DOMUSA Evolution EV AC Installation And Operating Instructions Manual

Type
Installation And Operating Instructions Manual
INSTALLATION AND OPERATING INSTRUCTIONS
¬ EVOLUTION EV AC
ER-0170/1996
CGM-04/392
Thank you for choosing a DOMUSA heating boiler. From the range of
DOMUSA products you have chosen the Evolution EV AC model. With
a suitable hydraulic installation, this oil-fired boiler will provide the
ideal level of comfort for your home.
This manual forms an essential part of the product and it must be
given to the user. Read the warnings and recommendations in the
manual carefully, as they contain important information on the safety,
use and maintenance of the installation.
These boilers are to be installed by skilled personnel only, in
accordance with the legislation in force and following the
manufacturer’s instructions.
The start-up of these boilers and any maintenance operations must
only be carried out by DOMUSA’s Authorised Technical Assistance
Services.
Incorrect installation of these boilers could result in damage to people,
animals or property, and the manufacturer will hold no liability in such
cases.
1
CONTENTS Page
1 LIST OF COMPONENTS.........................................................................................................................................................................................................................................2
2 CONTROL ELEMENTS............................................................................................................................................................................................................................................3
3 INSTALLATION INSTRUCTIONS.........................................................................................................................................................................................................................4
3.1 LOCATION.................................................................................................................................................................................................................................................................4
3.2 HYDRAULIC INSTALLATION.....................................................................................................................................................................................................................................4
3.3 ELECTRICAL CONNECTION......................................................................................................................................................................................................................................4
3.4 OIL INSTALLATION...................................................................................................................................................................................................................................................4
3.5 REMOVAL OF COMBUSTION PRODUCTS................................................................................................................................................................................................................4
3.6 INSTALLING A SANIT STORAGE HEATER (OPTIONAL)...........................................................................................................................................................................................6
3.7 ANTI-LEGIONNAIRES DISEASE FUNCTION (WITH STORAGE HEATER ONLY).......................................................................................................................................................6
3.8 INSTALLING THE UNDERFLOOR HEATING KIT SRAC2/EV (OPTIONAL)............................................................................................................................................................6
4 REMOVAL OF COMBUSTION PRODUCTS......................................................................................................................................................................................................7
4.1 Ø80 COMBUSTION PRODUCT EXHAUSTION AND AIR INTAKE DUAL DUCT SYSTEM (TYPE C53).......................................................................................................................7
4.2 CHANGING FROM DUAL DUCT FUME REMOVAL TO COAXIAL FUME REMOVAL.................................................................................................................................................8
4.3 Ø80-125 CONCENTRIC HORIZONTAL DUCT FOR REMOVAL OF COMBUSTION PRODUCTS AND AIR INTAKE (TYPE
C13)..............................................................................9
4.4 Ø80-125 CONCENTRIC VERTICAL DUCT FOR REMOVAL OF COMBUSTION PRODUCTS AND AIR INTAKE (TYPE
C33)..................................................................................10
5 FILLING THE INSTALLATION............................................................................................................................................................................................................................11
6 DIGITAL DISPLAY ................................................................................................................................................................................................................................................11
7 TEMPERATURE SELECTION..............................................................................................................................................................................................................................12
7.1 SELECTING THE BOILER SET POINT TEMPERATURE.............................................................................................................................................................................................12
7.2 SELECTING THE HOT WATER SET POINT TEMPERATURE (WITH STORAGE HEATER ONLY)..............................................................................................................................12
7.3 SELECTING THE UNDERFLOOR HEATING OUTLET SET POINT TEMPERATURE (WITH SRAC2/EV KIT OPTION).............................................................................................13
8 FUNCTIONING......................................................................................................................................................................................................................................................13
8.1 FUNCTIONING IN “HEATING ONLYMODE........................................................................................................................................................................................................13
8.2 FUNCTIONING WITH SANIT STORAGE HEATER (OPTIONAL).............................................................................................................................................................................14
8.3 FUNCTIONING WITH THE UNDERFLOOR HEATING KIT SRAC2/EV (OPTIONAL)..........................................................................................................................................14
9 ADDITIONAL FUNCTIONS................................................................................................................................................................................................................................15
9.1 PUMP ANTI-BLOCK FUNCTION.............................................................................................................................................................................................................................15
9.2 ANTI-FROST FUNCTION........................................................................................................................................................................................................................................15
9.3 BOILER PRESSURE SENSOR FUNCTION................................................................................................................................................................................................................15
9.4 TELEPHONE RELAY CONNECTION........................................................................................................................................................................................................................15
9.5 ROOM THERMOSTAT CONNECTION ....................................................................................................................................................................................................................16
9.6 ANTI-LEGIONNAIRES DISEASE FUNCTION (OPTIONAL) (WITH STORAGE HEATER ONLY)..............................................................................................................................16
10 E20 REMOTE CONTROL (OPTIONAL).........................................................................................................................................................................................................16
10.1 FUNCTIONING WITHOUT AN EXTERNAL SENSOR.............................................................................................................................................................................................17
10.2 FUNCTIONING WITH AN EXTERNAL SENSOR (OPTIONAL)..............................................................................................................................................................................17
10.3 FUNCTIONING WITH A DOMESTIC HOT WATER STORAGE HEATER (OPTIONAL)...........................................................................................................................................18
10.4 TELEPHONE RELAY FUNCTION ..........................................................................................................................................................................................................................18
11 SAFETY CUT-OUT SYSTEMS..........................................................................................................................................................................................................................18
11.1 TEMPERATURE SAFETY CUT-OUT......................................................................................................................................................................................................................18
11.2 BURNER CUT-OUT ..............................................................................................................................................................................................................................................18
11.3 LOW PRESSURE CUT-OUT..................................................................................................................................................................................................................................19
12 DRAINING THE BOILER...................................................................................................................................................................................................................................19
13 SWITCHING OFF THE BOILER.......................................................................................................................................................................................................................19
14 INITIAL START-UP.............................................................................................................................................................................................................................................19
15 DELIVERY AND INSTALLATION....................................................................................................................................................................................................................19
16 BOILER MAINTENANCE...................................................................................................................................................................................................................................20
16.1 CLEANING THE BOILER.......................................................................................................................................................................................................................................20
16.2 ANTI-FROST PROTECTION..................................................................................................................................................................................................................................21
16.3 BOILER WATER CHARACTERISTICS ....................................................................................................................................................................................................................21
17 TECHNICAL CHARACTERISTICS...................................................................................................................................................................................................................22
18 CIRCULATING PUMP FLOW CURVES.........................................................................................................................................................................................................23
19 DIAGRAMS AND MEASUREMENTS............................................................................................................................................................................................................23
20 CONNECTION DIAGRAM................................................................................................................................................................................................................................24
21 ELECTRICAL DIAGRAM ...................................................................................................................................................................................................................................25
22 ALARM CODES...................................................................................................................................................................................................................................................26
23 BURNER................................................................................................................................................................................................................................................................27
23.1 ASSEMBLY...........................................................................................................................................................................................................................................................27
23.2 BURNER START-UP .............................................................................................................................................................................................................................................27
23.3 ADJUSTING THE COMBUSTION CONDITIONS...................................................................................................................................................................................................27
23.4 PRIMARY AIR ADJUSTMENT...............................................................................................................................................................................................................................28
23.5 COMBUSTION LINE ADJUSTMENT.....................................................................................................................................................................................................................28
23.6 CORRECT POSITION OF ELECTRODES................................................................................................................................................................................................................28
23.7 OIL PRESSURE ADJUSTMENT.............................................................................................................................................................................................................................29
23.8 OIL SUPPLY PIPING DIAGRAMS..........................................................................................................................................................................................................................29
WARNING: CHECK PERIODICALLY THE FLEXIBLE PIPES CONDITIONS. USING KEROSENE, THEY HAVE TO BE REPLACED AT LEAST EVERY 2 YEARS.....................................29
23.9 TECHNICAL SPECIFICATIONS .............................................................................................................................................................................................................................30
23.10 OPERATING CURVES ........................................................................................................................................................................................................................................30
23.11 OIL FLOW VERSUS NOZZLE AND PUMP PRESSURE........................................................................................................................................................................................30
23.12 NOZZLES...........................................................................................................................................................................................................................................................30
23.13 ELECTRICAL CONNECTION DIAGRAM.............................................................................................................................................................................................................31
23.14 QUICK CONNECTOR.........................................................................................................................................................................................................................................31
24 FAILURES..............................................................................................................................................................................................................................................................32
25 SPARES LIST........................................................................................................................................................................................................................................................33
26 GUARANTEE CONDITIONS............................................................................................................................................................................................................................36
Evolution EV AC
2
1 LIST OF COMPONENTS
1
7
6
2
3
4
5
8
9
7
10
1.- Air drain valve.
2.- Domestic sealed burner.
3.- Heating pump.
4.- Boiler temperature sensors.
5.- Pressure sensor.
6.- Safety valve.
7.- Automatic air vent.
8.- Expansion vessel.
9.- Stainless steel condenser.
10.- Steel body.
3
2 CONTROL ELEMENTS
2016 18 1917
1211 151413
11. On/Off pilot light:
When this pilot light comes on, it indicates
that the boiler is switched on.
12. Alarm warning pilot light:
When this pilot light flashes, it indicates that an
alarm or boiler functioning cut-out has
occurred.
13. Digital display:
This is the boiler’s main operating display. It
shows the different boiler temperatures, the
installation pressure and the various alarm
codes.
14. Heating pilot light:
When this pilot light is on, it indicates that the
heating mode has been selected, and the boiler
is in winter mode.
15. Hot water pilot light:
When this pilot light is on, it indicates that the
hot water mode has been selected (it will only
light up if an optional storage heater has been
installed with the boiler). When only this pilot
light is on, the boiler is in summer mode.
16. Boiler temperature selector:
The boiler set point temperature can be
selected at any time. The temperature selector is
a push-in dial button. To use it, push the button
in to release it, and then push it in again to
conceal it.
17. On/Off button:
This button switches the boiler on and off.
18. Set button:
By pressing this button, the different
temperatures of the boiler can be viewed on the
digital display.
19. Mode select:
This button is for selecting the different boiler
operating modes: heating + hot water (winter
mode), or hot water only (summer mode). The
hot water function can only be selected if an
optional storage heater is installed on the boiler.
20. Hot water temperature selector:
This is used to select the hot water set point
temperature at any time (it will only switch on if
an optional storage heater is installed on the
boiler). It is a push-in dial button. To use it, push
the button in to release it, and then push it in
again to conceal it.
Evolution EV AC
4
3 INSTALLATION INSTRUCTIONS
The boiler must be installed by personnel authorised by the Department of Industry in accordance
with the applicable regulations and standards in force. However, the following recommendations
must be complied with when installing the boiler:
3.1 Location
The boiler must be installed in a sufficiently ventilated site. The boiler must be accessible from
above for maintenance, so it must not be installed under a fixed worktop or any other obstacle
preventing access from the top.
3.2 Hydraulic Installation
The hydraulic installation must be made by qualified personnel. The applicable installation
legislation is to be complied with, and the following recommendations should also be taken into
account:
- The inside of the installation piping should be thoroughly cleaned before switching on the
boiler.
- We recommend inserting cut-off valves between the installation piping and the boiler, to
simplify maintenance tasks.
- The condensation pipe must lead to a drain outlet, as the Evolution boiler is a
condensation boiler and a large amount of water may be generated. Also, before starting up
the boiler, it is recommended to fill the condensation outlet tube/siphon with water, so that
the fumes do not exit through this pipe.
3.3 Electrical Connection
The boiler is ready to be connected at 220 V II to terminals 1 and 2 of terminal strip J1 (see Electrical
Connection Diagram). Remember to earth the appliance.
The boiler is also provided with two terminals on terminal strip J5 for the room thermostat
connection (see Electrical Connection Diagram). To connect the room thermostat, remove the
bridge joining the two terminals and connect the room thermostat in the same place.
3.4 Oil Installation
The Evolution boiler is supplied with a Domestic gas-oil burner
(2)
(see model in Technical
Characteristics). To install the oil line, proceed in accordance with the burner instructions enclosed
with this manual (see Burner section). The oil line installation and start-up of the burner must be
carried out by qualified, authorised personnel.
3.5 Removal of combustion products
The combustion product exhaustion ducts must be installed by qualified personnel and must
comply with current legislation and standards.
Evolution boilers are sealed oil-fired boilers, and the combustion products are therefore removed
through an outlet pipe, with a separate air intake from outside.
We recommend that the position of the outside exhaustion duct corresponds to the figures and to
the following table:
5
Exhaustion duct position Minimum distance
(mm)
A under a cornice 300
B between two horizontal ducts 1000
C from an adjacent window 400
D between two vertical duction 1500
E from an adjacent ventilation grille 600
F under a balcony (*) 300
G under a window 600
H under a ventilation grille 600
I from a recess in the building 300
J from a corner of the building 300
K from the floor 2500
L from a vertical or horizontal duct or outlet (**) 300
M from a frontal surface at a distance of 3 metres from the fume outlet 2000
N as above, but with an opening 3000
(*) Providing the width of the balcony is not over 2000 mm.
(**)If the materials from which the pipe is made are sensitive to the action of the flue gases, this distance should be
over 500 mm.
Note: Spanish law also stipulates that the end of the exhaustion duct must be at a distance of no less than 400 mm.
from any air intake opening, and from the wall.
IMPORTANT: All accessories used for combustion product removal and air intake are to be those
supplied by Domusa.
Evolution EV AC
6
3.6 Installing a Sanit storage heater (Optional)
The procedure for making the correct electrical connection of a Sanit domestic hot water storage
heater with the Evolution EV AC boiler is as follows:
- Connect a hot water temperature sensor (supplied optionally) to the sensor terminal strip J3
(terminals 13 and 14). To do this, firstly remove the resistor (Ra) which is supplied with the same
(see the "Connection Diagram").
- Insert the temperature sensor bulb in the bulb sheath in the storage heater.
- Connect the storage heater charging pump to the supply terminal strip J2 (terminals 6 and 7)
(see the “Connection Diagram").
To correctly make the hydraulic installation, carefully follow the assembly and connection
instructions enclosed with the storage heater.
3.7 Anti-legionnaire’s disease function (with storage heater only)
When the Sanit storage heater is installed with the Evolution EV AC boiler, the anti-legionnaire’s
disease function can be activated for the hot water in the storage heater.
This function must be activated by sufficiently qualified personnel. This is done by changing the
boiler model selectors, which are located on the display card inside the control panel.
Before carrying out any operations inside the boiler, switch off the electrical supply to the
appliance. To activate the anti-legionnaire’s disease function, remove the top cover from the boiler
and use a screwdriver to remove the cover of the control panel box, removing the two screws
holding it in place. The electronic display board can then be accessed, where the programming
selectors are located.
The anti-legionnaire’s disease function is selected by turning selector nº 4 to ON position (see
“Electrical Diagram").
3.8 Installing the Underfloor Heating Kit SRAC2/EV (Optional)
The procedure for correctly making the electrical connection between the Underfloor Heating Kit
SRAC2/EV and the Evolution EV AC boiler is as follows:
- Connect a flow temperature sensor (supplied with the kit) to the sensor terminal strip J3
(terminals 12 and 13). To do this, firstly remove the resistor (Rr) supplied with the same (see the
“Connection Diagram").
- Mount the temperature sensor bulb in accordance with the instructions enclosed with the kit.
- Connect the heating pump to the supply terminal strip J2 (terminals 8 and 9) (see the
“Connection Diagram").
- Connect the 3-way mixing valve motor to the supply terminal strip J2 (terminals 10 and 11) (see
the “Connection Diagram").
To correctly make the hydraulic installation, carefully follow the assembly and connection
instructions enclosed with the kit SRAC2/EV.
7
4 REMOVAL OF COMBUSTION PRODUCTS
4.1 ø80 Combustion product exhaustion and air intake dual duct system (type C53)
For this type of boiler, the removal of combustion products and air intake take place through
separate Ø80 mm. dual ducts. The Ø80 dual duct outlet kit, code CGAS000186, is used for this
purpose. This is the type of fume removal provided for Evolution boilers by default.
The maximum length of piping that can be installed is 20 metres, as the maximum sum of the
metres of the air intake duct and the metres of the combustion product exhaustion duct. Each 90º
elbow, or each two 45º elbows, will reduce the available length by 1 m.
It is recommended that the exhaustion duct be fitted in a slightly upwardly-inclined direction, at
around 2º - 3º, thus preventing any water and condensation from dripping out.
Dual exhaustion duct kit
80
Code CGAS000186
1m duct
80
Code
90º elbow 80
Code CGAS000147
45º elbow 80
Code CGAS000148
Examples of installation:
L 20 mts.
Evolution EV AC
8
4.2 Changing from dual duct fume removal to coaxial fume removal
The Evolution boiler has a Ø80 dual duct system for the removal of combustion products and air
intake. If you prefer the removal of combustion products to be made by means of a Ø80/125 coaxial
tube, you may use the Ø80/125 coaxial tube adaptor kit (supplied to order), code
CGAS000213.
Adaptor for coaxial pipe
80/125
Code CGAS000213
The changeover may be made with two different assembly configurations:
1. Rear outlet: simply remove the combustion air intake from the boiler, unscrewing the three
screws holding it in place, mount the adaptor on the fume outlet towards the rear, and use the
flexible air inlet tube to connect it to the adaptor.
2. Side or top outlet: the procedure is the same, but to mount the adaptor kit laterally a 90º Ø80
elbow (code CGAS000147) needs to be fitted before the adaptor at the fume outlet.
The two
configurations are shown in the
figures below:
Toma de aire de combustión
Salida hacia atrás Salida lateral
Codo 90º Ø80
Combustion air intake
Side outletRear outlet
Elbow
Adaptor for coaxial pipe 80/125
Code CGAS000213
9
4.3 ø80-125 concentric horizontal duct for removal of combustion products and air intake (type
C13)
The removal of combustion products and air intake can be made using concentric Ø80 mm ducts
for the removal of combustion products and Ø125 mm ducts for the air intake, using the 1m Ø80-
125 horizontal duct kit, code CGAS000189.
The maximum length from the boiler for horizontal ducts, including the kit terminal, is 10 metres.
Each 90° elbow, or two 45° elbows, will reduce the available length by 1 metre.
It is recommended that the pipe be fitted in a slightly upwardly-inclined direction, at around 2º - 3º,
to prevent any water or condensation from dripping out.
Kit salida horizontal 1m
80/125
Cod. CGAS000189
Curva 9 coaxial 80/125
Cod. CGAS000182
Curva 4 coaxial 80/125
Cod. CGAS000183
Tubo 1m coaxial 80/125
Cod. CGAS000184
Examples of installation:
L 10 mts.
1m ø 80/125 horizontal duct kit
Code CGAS000189
ø 80/125 90º coaxial curve
Code CGAS000182
ø 80/125 45º coaxial curve
Code CGAS000183
1m ø 80/125 coaxial duct
Code CGAS000184
Evolution EV AC
10
4.4 ø80-125 concentric vertical duct for removal of combustion products and air intake (type
C33)
The removal of combustion products and air intake can be made using concentric Ø80 mm ducts
for the removal of combustion products and Ø125 mm ducts for the air intake, using the Ø80-125
vertical duct kit, code
CGAS000231.
The maximum length from the boiler for vertical ducts, including the kit terminal, is 12 metres.
Each 90° elbow, or two 45° elbows, will reduce the available length by 1 metre.
Vertical outlet kit80/125
Cod. CGAS000231 Black tile
80/125
Cod. CGAS000074
45º curve
80/125
Cod.CGAS000183 90º curve
80/125
Cod. CGAS000182
1m coaxial tube80/125
Cod. CGAS000184
Black tile 80/125
Cod. CGAS000075
Examples of installation:
L 12 mts.
11
5 FILLING THE INSTALLATION
A fill valve for filling the installation is to be provided for. The installation should be filled up using this
valve until a pressure of 1 - 1.5 bar appears on the left side of the digital display. Filling is to be done
slowly and with the cap of the automatic air drain valve
(7)
loose, so that the air is released from the
installation. The rest of the installation is also to be suitably drained using the air drain valves fitted for
this purpose. Once the installation has been filled, close the filling valve.
Evolution boilers incorporate a pressure sensor
(5)
, which controls the pressure of the installation. If
the installation drops below the minimum pressure of 0.5 bar, the boiler will not switch on and a low
pressure alarm will appear on the display ("AP").
NOTE: Switching on the boiler with no water inside could result in serious damage.
6 DIGITAL DISPLAY
The Evolution boiler is electronic and incorporates a digital display
(13)
showing the actual
temperatures, the set point temperatures and the pressure of the installation. When the display is on
standby, the pressure is indicated on the left side of the display (in bars), and the actual temperature of
the boiler on the right of the display (in ºC). By pressing the set button underneath the display, the rest
of the available display options can be browsed, as follows:
Set button
Digital display
1.5
63
Press the set button successively to select the different display options. When the desired option
has been selected, it will return to standby after ten seconds have elapsed.
The following table shows the different display options:
1.5 63
bar ºC
Standby. The pressure is shown on the left, and the actual boiler
temperature on the right.
T 1 63 Actual boiler temperature.
T2 45 Actual hot water temperature (with storage heater).
T3 35 Actual flow temperature of the underfloor heating installation.
(option SRAC2/EV only)
TC 70 Boiler temperature selected using the corresponding dial
(16)
.
A( 45 Hot water temperature selected using the corresponding dial
(20)
(with storage heater).
TR 35 Set point flow temperature for the underfloor heating installation
selected using the corresponding dial
(16)
.
(option SRAC2/EV only)
SP 1.5 Actual boiler pressure, measured by the Pressure Sensor
(5)
.
Evolution EV AC
12
7 TEMPERATURE SELECTION
7.1 Selecting the boiler set point temperature
TC 70
/
The desired boiler operating temperature is selected using the push-in button, as shown in the
picture. Press the button down gently to release it. To press it back in again, push the button until it
locks. The push-in button is turned to select the desired temperature.
"tc"
will appears on the
display and you can view the selected set point temperature. When you have selected the
temperature, push the button in again. The display will return to standby status after ten seconds.
The boiler set point temperature can also be selected by browsing with the set button until the
"tc"
option appears on the display. When it appears, turn the push-in button to select the desired
temperature.
The boiler set point temperature range that can be selected is 30 - 85 ºC. Model Evolution boilers
are condensing boilers, and so in order to obtain maximum boiler performance and energy savings,
it is therefore recommended to select a set point temperature of 55 - 70 ºC, providing the heating
system installed and the insulation conditions of your home permit this.
7.2 Selecting the hot water set point temperature (with storage heater only)
A( 45
/
The desired hot water temperature is selected using the push-in button, as shown in the picture.
Press the button down gently to release it, and to press it in again, push the button until it locks.
To select the desired temperature, turn the push-in button.
"AC"
will appear on the display and
the selected set point temperature can be viewed. When you have selected the temperature,
push the button in again. The display will return to standby status after ten seconds. The hot
water set point temperature range permitted is 15 - 60ºC.
The hot water set point temperature can also be selected by browsing with the set button until
the option
"AC"
appears. When this option appears on the display, turn the push-in button to
select the desired temperature.
13
7.3 Selecting the underfloor heating outlet set point temperature (with SRAC2/EV kit option)
TR 35
/
When the boiler is installed with the optional underfloor heating kit, SRAC2/EV, the desired flow
temperature of the installation can be selected using the push-in button as shown in the figure
above. Press the button down gently to release it, and to press it in again, push the button until it
locks. To select the desired temperature, turn the push-in button.
"tr"
will appear on the display and
you will see the set point temperature selected. When you have selected the temperature, push the
button in again. The display will return to standby status after ten seconds..
The installation flow set point temperature can also be selected by browsing with the set button
until
“tr”
appears on the display. Then turn the push-in button to select the desired temperature.
The set point temperature range that can be selected is 0 - 45 ºC. To obtain optimum performance
from the underfloor heating system, we recommend selecting a set point temperature of 25 - 35 ºC,
providing the heating system installed and the insulation in your home permit this.
8 FUNCTIONING
The Evolution EV AC boiler is supplied by default in “heating only” mode, for a heating installation
only. Optionally, a domestic hot water storage heater (Sanit) and/or an underfloor heating kit
(SRAC2/EV) may be installed, providing the installation with more features.
8.1 Functioning in “Heating Only” mode
1.5 63
In this mode, the desired set point temperature for the boiler should be selected, and the
temperature of the room thermostat or E20 remote control (if the appliance is equipped with
these). The burner and the heating pump will begin to function until the selected set point
temperature of the boiler is reached in the installation (or on the room thermostat, if the appliance
is equipped with one). When the temperature of the installation drops below the boiler
temperature selected, the burner will start the heating cycle up again.
Evolution EV AC
14
8.2 Functioning with Sanit storage heater (Optional)
The Evolution EV AC boiler may be installed together with a storage heater from the DOMUSA
Sanit range, to obtain domestic hot water. For correct installation, follow carefully the assembly
and read carefully the "Installation instructions" section of this manual.
There are two different modes of functioning. They can be selected using the mode selection
button, as shown in the figures. The selection is indicated by the two mode pilot lights on the right
of the display.
1.5 63
/
Winter mode
In this mode, the boiler can heat up the heating installation and produce hot water at the same
time. To select this mode, press the mode selection button until the two pilot lights
(14) (15)
come on. The burner and hot water pump will switch on. When the storage heater reaches the
hot water set point temperature selected, it is ready to heat up the heating installation,
switching on the heating pump and switching off the hot water pump. The burner stops when
the boiler reaches the boiler set point temperature selected. When the room temperature
reaches the temperature adjusted on the installation room thermostat (if there is one), the
heating pump will switch off.
Summer mode
In this mode, the boiler will provide hot water only. To select this mode, press the mode
selection button until the bottom pilot light comes on (
15
). The burner and hot water pump
will be switched on until the storage heater reaches the selected hot water set point
temperature.
8.3 Functioning with the Underfloor Heating Kit SRAC2/EV (Optional)
The Evolution EV AC boiler may be installed together with an underfloor heating kit, SRAC2/EV.
This kit basically consists of a motorised 3-way mixing valve and an underfloor heating installation
flow temperature sensor. To correctly install it, carefully follow the assembly and connection
instructions enclosed with the kit.
The underfloor heating installation is worked by the electronic boiler control. The temperature is
adjusted by means of the installation flow sensor, selecting the flow temperature using the boiler
adjustment control dial on the control panel. It may be adjusted between 0 and 45 ºC. In this
operating mode, the boiler set point temperature is set by the electronic control at 75ºC by default,
and the installation flow temperature can be adjusted to the set point temperature selected by
working the mixing valve.
15
TC 75
/
The boiler set point temperature can be changed by browsing with the set button until the option
“tc”
appears on the display. When it appears, push the set button in and hold it down for 5
seconds, until the symbol
"tc"
begins to flash. Then push the set button successively to increase the
boiler set point temperature. When the desired temperature has been selected, push the set button
and hold it down for 5 seconds again, until it stops flashing. The value selected will be stored in the
memory.
9 ADDITIONAL FUNCTIONS
The Evolution EV AC boiler is equipped with an electronic control for efficiently regulating automatic
boiler operation. It also includes the following additional control features:
9.1 Pump anti-block function
This feature prevents the boiler circulation pumps from blocking if the pumps have not been
started up for a long period of time. This system remains enabled while the boiler is plugged into
the mains.
9.2 Anti-frost function
This function protects the boiler from freezing up during cold weather. If the boiler temperature
drops to below 6 ºC, the heating circulation pump will start up. If the boiler temperature continues
to drop and reaches 4 ºC, the burner will start up, heating the installation. When this function has
been activated, it will remain active until the boiler reaches 8 ºC. This system remains on standby
while the boiler is plugged into the mains.
9.3 Boiler pressure sensor function
This function prevents boiler failure due to a low water level and excess pressure in the boiler. The
pressure is detected by a pressure sensor
(5)
, and its value appears on the control panel display. If
the pressure drops below 0.5 bar, the electronic control switches off the boiler and activates an
alarm on the display. When the boiler pressure reaches 2.5 bar, an alarm pilot light
(12)
begins to
flash to warn that the pressure is too high. In this case we recommend calling the Technical
Assistance Service, and to partially drain the boiler.
9.4 Telephone relay connection
The Evolution boiler is designed to enable a phone relay to be connected for switching the boiler
on and off. This feature allows the boiler to be switched on and off remotely, from any location, by
means of a phone call. The relay is connected to the boiler via terminal strip J6 (see Electrical
Connection Diagram). When the phone relay contact closes, the boiler switches on, and when the
relay is open, it switches off, with the anti-frost protection and pump anti-block functions
remaining activated.
Evolution EV AC
16
9.5 Room thermostat connection
The boiler has two terminals on terminal strip J5 for connecting a room thermostat or room timer
(see Electrical Connection Diagram). This allows the heating mode to switch off according to the
room temperature. To connect it, remove the bridge from terminal strip J5 and connect the room
thermostat in the same place.
Installing a room thermostat will optimise the functioning of the installation, adapting the heating
to the requirements of your home and obtaining enhanced comfort. Also, if the thermostat allows
the hours of functioning to be programmed (room timer), it will be able to adapt the heating
system to the hours during which the installation is in use.
9.6 Anti-legionnaire’s disease function (optional) (with storage heater only)
This optional function prevents the bacteria causing legionnaire’s disease from proliferating in the
hot water accumulated in the storage heater. Every 7 days, the temperature of the water in the
storage heater is raised to 70 ºC to kill any such bacteria. This function will only be activated when
the boiler is functioning, with the master switch turned to “I”.
The boiler is supplied with this function deactivated. To enable the function, read the section
"Installation Instructions" carefully. We recommend that the operation for enabling this function is
carried out by qualified personnel.
10 E20 REMOTE CONTROL (OPTIONAL)
Together with the Evolution EV AC boiler, a remote control (E20) can optionally be supplied. This
remote control can be used to fully operate the boiler from any location within the home.
The remote control enables the hours of home comfort to be programmed, adjusting the installation
to the particular requirements of the home by measuring the room temperature and consequently
adapting the installation temperature. The remote control can also be used to adjust the hot water
and heating set point temperatures (storage heater option) at any time, and for viewing the different
boiler operation parameters. It also warns of any functioning anomalies affecting the boiler.
The E20 remote control may optionally be connected to an external sensor, for measuring the outside
temperature. With this option installed, the remote control can adjust the home comfort level
depending on the weather conditions at each particular moment, optimising fuel consumption and
the heating inside the home.
When an E20 remote control is connected to the boiler, the control of the boiler is performed
exclusively by the remote control. The different boiler temperatures that can be selected will need to
be changed using the remote control. It is easy to install, only needing 2 wires for communication
between the boiler and the E20 control. It is connected to the boiler by connecting the two wires on
terminal strip J4 (see Connection Diagram). For correct installation and functioning, carefully read the
instructions enclosed with the remote control.
The following sections contain a general explanation of the different operating modes and options of
the E20 remote control.
17
10.1 Functioning without an external sensor
Conventional heating installation (direct circuit)
The maximum temperature for the heating circuit, hours of heating and room temperatures
desired can be selected on the remote control. The E20 will calculate the boiler temperature
necessary at each particular time, depending on the temperature inside the home, and it will
switch the heating on and off according to the heating times and room temperatures
programmed.
Installing heating with an underfloor heating kit SRAC2/EV (mixed circuit)
If the boiler has an underfloor heating kit SRAC2/EV installed, the adjustment and control of the
underfloor heating is made via the boiler control panel (see "operation with underfloor heating
kit").
The E20 remote control can be used to programme the desired heating times and room
temperatures.
10.2 Functioning with an external sensor (Optional)
If an external temperature sensor is connected to the E20 remote control, the E20 can calculate the
heating installation mode temperature in accordance with the outside weather conditions at each
particular time, with optimum adjustment of the heating installation conditions for increased home
comfort and energy savings.
Conventional heating installation (direct circuit)
The maximum temperature and an operating curve for the heating circuit, the heating times and
the room temperatures desired can be selected on the remote control (see instructions enclosed
with the E20 remote control). The E20 will calculate the boiler temperature necessary at each
particular time, depending on the temperature inside the home and the weather conditions
outside, in accordance with the operating curve selected (parameter CURVE 1 on the E20),
switching the heating on and off in accordance with the heating times and the room
temperatures programmed.
Installing heating with the underfloor heating kit SRAC2/EV (mixed circuit)
If the boiler has an underfloor heating kit SRAC2/EV installed and the control of this circuit is
activated on the E20 remote control, using the parameter CURVE 2 (see instructions enclosed
with the E20 remote control), the adjustment and control of the underfloor heating circuit flow
temperature will be performed by the remote control. The E20 will calculate the flow
temperature necessary at each particular time, depending on the temperature inside and
outside the home, in accordance with the operating curve selected (parameter CURVE 2 on the
E20 remote control). For mixed underfloor heating circuits, we recommend selecting operating
curves of under 0.8.
The boiler set point temperature will be fixed at 75 ºC and may be changed via the boiler control
panel. To change this setting, browse with the set button until the option
“tc”
appears on the
display. When it appears, press the set button and hold it down for 5 seconds until the
"tc"
symbol begins to flash. If the set button is pressed successively, the boiler set point temperature
will gradually increase. When the desired temperature has been selected, press the set button
and hold it down for 5 seconds again until it stops flashing. The value selected will be stored in
the memory.
The E20 remote control can also be used to selected the maximum heating circuit flow
temperature and programme the desired heating times and room temperature. The E20 remote
control will switch the heating on and off according to the heating times and room
temperatures programmed.
Evolution EV AC
18
NOTE: For mixed underfloor heating circuits, we recommend selecting a maximum flow
temperature of NO HIGHER THAN 45 ºC, in order to protect the underfloor heating
installation from overheating.
10.3 Functioning with a domestic hot water storage heater (Optional)
When the boiler is installed with a connected hot water supply storage heater, the E20 remote
control can be used to select up to 2 hot water temperatures and the hot water times desired. The
E20 remote control will adjust the hot water temperature of the storage heater at each particular
time and switch the hot water on and off in accordance with the times programmed.
The E20 remote control also has an option for activating an anti-legionnaire’s disease bacteria
function (see instructions enclosed with the E20 remote control).
10.4 Telephone relay function
The E20 remote control is designed to be connected to an external telephone relay. If a telephone
relay is connected to it, the heating and hot water can be switched on and off from any location
anywhere in the world, by making a telephone call (see instructions enclosed with the E20 remote
control).
11 SAFETY CUT-OUT SYSTEMS
The boiler electronic control system may activate the boiler safety cut-out system, as shown below.
When any of the cut-outs are activated, the boiler will switch off, an alarm code will flash on the
display and the red alarm warning pilot light will start to flash.
AL AT
If any of the cut-outs below should occur repeatedly, switch off the boiler and call your nearest
official technical assistance service.
11.1 Temperature safety cut-out
When this cut-out occurs, the code "At" (temperature alarm) will
begin to flash on the digital display
(13)
and the alarm warning
pilot light will flash on the control panel. The burner will switch
off and stop heating the installation.
This occurs when the boiler exceeds a temperature of 110 ºC. To unblock it, wait until the boiler
drops to below 100 ºC and press the button on the safety thermostat, located inside the boiler on
the underside of the electric box, after first having removed the button cover.
11.2 Burner cut-out
When this cut-out occurs, the code "AQ" (burner alarm) will
begin to flash on the digital display
(13)
and the alarm warning
pilot light will flash. The burner will switch off and stop heating
the installation.
This occurs as a result of an anomaly in the burner
(2)
or in the
fuel installation. To unblock it, press the illuminated button that lights up on the burner.
AL AT
bar ºC
AL AQ
bar ºC
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

DOMUSA Evolution EV AC Installation And Operating Instructions Manual

Type
Installation And Operating Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI