Elmdor FRC14X14PC-DUL Installation guide

Type
Installation guide
1. With metal studding, install a framed opening at
specified location of panel. Opening dimensions
should be 1-5/8" larger than door size of panel;
i.e., for a 16" x 16" panel, opening should be
17-5/8" x 17-5/8" before being lined with
drywall.
2. The interior of opening should be lined with
5/8" type "X" gypsumboard, using screws spaced
18" o.c. maximum to the 1-5/8" track. Minimum
of two screws per side. (Wrapping of joist not
required in one hour ceiling application.)
3. Remove automatic door closer (spring).
4. Place panel in position in opening and mark
location of attaching screws on studding, using
holes in latch and hinge sides of panel frame as
marking guides.
5. Remove panel and drill 5/32" holes through
studding at points marked for attachment holes.
6. Place panel in position (leaving masonry anchor
straps flat against panel frame) and attach with
#10 drywall screws.
7. Panel can be supported with 12 gage wire ties or
plumbers tape attached from framing screws to
wood studs of flooring above.
8. Check panel for freedom of movement. If binding
occurs, shim as necessary to prevent racking of
frame.
9. Re-attach automatic door closer (spring), and
secure to sub-framing above to ensure door is
self-closing.
a. Panel sizes 16" x 16" and larger are supplied with an
extra spring. It is the responsibility of the installer to
attach these springs from the spring base on back of
panel to framing of floor above to insure that door is
self-closing.
b. Before installing panel, bend "lock release" bracket
inward causing panel to stay in the "up" position.
c. In order to insure that panel is self-closing, it must
be released from at least 60 degrees from the
horizontal.
*****************
Alternate installation for 1 hour ceiling with wood frame.
Ceiling to have two layers of 5/8" gypsum wallboard
leaving a 1" airspace around the door/frame assembly.
No lining of wood joist required.
Important:
Note:
All fire rated access panels are self-closing.
FRC INSTALLATION
FIRE RATED ACCESS PANEL
CEILING INSTALLATION INSTRUCTION
ACCESS DOORS
THREE HOUR CEILING NON-COMBUSTIBLE SYSTEM
OR ONE HOUR WOOD FRAME SYSTEM AT ALL FOUR SIDES OF DOOR
ELMDOR/STONEMAN • P.O. BOX 3527 • CITY OF INDUSTRY, CA 91744-0527 U.S.A. • TEL: (800) 591-9181 • (626) 968-8699 • FAX: (626) 333-4109
A Division of Acorn Engineering Company www.elmdorstoneman.com • E-mail: [email protected]
2-1/2"
ONE HOUR RATED CONSTRUCTION THREE HOUR RATED CONSTRUCTION
1" 1"
1-1/4" DRYWALL
SCREWS
(THROUGH
HOLES
PROVIDED)
INSIDE
LATCH
RELEASE
EXTRA SPRING PROVIDED FOR CEILING INSTALLATION ON SIZES
16" x 16" OR LARGER. BOTH SPRINGS MUST BE ATTACHED FROM
the SPRING BASE TO THE FRAMING OR FLOOR ABOVE IN SUCH
MANNER TO ENSURE THE PANEL IS SELF-CLOSING.
LATCH RELEASE
BENT INWARDS
SO PANEL REMAINS
IN THE "UP" POSITION
SPRING
BASE
12 GAGE
WIRE TIE
TWO LAYERS
OF TYPE X
DRYWALL
STEEL STUD
WOOD
STUD
Revised: 3/24/09
Recyclable
Product
Member of U.S. Green
Building Council
  • Page 1 1

Elmdor FRC14X14PC-DUL Installation guide

Type
Installation guide