Removeelectricalenclosurecover.RemoveknockoutforAClineinputwires.Installlistedelectricalttingsinthe
knockoutholesforwireprotection.Removeknockoutforindicatortestswitchwires.Installlistedelectricalttingsin
the knockout holes for wire protection.
2
Electrical Connections
Important: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required.
The emergency driver must be fed from the same branch circuit as the AC driver.
1
1
2
3
4
5
Important: This unit must be installed with the factory-
provided remote mount Indicator test switch (ITS).
Follow National Electrical Code (NEC) and local code
regulations when installing the ITS.
Choose a suitable location in a wall or the ceiling for
the ITS. Maximum remote mounting distance for the ITS
is 50 feet. Install a UL listed single-gang electrical box.
Using UL listed wire, minimum size 18 AWG, minimum
75°C rating, and UL listed electrical conduit, connect
the leads on the ITS. Provide enough wire to reach the
lightingxtureelectricalenclosure.Use18-14AWG
twist-on wire connectors.
Recommended: use one violet and one brown wire to match the leads on the ITS.
Remove one knockout from the single-gang electrical box. Using UL listed conduit, run wire from the ITS to the
lightingxtureelectricalenclosure.
Close the single-gang electrical box using the factory-provided wall plate cover and hardware.
Indicator Test Switch Installation
ITS Installation: BT22, BT14 & BT24 Series
BT22 Series BT14 & BT24 Series
Remove cover
Remove cover
For indicator test switch
For indicator test switch
For AC line
For AC line
Connect the conduit from the indicator test switch to the electrical enclosure. Connect the positive (violet) and
negative (brown) leads of the indicator test switch to the matching leads of the emergency driver using 18-14AWG
twist-on wire connectors.
3
BT14 & BT24 SeriesBT22 Series
To indicator
test switch
To indicator
test switch
To emergency
driver
To emergency
driver