Cooler
MC043341
(4 line beer conduit [2 beer, 2 glycol lines])
Single Faucet
Beer Tower
Figure 7
Single Conduit, Eight Beer System
Model 300 Refrigeration Unit
To Beer Keg
Walk-in Cooler
(Shown with optional pump)
Four Faucet Beer Tower
MC103310 (4 beer & glycol lines)
MC103310
(8 beer & 6 glycol lines)
Dual Conduit, Eight Beer System
Model 300 Refrigeration Unit
To Beer Keg
Walk-in Cooler
To Beer Keg
Walk-in Cooler
(Shown with optional pump)
Two Faucet
Beer Tower
Two Faucet
Beer Tower
MC073341 (2 beer, 2 glycol lines)
MC073341 (2 beer, 2 glycol lines)
Figure 8
Figure 9
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38

MULTIPLEX Beverage Conduit Owner Instruction Manual

Type
Owner Instruction Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI