DSE DSE2157 Installation Instructions Manual

Type
Installation Instructions Manual

DSE DSE2157 is a relay expansion module used in conjunction with the DSE7000 series controllers to provide additional relay output functionality. The relay outputs are configured in the ‘host controller’, the DSE2157 module is not itself configured aside from the ‘ID switch’ detailed below. The module has an ID switch that allows you to select the ‘ID’ of the 2157 expansion module as the host controller is capable of giving instructions to a number of 2157 expansion modules at the same time. The enclosure cover must be unclipped and removed to gain access to the switch. The switch should be operated using a small screwdriver and set to match the required ID.

DSE DSE2157 is a relay expansion module used in conjunction with the DSE7000 series controllers to provide additional relay output functionality. The relay outputs are configured in the ‘host controller’, the DSE2157 module is not itself configured aside from the ‘ID switch’ detailed below. The module has an ID switch that allows you to select the ‘ID’ of the 2157 expansion module as the host controller is capable of giving instructions to a number of 2157 expansion modules at the same time. The enclosure cover must be unclipped and removed to gain access to the switch. The switch should be operated using a small screwdriver and set to match the required ID.

DEEP SEA ELECTRONICS
2157 Output Expansion Installation Instructions
Introduction
DSE2157 relay expansion module is used in conjunction with the DSE7000 series controllers to
provide additional relay output functionality. The relay outputs are configured in thehost controller’,
the DSE2157 module is not itself configured apart from theID switch’ detailed below.
For further details on configuring thehost controller’ you are referred to the relevant configuration
software manual.
Controls and indications
LED Indications
Function Colour Action
Power on / Link lost RED Steady when DC supply is connected and data is being received
from the host controller.
Flashing when the DC supply is connected and the data
connection to the host controller is not operating.
Status 1-8 RED Lit when the corresponding relay is active
ID switch
The rotary ID switch is used to select theID’ of the 2157 expansion module as the host controller is
capable of giving instructions to a number of 2157 expansion modules at the same time (consult
relevant modules instructions for further details on number of supported expansion units).
The enclosure cover must be unclipped and removed to gain access to the switch. The switch should
be operated using a small screwdriver and set to match the required ID.
NOTE : The ID must be a unique number, different from the ID of any other 2157 module
connected to the host controller.
If two or more 2157 controllers are required to mimic each other then they should be
configured with different IDs, and both configured the same in the host controller.
NOTE : The selection of the ID of other types of expansion modules WILL NOT interfere/clash
with the ID of the 2548. For instance if the 2548 is set to ID 4, it is acceptable to have a different
type of expansion module (for instance 2130) set to ID 4 also.
053-034
ISSUE 2
ID Switch
Power on /
Link lost LED
8 x Status LED
(1 LED per
relay)
Typical wiring diagrams
NOTE : Configuration of the outputs is performed in the host controller.
Dimensions
Overall size 164.6mm x 76.4mm x 48.9mm (6.48” x 3.01” x 1.93”)
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes M4 clearance
Mounting hole centres 152.37mm x 64.50mm (6.00” x 2.54”)
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
LO CALL (from UK BT landlines) :
Telephone 0845 260 8900
Email: sales@deepseaplc.com
Web:
www.deepseaplc.com
Deep Sea Electronics Inc.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) : Tel: 1 866 636 9703
Email: sales@deepseausa.com
Web: www.deepseausa.com
Deep Sea Electronics Plc.
(Far East)
Tel:+66 2 670 6228
Fax: +66 2 678 3028
Email: sales@deepseaplc.com
Web: www.deepseaplc.com
DEEP SEA ELECTRONICS
DSEEXTRA
®
DSE2157 relay output expansion module
057-083
Author : Anthony Manton
COMPLEX SOLUTIONS
MADE SIMPLE
DSE2157 relay output expansion module
2
057-083 Issue 1 DSE2157 relay output expansion operator manual
Deep Sea Electronics Plc
Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND
Sales Tel: +44 (0) 1723 890099
Sales Fax: +44 (0) 1723 893303
E-mail : sales@Deepseaplc.com
Website : www.deepseaplc.com
DSE2157 relay output expansion module
© Deep Sea Electronics Plc
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents
Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication
should be addressed to Deep Sea Electronics Plc at the address above.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.
Amendments since last publication
Amd. No. Comments
Typeface : The typeface used in this document is Arial. Care should be taken not to mistake the upper
case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.
DSE2157 relay output expansion module
057-083 Issue 1 DSE2157 relay output expansion operator manual
3
1
BIBLIOGRAPHY .................................................................................................. 4
2
INTRODUCTION .................................................................................................. 4
3
SPECIFICATIONS ............................................................................................... 5
3.1
PART NUMBERING ................................................................................................................. 5
3.1
POWER SUPPLY ..................................................................................................................... 5
3.2
DSENET® ................................................................................................................................. 5
3.3
OUTPUTS ................................................................................................................................. 6
3.4
DIMENSIONS ........................................................................................................................... 6
3.5
APPLICABLE STANDARDS ................................................................................................... 6
4
INSTALLATION ................................................................................................... 7
5
USER CONNECTIONS ........................................................................................ 7
5.1
TERMINAL SPECIFICATION .................................................................................................. 7
5.1.1
CONNECTOR A ................................................................................................................ 7
5.1.2
CONNECTOR B ................................................................................................................ 7
6
TYPICAL WIRING DIAGRAM ............................................................................. 8
7
CONTROLS AND INDICATIONS ........................................................................ 9
7.1
LED INDICATIONS .................................................................................................................. 9
7.2
ID SWITCH ............................................................................................................................... 9
8
FAULT DIAGNOSIS .......................................................................................... 10
9
MAINTENANCE, SPARES, REPAIR AND SERVICING ................................... 10
10
WARRANTY ................................................................................................... 10
11
DISPOSAL ...................................................................................................... 10
11.1
WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) ................................. 10
11.2
ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES ............................................... 10
DSE2157 relay output expansion module
4
057-083 Issue 1 DSE2157 relay output expansion operator manual
1 BIBLIOGRAPHY
This document refers to and is reffered to by the following DSE publications which can be obtained
from the DSE website www.deepseaplc.com
DESCRIPTION
057-074 7000 series operators manual
057-077 7000 series configuration software manual
2 INTRODUCTION
This document details the installation requirements of the DSE2157 relay expansion module part of
the DSEExtra® range of ancilliary modules.
The manual forms part of the product and should be kept for the entire life of the product. If the
product is passed or supplied to another party, ensure that this document is passed to them for
reference purposes.
This is not a controlled document. You will not be automatically informed of updates. Any future
updates of this document will be included to the DSE website at www.deepseaplc.com
DSE2157 relay expansion module is used in conjunction with the DSE7000 series controllers to
provide additional relay output functionality. The relay outputs are configured in the ‘host controller’,
the DSE2157 module is not itself configured aside from the ‘ID switch’ detailed below.
For further details on configuring the ‘host controller’ you are referred to the relevant configuration
software manual (refer to the section entitled Bibliography elsewhere in this document).
DSE2157 relay output expansion module
057-083 Issue 1 DSE2157 relay output expansion operator manual
5
3 SPECIFICATIONS
3.1 PART NUMBERING
2157 - 001 - 00
At the time of this document production, there are no variants of this product and there have been no
revisions of the module hardware.
3.1 POWER SUPPLY
Minimum supply voltage 8V continuous, 4V for up to 5 minutes.
Cranking dropouts Able to survive 0V for 50mS providing the supply was at least 10V before
the dropout and recovers to 5 volts afterwards.
Maximum supply voltage 35V continuous (protection to 60V)
Maximum operating
current
325mA at 12V, 152mA at 24V
Conditions: All relays energised.
Maximum standby current 70mA at 12V, 32mA at 24V
Conditions: All relays de-energised.
3.2 DSENET®
DSEnet is the interconnection cable between the host controller and the expansion module(s) and
must not be connect to any device other than DSE equipment designed for connection to the DSEnet.
Cable type Two core screened twisted pair
Cable characteristic impedance
120Ω
Recommended cable Belden 9841
Belden 9271
Maximum cable length 1000m (1km) when using Belden 9841 or direct equivalent.
500m (0.5km) when using Belden 9271 or direct equivalent.
DSEnet topology Bus with no stubs (spurs)
DSEnet termination
120Ω. Fitted internally to host controller. Must be fitted externally
to the ‘last’ expansion module by the customer .
Maximum expansion modules Refer to host controller documentation
NOTE : As a termination resistor is internally fitted to the host controller, the host controller
must be the ‘first’ unit on the DSEnet. A termination resistor MUST be fitted to the ‘last’ unit on
the DSEnet. For further details, please see the section entitled ‘typical wiring diagram
elsewhere in this document.
Product type
DSE 2157
input
expansion
module
2157
Variant
Standard
product
00
Hardware revision
Revision 1
001
DSE2157 relay output expansion module
6
057-083 Issue 1 DSE2157 relay output expansion operator manual
3.3 OUTPUTS
Relay rating 2A DC rated (Max 30V)
3.4 DIMENSIONS
Overall size 164.6mm x 76.4mm x 48.9mm
(6.48” x 3.01” x 1.93”)
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes M4 clearance
Mounting hole centres 152.37mm x 64.50mm
(6.00” x 2.54”)
Dimensions in mm
3.5 APPLICABLE STANDARDS
BS
4884
-
1
:1992
This document conforms to BS4884-1 1992 Specification for
presentation of essential information.
BS
4884
-
2:1993
This document conforms to BS4884-2 1993 Guide to content
BS
4884
-
3:1993
This document conforms to BS4884-3 1993 Guide to presentation
BS EN 60068
-
2
-
1
(Minimum temperature)
-30°C (-22°F)
BS EN 60068
-
2
-
2
(Maximum temperature)
+70°C (158°F)
BS EN 60950
Safety of information technology equipment, including electrical
business equipment
BS EN 61000
-
6
-
2
EMC Generic Immunity Standard (Industrial)
BS EN 61000
-
6
-
4
EMC Generic Emission Standard (Industrial)
BS EN 60529
(Degrees of protection
provided by enclosures)
IP21
UL508
NEMA rating
enclosure type 1 (indoor use only)
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
DSE2157 relay output expansion module
057-083 Issue 1 DSE2157 relay output expansion operator manual
7
4 INSTALLATION
The DSE2130 is designed to mounted within a control panel, on the panel DIN rail utilising the integral
mounts. For dimension and mounting details, see the section entitled Specification, Dimensions
elsewhere in this document.
5 USER CONNECTIONS
5.1 TERMINAL SPECIFICATION
Connection type Screw terminal, rising clamp, no internal spring
Min cable size 0.5mm² (AWG 20)
Max cable size 2.5mm² (AWG 14)
Recommended cable
size
Refer to tables below
Relay rating 2A DC rated (Max 30V)
Update rate The host controller updates the 2157 relay state every 100ms. It is not
recommended to use the 2157 relays for load switching control.
5.1.1 CONNECTOR A
Terminal
Function Recommended size
1 DC supply positive 1.0mm² (AWG 18)
2 DC supply negative 1.0mm² (AWG 18)
3 Screen DSEnet only. Do not connect to earh
4 A 0.5mm² (AWG 20) DSEnet only
5 B 0.5mm² (AWG 20) DSEnet only
5.1.2 CONNECTOR B
Terminal
Function
Recommended size
6 Relay 1 1.0mm² (AWG 18)
Normally open
7 Relay 1 1.0mm² (AWG 18)
8 Relay 2 1.0mm² (AWG 18)
Normally open
9 Relay 2 1.0mm² (AWG 18)
10 Relay 3 1.0mm² (AWG 18)
Normally open
11 Relay 3 1.0mm² (AWG 18)
12 Relay 4 1.0mm² (AWG 18)
Normally open
13 Relay 4 1.0mm² (AWG 18)
14 Relay 5 1.0mm² (AWG 18) Common
Normally closed
Normally open
15 Relay 5 1.0mm² (AWG 18)
16 Relay 5 1.0mm² (AWG 18)
17 Relay 6 1.0mm² (AWG 18) Common
Normally closed
Normally open
18 Relay 6 1.0mm² (AWG 18)
19 Relay 6 1.0mm² (AWG 18)
20 Relay 7 1.0mm² (AWG 18) Common
Normally closed
Normally open
21 Relay 7 1.0mm² (AWG 18)
22 Relay 7 1.0mm² (AWG 18)
23 Relay 8 1.0mm² (AWG 18) Common
Normally closed
Normally open
24 Relay 8 1.0mm² (AWG 18)
25 Relay 8 1.0mm² (AWG 18)
NOTE : Normally open / normally closed refers to the contacts when the DC supply is removed
from the module. The powered up state of the module depends upon configuration of the
connected ‘host module’.
DSE2157 relay output expansion module
8
057-083 Issue 1 DSE2157 relay output expansion operator manual
6 TYPICAL WIRING DIAGRAM
DSE2157 relay output expansion module
057-083 Issue 1 DSE2157 relay output expansion operator manual
9
7 CONTROLS AND INDICATIONS
7.1 LED INDICATIONS
Function Colour Action
Power on / Link lost RED Steady when DC supply is connected and data is being received
from the host controller.
Flashing when the DC supply is connected and the data connection
to the host controller is not operating.
Status 1-8 RED Lit when the corresponding relay is active
7.2 ID SWITCH
The rotary ID switch is used to select the ‘ID’ of the 2157 expansion module as the host controller is
capable of giving instructions to a number of 2157 expansion modules at the same time (consult
relevant modules instructions for further details on number of supported expansion units).
The enclosure cover must be unclipped and removed to gain access to the switch. The switch should
be operated using a small screwdriver and set to match the required ID.
NOTE : The ID must be a unique number, different from the ID of any other 2157 module
connected to the host controller.
If two or more 2157 controllers are required to ‘mimic’ each other then they should be
configured with different IDs, and both configured the same in the host controller.
Address Switch
Power on /
Link lost LED
8 x Status LED
(1 LED per
relay)
DSE2157 relay output expansion module
10
057-083 Issue 1 DSE2157 relay output expansion operator manual
8 FAULT DIAGNOSIS
Nature of problem
Suggest
ion
Relays don’t activate on the 2157 board Ensure the host controller is correctly
configured to send signals to the 2157
Power LED indication does not illuminate Check polarity and size of the connected DC
supply are within the specifications of the
DSE2157
Power LED flashes This means the the communications link to the
host controller has been lost.
Check the connection of the DSEnet paying
particular attention to the cable type being used
and the positioning of the termination resistors.
9 MAINTENANCE, SPARES, REPAIR AND SERVICING
The DSE2157 is designed to be Fit and Forget. As such, there are no user serviceable parts. In the
case of malfunction you should contact your original equipment supplier (OEM).
10 WARRANTY
DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any
applicable warranty, you are referred to your original equipment supplier (OEM).
11 DISPOSAL
11.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
Directive 2002/96/EC
If you use electrical and electronic equipment you must store, collect, treat,
recycle and dispose of WEEE separately from your other waste.
11.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES
Directive 2002/95/EC:2006
To remove specified hazardous substances (Lead, Mercury, Hexavalent Chromium, Cadmium, PBB &
PBDE´s)
Exemption Note: Category 9. (Monitoring & Control Instruments) as defined in Annex 1B of the WEEE
directive will be exempt from the RoHS legislation. This was confirmed in the August 2005 UK´s
Department of Trade and Industry RoHS REGULATIONS Guide (Para 11).
Despite this exemption DSE has been carefully removing all non RoHS compliant components from
our supply chain and products.
When this is completed a Lead Free & RoHS compatible manufacturing process will be phased into
DSE production.
This is a process that is almost complete and is being phased through different product groups.
®
DSEGenset
DSE2157
DSENET
®
OUTPUT EXPANSION MODULE
ISSUE 3
HOST MODULE (1)
1
DSENET
®
EXPANSION
DC POWER
SUPPLY 8-35V
7
OTHER
DSE2157
VOLT-FREE NORMALLY OPEN OUTPUTS VOLT-FREE CHANGE OVER OUTPUTS
DSENET
®
2
1
5
7
2
1
3
0
2
5
1
0
/
2
0
2
5
4
8
4 4
COMPATIBLE WITH DSE7310/20, DSE8610/60/80 & DSE8710/60
HOST MODULE
DSE2157
DSENET
®
OUTPUT EXPANSION MODULE
DSEGenset
®
The DSE2157 is an output relay
expansion module for use with
DSENet
®
compatible control
modules. The DSE2157 has been
designed to extend a host module’s
output capabilities.
A maximum of 10 DSE2157’s can be
connected to an individual module at
any one time. All outputs
are configurable via the host
controller.
The additional output capabilities of
the DSE2157 give OEMs the
flexibility to meet increasingly
complex industry specifications.
The module incorporatesDINrail
and chassis mountings allowing
convenient fixing into a panel.
The module will work up to 1 KM
(0.6miles) from the host control
module.
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
B
S EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
ELECTRICAL SAFETY
B
S EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30
o
C
B
S EN 60068-2-2
Bb/Be Dry Heat +70
o
C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three
major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55
o
C
@
95% RH 48 Hours
B
S EN 60068-2-78
Cab Damp Heat Static 40
o
C
@
93% RH 48 Hours
S
HOCK
B
S EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
HOST MODULE (1)
1
DSENET
®
EXPANSION
DC POWER
SUPPLY 8-35V
COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY
OF GEN-SET APPLICATIONS
7
OTHER
DSE2157
VOLT-FREE NORMALLY OPEN OUTPUTS VOLT-FREE CHANGE OVER OUTPUTS
DSENET
®
2
1
5
7
2
1
3
0
2
5
1
0
/
2
0
2
5
4
8
4 4
COMPATIBLE WITH DSE7310/20, DSE8610/60/80 & DSE8710/60
HOST MODULE
ISSUE 3
®
DSEGenset
SPECIFICATION
DEEP SEA ELECTRONICS PLC UK
Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com
DEEP SEA ELECTRONICS INC USA
3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com
055-061/10/10 (3) USRegistered in England & Wales No.01319649
VAT No.316923457
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change
the details shown on this data sheet without prior notice. The contents are intended for guidance only.
DSE2157
DSENET
®
OUTPUT EXPANSION MODULE
KEY FEATURES
Power On/Link Lost LED ID
SWITCH
10 expansion modules can be
connected to 1 host controller at
a time
8 configurable relay contacts
with LED indicators:
- 4 Normally Open (N/O)
- 4 Change Over (C/O)
Terminal strip connection for
quick and easy set-up
ID SWITCH
The rotary ID switch is used to
select the address of the DSE2157
expansion module, as the host
control module is capable of giving
instructions to a number of
DSE2157 expansion modules at
the same time.
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
C
RANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is
achieved without the need for internal
batteries. LEDs and backlight will not be
maintained during cranking.
M
AXIMUM OPERATING CURRENT
325 mA at 12 V, 152 mA at 24 V
MAXIMUM STANDBY CURRENT
7
0 mA at 12 V, 32 mA at 24 V
AUXILIARY RELAY CONTACTS
2 Amp DC rated voltage free
DIMENSIONS
OVERALL
1
65 mm x 76 mm x 49 mm
6.5” x 3” x 1.9”
RELATED MATERIALS
TITLE PART NO’S
DSE2157 Installation Instructions 053-034
DSE2157 Operator Manual 057-083
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

DSE DSE2157 Installation Instructions Manual

Type
Installation Instructions Manual

DSE DSE2157 is a relay expansion module used in conjunction with the DSE7000 series controllers to provide additional relay output functionality. The relay outputs are configured in the ‘host controller’, the DSE2157 module is not itself configured aside from the ‘ID switch’ detailed below. The module has an ID switch that allows you to select the ‘ID’ of the 2157 expansion module as the host controller is capable of giving instructions to a number of 2157 expansion modules at the same time. The enclosure cover must be unclipped and removed to gain access to the switch. The switch should be operated using a small screwdriver and set to match the required ID.