8015335/XS28/07-24-2014 • Subject to change without notice • SICK AG • Waldkirch • Germany • www.sick.com CDF600-21XX | SICK 3
The eldbus module offers a supply voltage range of
DC 10 V to 30 V. The supply voltage is also applied to the
connected ID sensor.
The power supply or the power supply unit must meet the
requirements relating to SELV according to the currently
valid EN 60950-1 standard. In addition, the supply voltage
must be designed according to the requirements for LPS
(Limited Power Source) as per the EN 60950-1 standard or
must comply with NEC (National Electrical Code) Class 2.
Power output of the power source:
The eldbus module itself consumes < 5 W power (without ID
sensor and trigger sensor).
The additional power consumed by the connected ID sensor
and trigger sensor (if there is one) varies by type.
The output of the power supply unit must be dimensioned
based on the total consumption of all loads.
NOTE
Risk of damage caused by electrical current!
The supply voltage at the DEVICE connection is not short-cir-
cuit-protected. If the POWER LED no longer lights up following
a short circuit between pin 1 and pin 5, the device must be
sent to SICK Service so that its functionality can be re-estab-
lished.
4. Do not switch on the supply voltage yet.
CDF600-21xx-relevant specications of ID sensors
ID sensor Supply voltage Power con-
sumption
1)
Firmware
version
ID sensors that support proxy mode
CLV61x FIELD-
BUS
DC 10 V ... 30 V 2.8 W, typical V. 1.00
CLV62x DC 10 V ... 30 V Max. 4,5 W V. 5.26
CLV63x
line/raster
DC 18 V ... 30 V 5 W typical
CLV63x
Line with SwSP
DC 18 V ... 30 V 6 W typical
CLV64x
line/raster
DC 18 V ... 30 V 5 W typical
CLV64x
Line with SwSP
DC 18 V ... 30 V 6.5 W typical
CLV65x
line
DC 18 V ... 30 V 8.5 W typical
CLV65x
Line with SwSP
DC 18 V ... 30 V Typical 9.5 W
CLV63x ... 65x,
for heating in
addition
2)
DC 24 V ±10% Electronics
type-specic,
see above,
heating
max 30 W
CLV69x
3)
line
DC 18 V ... 30 V Max. 15 W V. 1.4.0.10
CLV69x
3)
Line with SwSP
DC 18 V ... 30 V Max. 17 W V. 1.4.0.10
Lector
®
62x DC 10 V ... 30 V Typical 3 W V. 1.50
RFH62x DC 10 V ... 30 V Max. 5 W V. 1.32
ID sensor Supply voltage Power con-
sumption
1)
Firmware
version
RFH63x DC 10 V ... 30 V < 6 W, typical V. 1.80
RFU62x DC 10 V ... 30 V
4)
< 8 W
5)
, typical V. 1.40
RFU63x DC 18 V ... 30 V < 20 W, typical V. 1.30
ID sensors that support gateway mode
Lector
®
64x/65x DC 24 V ± 20% 20 W typical –
IDM160 Transducer
DC 24 V/5 V
1.15 W typical –
IDM161 Transducer
DC 24 V/5 V
0.9 W typical –
IDM260 Transducer
DC 24 V/5 V
1.68 W typical –
IDM261 Transducer
DC 24 V/5 V
1.65 W typical –
1) Switching output without load.
Power consumption of the eldbus module additionally < 5 W.
2) Connection plan see & CDF600-21xx Fieldbus Module Technical Information
(no. 8015337)
3) Without
conguration option via conguration module in the GSD le.
4) DC 20 V to 30 V when using the RFU62x-101xx in ambient temperatures of
–20°C to –40°C.
5) Additionally max. 12 W from –20°C to –40°C.
Line w. OM = line scanner with oscillating mirror
Other ID sensors on request.
Step 3: Conguration
a. Overview of the conguration process
1. Set operating mode and bus address of the eldbus
module with the three "Mode" and "Addr." rotary encoding
switches.
2. Integrate the eldbus module in the eldbus master.
3. Congure data communication in the eldbus.
4. Only ID sensor that supports proxy mode:
Use the SOPAS ET conguration software to set the
remaining functions of the eldbus module.
b. Setting the operating mode and bus address in
the eldbus module
1. Open the side cover by unscrewing the two screws (ß)
( see “Device overview”, page 4). You can now
access the rotary encoding switches.
2. Set the operating mode with the "Mode" switch.
Position 0 or 1:
Fieldbus module operates as a proxy for an ID sensor (e.g.,
bar code scanners from the CLV6xx product family).
Position 2 to 5:
Fieldbus module operates as a gateway for an ID sensor
that supports gateway mode (e.g., hand-held scanner).
Data transmission rate according to switch setting. List
of modes that can be congured see “”Mode” rotary
encoding switch (hexadecimal-coded)”, page 4.
3. Use the "Addr x10" and "Addr x1" rotary encoding switches
to set a unique bus address for the eldbus module (a bus
address that only appears once in the PROFIBUS network).
Overview of addresses that can be congured see
“”Addr x10”/”Addr x1” rotary encoding switches (deci-
mal-coded)”, page 4.
The new settings are applied on the eldbus module when
the supply voltage is switched on. Changes to the settings of
the rotary encoding switches after the power supply has been
switched on are not applied in data communication initially;
however, the "POWER" LED ashes cyclically 10 times.
To apply a change to the operating mode/bus address to the
eldbus module, restart both the eldbus module and the ID
sensor. In order to do this, switch off the supply voltage for
the eldbus module and switch it on again.
After the restart, the selected address is adopted by the ID
sensor under SOPAS ET for display under SLAVE ADDRESS on
the PROFIBUS/DEVICENET tab.
c. Conguring the eldbus module (resume here for
ID sensor that supports proxy mode)
The SOPAS ET conguration software for SICK identication
sensors is used as standard for the commissioning and fur-
ther conguration of the eldbus module with the ID sensor
that supports proxy mode connected to it.
The conguration of the eldbus module is integrated in the
menu of the respective ID sensor supporting proxy mode.
Installing and starting the conguration software
> Download and install the latest version of the SOPAS ET
conguration software, as well as current device descrip-
tion les (*.sdd), from the online product page for the
software:
www.mysick.com/en/SOPAS_ET
by following the instructions provided there.
Connect the PC to the eldbus module and switch on devices
1. Connect the PC (switched-off) as follows:
• Serial version of the ID sensor, which supports proxy
mode, with xed connecting cable (serial data interfac-
es only):
Use a data cable (e.g., no. 6036106, 2 m) to connect
the USB interface of the eldbus module (
9) to the PC
interface (USB).
• Ethernet version of the ID sensor supporting proxy
mode:
Use a data cable (e.g., no. 6034414, 2 m) to connect
the Ethernet interface of the ID sensor to the Ethernet
network of the PC.
2. On the user side, switch on the supply voltage DC 10 V
to 30 V chosen according to the table on the left for the
eldbus module and the connected ID sensor.
Following initialization of the eldbus module and while
attempting to establish communication with the ID sensor,
the green "POWER" LED ashes. Once communication
has been established and the eldbus module is ready for
operation, the "POWER" LED illuminates continually.
Meaning of LEDs see “Optical status indicators”,
page 4.
3. Switch on PC and start conguration software via the
"SOPAS" option. Path: Start > Programs > SICK > SOPAS
ET Engineering Tool > SOPAS.
4. Start communication with the ID sensor with SOPAS ET as
described in the operating instructions for the connect-
ed ID sensor that supports proxy mode. In order to do
this, select the required communication interface in the
connection wizard.
The remaining steps in the process of conguring the
connected ID sensor are described in the & CDF600-21xx
Fieldbus Module Technical Information (no. 8015337).
d. Integrating the ID sensor in the eld bus master
and conguring data communication on the
eldbus
This section provides a brief overview of the general proce-
dure. This is covered in detail in relation to the ID sensor in
the & CDF600-21xx Fieldbus Module Technical Information
(no. 8015337).
Important!
The required GSD les are available on the on the product
site of the eldbus module online: www.mysick.com/en/
cdf600-2.
ID sensor that supports proxy mode:
1. Integrate the ID sensor as a new device (slave) in the eld-
bus master (e.g., PLC). For this purpose, transfer the SICK
sensor-specic GSD le for the corresponding ID sensor to
the device description database of the eldbus master.
2. Set the desired lengths of the eldbus input and output
data appropriately based on the selected communication
mode of the ID sensor and assign the corresponding PDOs
(Process Data Objects) in the eldbus master for data
exchange with the eldbus module.
3. Specify the object trigger source and the output format of
the ID sensor for the eldbus using SOPAS ET.
ID sensor that supports gateway mode:
1. Integrate the eldbus module as a new device (slave) in
the eldbus master (e.g., PLC).
For this purpose, transfer the SICK-specic GSD le for the
eldbus module (SICK0E0E.GSD) to the device description
database of the eldbus master.
IDM1xx and IDM2xx hand-held scanner:
Use the conguration codes to congure the hand-held
scanner for the eldbus module. For more information see
& CDF600-21xx Fieldbus Module Technical Information
(no. 8015337).
2. Any ID sensor with RS-232 interface:
Connect RS-232 interface to pin 2, 3, 5 of the eldbus
module (DEVICE connection).
Set data string framing to STX and ETX, set data format to
8 data bits, no parity, 1 stop bit. Set a data transmission
rate of 9.6 or 57.6 kBd in the sensor in accordance with
the selected position of the "Mode" rotary encoding switch.