Miller 4:1 IMPEDANCE MATCHING TRANSFORMER 043276 Owner's manual

Type
Owner's manual

This manual is also suitable for

Miller 4:1 IMPEDANCE MATCHING TRANSFORMER 043276

Compatible with power sources with a 10 to 50 kHz output frequency range, the Miller 4:1 Impedance Matching Transformer 043276 is ideal for a variety of induction heating applications. With a 70 kVA rating and a 1.3 qt/min (1.2 L/min) minimum coolant flow rate, this transformer provides efficient and reliable performance.

Key Features:

  • 4:1 turns ratio for step-down transformer applications
  • Reflective impedance approximately 16 times coil impedance
  • 70% duty cycle at rated primary amperage
  • Built-in flow indicator for checking coolant flow

Miller 4:1 IMPEDANCE MATCHING TRANSFORMER 043276

Compatible with power sources with a 10 to 50 kHz output frequency range, the Miller 4:1 Impedance Matching Transformer 043276 is ideal for a variety of induction heating applications. With a 70 kVA rating and a 1.3 qt/min (1.2 L/min) minimum coolant flow rate, this transformer provides efficient and reliable performance.

Key Features:

  • 4:1 turns ratio for step-down transformer applications
  • Reflective impedance approximately 16 times coil impedance
  • 70% duty cycle at rated primary amperage
  • Built-in flow indicator for checking coolant flow
OWNER’S MANUAL
February 2003 FORM: OM-178 715C
4:1 Impedance Matching Transformer 043 276
1. Specifications
4:1 Turns Ratio; Step Down Transformer
10 To 50 kHz Output Frequency Range
Reflective Impedance is approximately 16 Times Coil Impedance
70% Duty Cycle At Rated Primary Amperage
70% Duty Cycle At Rated Primary Amperage
1.3 qt/min (1.2 L/min) Minimum Coolant Flow Rate (Built-In Flow Indicator For Checking Coolant Flow)
70 kVA Rating
Length: 12 in (305 mm); Width: 8-3/4 in (222 mm); Height: 6-1/4 in (159 mm)
801 415-C
Weight: Net 18-3/4 lb (8.5 kg)
2. Safety Symbol Definitions
Warning! Watch Out! There are possible hazards as shown in the adjoining symbols.
Beware of electric shock from wiring. Keep all panels and covers closed.
Induction heating can cause fire. Move flammables away. Do not overheat parts and adhesive. Watch for fire; keep extinguisher
nearby.
Breathing fumes and gases from induction heating operations can harm your health. Properly ventilate work area. Read Material
Safety Data Sheets (MSDS’s) and manufacturer’s instructions for materials used.
Hot parts can cause burns. Induction heating makes parts very hot – let them cool before touching. Do not touch or handle in-
duction head during operation. Keep metal jewelry and other metal personal items away from head during operation.
Wear safety glasses with side shields.
Have only trained and qualified persons install, operate, or service this unit. Call your distributor if you do not understand the
directions. For INDUCTION HEATING SAFETY and EMF information, read power source manual.
Beware of moving parts. Keep guards and panels in place, covers closed, and hands away from moving parts.
Recycle or dispose of used liquids in an environmentally safe way. This is especially true for engine fluids such as drain oil and
used coolant; also important for coolant from cooling systems.
OM-178 715 Page 2
3. Connecting Transformer To Power Source
ST-801 049
1 Output Receptacle RC15
2 Plug From Transformer
3 Threaded Collar
Receptacle RC15 is a 4-socket
receptacle.
To connect to receptacle, align
keyway, insert plug, and tighten
threaded collar.
4 14-Socket Receptacle
1
Power Source Rear Panel
2
3
4
4. Connecting Coolant Lines To Transformer
801 415-C / Ref. S-0446-A / S-0628-A
1 Coolant In Fitting
2 Coolant Out Fitting
Connect lines from coolant system to
correct fittings on transformer.
Install induction coil using the supplied
O-rings (5/16 in ID x 7/16 in OD or
#14 – 1/2 in ID x 5/8 in OD) and customer
supplied 10-32 bolts.
3 Flow Indicator
4 Flow Switch Plug And Receptacle
5 Pendant Receptacle RC4
Connect flow switch receptacle to pins C
and D at receptacle RC4 on Pendant.
Turn on coolant flow and power source,
and check for any coolant leaks. Check
coolant flow at flow indicator on
transformer.
If power source contactor does not
energize, flow switch is not closed. Check
coolant system for proper flow through
transformer.
Tools Needed:
1
2
4
3
D
A
C
B
5
5. Operation
Install & Connect
Power Source
Put On
Personal Safety
Equipment
Set
Controls
Turn On
Power
Switch
Wait
10 Seconds
Unit Ready
To Heat
Turn On
Coolant Supply
Position Work
Near
Heat Station
Install & Connect
Transformer &
Install & Connect
Coolant Supply
Induction Coil
OM-178 715 Page 3
6. Routine Maintenance
Y Disconnect power before maintaining.
3 Months
Clean And
Tighten Output
Connection
(see Section 3)
Water Hose
Replace
Cracked
Parts
Output
Cord
6 Months
Replace
Unreadable
Labels
Blow Out Or
Vacuum Inside.
During Heavy
Service,
Clean Monthly
OR
7. Troubleshooting
Trouble Remedy
No heat output. Connect power source to proper input voltage or check for low line voltage (see power source Owner’s
Manual).
Transformer coolant flow switch not closed. Check coolant system for proper flow through transformer.
No heat output; fan motor continues to
run.
Tuning capacitor cover safety interlock switch open (see power source Owner’s Manual).
Secure transformer plug in power source receptacle (see Section 3).
Thermostat TP1 open (overheating). Allow fan to run; the thermostat will close when the unit has cooled
(see power source Owner’s Manual).
Low heat output. Check tuning of induction heating output system (see Section 8).
8. Tuning Chart
CAUTION
ENERGIZING CONTACTOR WITHOUT ALL 3 TUNING CAPACITORS IN OUTPUT CIRCUIT will damage power
source.
DO NOT operate power source without all 3 tuning capacitors in output circuit.
Voltage* Current (Amperage)* Frequency (KHz) Corrective Action
High Low Low Lower inductance or decrease matching transformer turns ratio
High Low High Add capacitance
High Low Mid-Range Decrease matching transformer turns ratio and add capacitance
Low High Low Lower capacitance
Low High High Increase matching transformer turns ratio, or lower capacitance
and increase inductance
Low High Mid-Range Increase matching transformer turns ratio and lower capacitance
*High voltage > 300 V rms; Low voltage < 200 V rms; Operating current range: 0 to 210 A rms
OM-178 715 Page 4
9. Parts List
. Hardware is common and
not available unless listed.
1
2
3
4
5
6
7
8
4
9
10
11
*12
13
*Fittings must be removed from old flow
switch and installed in replacement switch.
801 415-C
Figure 9-1. 4:1 Impedance Matching Transformer
Description
Part
No.
Dia.
Mkgs.
043 276
Item
No.
Figure 9-1. Impedance Matching Transformer
Quanti
ty
1 186 003 INDICATOR, flow 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 178 191 LABEL, coolant in/coolant out 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 196 750 COVER, induction head 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 145 642 CONNECTOR, tubing 1.000 w/1.000 npt str w/o nut 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 CINCH, S–202–B socket 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 CINCH, P–202–CCT plug 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 145 643 CONDUIT, non metallic flexible 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 043 995 WIRE, litz 4AWG rnd 43, 750 cma 5x5x5x14 teflon red 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 167 938 ADAPTER, amphenol/heyco 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 167 722 CONNECTOR, circ ms/met 4 pin size 36 plug 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11 O–RING (#14 – 1/2 in ID x 5/8 in OD) or. . . . . . . . . . . . . . . . . . . . . . . .
11 O–RING (5/16 in ID x 7/16 in OD) 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12 GEMS flow switch #122353 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13 178 192 LABEL, warning induction heating 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Miller 4:1 IMPEDANCE MATCHING TRANSFORMER 043276 Owner's manual

Type
Owner's manual
This manual is also suitable for

Miller 4:1 IMPEDANCE MATCHING TRANSFORMER 043276

Compatible with power sources with a 10 to 50 kHz output frequency range, the Miller 4:1 Impedance Matching Transformer 043276 is ideal for a variety of induction heating applications. With a 70 kVA rating and a 1.3 qt/min (1.2 L/min) minimum coolant flow rate, this transformer provides efficient and reliable performance.

Key Features:

  • 4:1 turns ratio for step-down transformer applications
  • Reflective impedance approximately 16 times coil impedance
  • 70% duty cycle at rated primary amperage
  • Built-in flow indicator for checking coolant flow