Magnetrol E3 Modulevel Foundation Fieldbus User manual

Type
User manual
Liquid Level
Displacer Transmitter
 


 

48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
Read this Manual Before Installing
T
his manual provides information on the E3 Modulevel
®
Electronic Transmitters. It is important that all instructions
are read carefully and followed in sequence. Detailed instal-
lation, wiring and calibration instructions are included in
this manual.
If this equipment is used in a manner not specified by this
manufacturer, the protection provided by the equipment
may be impaired.
Conventions Used in this Manual
Certain conventions are used in this manual to convey
specific types of information. General technical material,
support data, and safety information are presented in
narrative form. The following styles are used for notes,
cautions, and warnings.
Notes
Notes contain information that augments or clarifies an
operating step. Notes do not normally contain actions.
They follow the procedural steps to which they refer.
Cautions
Cautions alert the technician to special conditions that
could injure personnel, damage equipment, or reduce a
component’s mechanical integrity. Cautions are also
used to alert the technician to unsafe practices or the
need for special protective equipment or specific materi-
als. In this manual, a caution box indicates a potentially
hazardous situation which, if not avoided, may result in
minor or moderate injury.
Warnings
Warnings identify potentially dangerous situations or
serious hazards. In this manual, a warning indicates an
imminently hazardous situation which, if not avoided,
could result in serious injury or death.
Safety Messages
Follow all standard industry procedures for servicing
electrical and computer equipment when working with
or around high voltage. Always shut off the power supply
before touching any components.
Electrical components are sensitive to electrostatic
discharge. To prevent equipment damage, observe safety
procedures when working with electrostatic sensitive
components.
WARNING! Explosion hazard. Do not connect or
disconnect equipment unless power has been switched
off or the area is known to be non-hazardous.
Low Voltage Directive
F
or use in Installation Category I, Pollution Degree 2. If
equipment is used in a manner not specified by manufac-
turer, protection provided by equipment may be impaired.
Notice of Trademark, Copyright and Limitations
Magnetrol
®
& Magnetrol
®
logotype and Modulevel
®
are
registered trademarks of Magnetrol
®
International,
Incorporated.
Copyright © 2019 Magnetrol
®
International, Incorporated.
All rights reserved.
Performance specifications are effective with date of issue
and are subject to change without notice. Magnetrol
®
reserves the right to make changes to the product described
in this manual at any time without notice. MAGNETROL
makes no warranty with respect to the accuracy of the
information in this manual.
Warranty
All MAGNETROL electronic level and flow controls are
warranted free of defects in materials or workmanship for
eighteen months from the date of original factory ship-
ment.
If returned within the warranty period; and, upon factory
inspection of the control, the cause of the claim is
determined to be covered under the warranty; then,
MAGNETROL will repair or replace the control at no cost
to the purchaser (or owner) other than transportation.
MAGNETROL shall not be liable for misapplication, labor
claims, direct or consequential damage or expense arising
from the installation or use of equipment. There are no
other warranties expressed or implied, except special
written warranties covering some MAGNETROL products.
Quality Assurance
The quality assurance system in place at MAGNETROL
guarantees the highest level of quality throughout the
company. MAGNETROL is committed to providing full
customer satisfaction both in quality products and quality
service.
The MAGNETROL quality assurance system is registered
to ISO 9001 affirming its commitment to known interna-
tional quality standards providing the strongest assurance
of product/service quality available.
Table of Contents
1.0 FO
UNDATION
fieldbus
Overview
1.1 Description ...............................................................4
1.2 Benefits .....................................................................5
1.3 Device Configuration................................................5
1.4 Intrinsic Safety ..........................................................6
1.5 Link Active Scheduler (LAS).....................................6
2.0 QuickStart Installation
2.1 Getting Started..........................................................7
2.1.1 Equipment and Tools .....................................7
2.1.2 Configuration Information.............................7
2.2 QuickStart Mounting................................................7
2.2.1 Tank Top........................................................7
2.2.2 External Chamber ..........................................8
2.3 QuickStart Wiring ....................................................8
2.4 QuickStart Configuration .........................................9
3.0 Complete Installation
3.1 Unpacking ..............................................................10
3.2 Electrostatic Discharge (ESD) Handing Procedure..10
3.3 Before You Begin.....................................................11
3.3.1 Site Preparation ............................................11
3.3.2 Equipment and Tools ...................................11
3.3.3 Operational Considerations..........................11
3.4 Mounting................................................................12
3.4.1 Tank Top Installation (E3A & E3B).............12
3.4.2 External Chamber Installation
(E3C, E3D, E3E, E3F) ................................13
3.5 Wiring ....................................................................14
3.5.1 General Purpose or Non-Incendive ..............15
3.5.2 Intrinsically Safe...........................................15
3.5.3 Explosion Proof............................................16
4.0 Reference Information
4.1 Overview.................................................................17
4.1.1 Universal Fieldbus Block Parameters ............17
4.2 Resource Block........................................................18
4.3 Modulevel
®
Transducer Block..................................21
4.3.1 Modulevel
®
Transducer Block Parameters.....21
4.3.2 Password Parameters.....................................21
4.3.3 E3 Modulevel
®
Configuration Parameters ....22
4.3.4 Offset Description........................................22
4.4 User-Calibration Parameters....................................22
4.4.1 User Calibration Procedure ..........................22
4.4.2 Factory Parameters .......................................24
4.4.3 Firmware Version .........................................24
4.5 Analog Input Block.................................................24
4.5.1 AI Block Parameters .....................................24
4.5.2 Local Display of Analog Input Transducer
Block Output ...............................................27
4.5.2.1 AI Out Display Screens.........................27
4.6 PID Block...............................................................28
4.6.1 PID Block Parameters ..................................28
5.0 E3 Modulevel
®
Menu: Step by Step Procedure
5.1 Measurement Type: Level Only..............................31
6.0 Diagnostic Parameters
6.1 Simulation Feature ..................................................34
7.0 Documentation
7.1 Fieldbus Data Sheet for Individual Instrument .......35
7.2 Fieldbus Data Sheet for Multiple Devices ...............36
8.0 Documentation
8.1 Description .............................................................37
8.2 Theory of Operation...............................................37
8.2.1 Displacer/Range Spring................................37
8.2.2 LVDT ..........................................................37
8.2.3 Interface .......................................................38
8.2.4 Density.........................................................38
8.3 Troubleshooting ......................................................38
8.3.1 Troubleshooting System Problems................39
8.3.2 Checking the LVDT Winding Resistance.....40
8.3.3 Device Status Parameter in the
Transducer Block..........................................41
8.3.4 FF Segment Checklist ..................................43
8.4 Agency Approvals....................................................44
8.4.1 FM (Factory Mutual) ...................................44
8.4.2 CSA (Canadian Standards Association) ........44
8.4.3 ATEX (European Directive for
Explosion Protection)...................................45
8.4.4 Agency Drawings .........................................46
8.5 Parts........................................................................47
8.5.1 Transmitter Head Replacement Parts ...........47
8.5.2 Mechanical Replacement Parts .....................48
8.5.3 Recommended Spare Parts ...........................49
8.6 Specifications ..........................................................50
8.6.1 Functional....................................................50
8.6.2 Performance Level .....................................51
8.6.3 Performance Interface Level & Density.....51
8.6.4 Physical ........................................................52
8.7 Model Numbers......................................................54
8.7.1 E3x for Non-Steam Service ..........................54
8.7.2 E3x for Steam Service...................................56
8.8 References ...............................................................58
Appendix – Transducer Block Parameters.....................58
FOUNDATION fieldbus Configuration Data Sheet..........59
E3 Modulevel
®
Displacer Level Transmitter
Installation, Operation and Maintenance Manual
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
4
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
1.0 FOUNDATION fieldbus
Overview
1.1 Description
F
O
UNDATION
fieldbus
is a digital communications system
that serially interconnects devices in the field. A Fieldbus
system is similar to a Distributed Control System (DCS)
with two exceptions:
Although a F
OUNDATION fieldbus
system can use the same
physical wiring as an existing 4–20 mA device, Fieldbus
devices are not connected point to point, but rather are
multidropped and wired in parallel on a single pair of wires
(referred to as a segment).
•F
OUNDATION fieldbus
is a system that allows the user to
distribute control across a network. Fieldbus devices are
smart and actually maintain control over the system.
Unlike 4–20 mA analog installations in which the two wires
carry a single variable (the varying 4–20 mA current), a dig-
ital communications scheme such as F
OUNDATION fieldbus
considers the two wires as a network. The network can carry
many process variables as well as other information. The
E3 Modulevel
®
transmitter is a FOUNDATION fieldbus
reg-
istered device that communicates with the H1
F
OUNDATION fieldbus
protocol operating at 31.25
kbits/sec. The H1 physical layer is an approved IEC 61158
standard.
An IEC61158 shielded twisted
pair wire segment can be as long
as 6234 feet (1900 meters) with-
out a repeater. Up to 4 repeaters
per segment can be used to extend
the distance. The maximum num-
ber of devices allowed on a
Fieldbus segment is 32 although
this depends on the current draw
of the devices on any given seg-
ment. See Figure 1.
Details regarding cable specifica-
tions, grounding, termination, and
other network information can be
found in IEC 61158 or the wiring
installation application guide
AG-140 at www.fieldbus.org.
Control Room
Power Supply
Terminator
6234 feet (1900 meters) maximum
PC
Terminator
Power
Conditioner


5
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
1.2 Benefits
The benefits of F
OUNDATION fieldbus
can be found
throughout all phases of an installation:
1. Design/Installation: Connecting multiple devices to a single
pair of wires means less wire and fewer I/O equipment.
Initial Engineering costs are also reduced because the
Fieldbus Foundation requires interoperability, defined as
the ability to operate multiple devices in the same system,
regardless of manufacturer, without a loss of functionality.”
All F
OUNDATION fieldbus
devices must be tested for
interoperability by the Fieldbus Foundation. Magnetrol
®
E3 MODULEVEL FOUNDATION fieldbus
device registration
information can be found at www.fieldbus.org.
2. Operation: With control now taking place within the
devices in the field, better loop performance and control are
the result. A FOUNDATION fieldbus
system allows for mul-
tiple variables to be brought back from each device to the
control room for additional trending and reporting.
3. Maintenance: The self-diagnostics residing in the smart
field devices minimizes the need to send maintenance
personnel to the field.
1.3 Device Configuration
Device Descriptions
The function of a FOUNDATION fieldbus
device is deter-
mined by the arrangement of a system of blocks defined by
the Fieldbus Foundation. The types of blocks used in a typi-
cal User Application are described as follows:
Resource Block describes the characteristics of the
F
OUNDATION fieldbus
device such as the device name,
manufacturer, and serial number.
Function Blocks are built into the F
OUNDATION fieldbus
devices as needed to provide the desired control system
behavior. The input and output parameters of function
blocks can be linked over the Fieldbus. There can be
numerous function blocks in a single User Application.
Transducer Blocks contain information such as calibration
parameters and sensor type. They are used to connect the
sensor to the input function blocks.
An important requirement of Fieldbus devices is the inter-
operability concept mentioned earlier. Device Description
(DD) technology is used to achieve this interoperability.
The DD provides extended descriptions for each object and
provides pertinent information needed by the host system.
6
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
DDs are similar to the drivers that your personal computer
(PC) uses to operate peripheral devices connected to it. Any
Fieldbus host system can operate with a device if it has the
proper DD and Common File Format (CFF) for that device.
The most recent DD and CFF files can be found on the
F
OUNDATION fieldbus
web site at fieldbus.org.
1.4 Intrinsic Safety
The H1 physical layer supports Intrinsic Safety (IS) applica-
tions with bus-powered devices. To accomplish this, an IS
barrier or galvanic isolator is placed between the power
supply in the safe area and the device in the hazardous area.
H1 also supports the Fieldbus Intrinsically Safe Concept
(FISCO) model which allows more field devices in a
network. The FISCO model considers the capacitance and
inductance of the wiring to be distributed along its entire
length. Therefore, the stored energy during a fault will be
less and more devices are permitted on a pair of wires.
Instead of the conservative entity model, which only allows
about 90 mA of current, the FISCO model allows a maxi-
mum of 110 mA for Class II C installations and 240 mA
for Class II B installations.
FISCO certifying agencies have limited the maximum
segment length to 1000 meters because the FISCO model
does not rely on standardized ignition curves.
The E3 MODULEVEL is available with entity IS, FISCO IS,
FNICO non-incendive, or explosion proof approvals.
1.5 Link Active Scheduler (LAS)
The default operating class of the E3 MODULEVEL with
F
OUNDATION fieldbus
is a basic device. However, it is
capable of being a Link Active Scheduler (LAS). The LAS
controls all communication on a F
OUNDATION fieldbus
segment. It maintains the “Live List” of all devices on a seg-
ment, coordinates both the cyclic and acyclic timing and, at
any given time, controls which device publishes data via
Compel Data (CD) and Pass Token (PT).
The primary LAS is usually maintained in the host system,
but in the event of a failure, all associated control can be
transferred to a backup LAS in a field device such as
the E3 MODULEVEL. The operating class of
E3 MODULEVEL can be changed from basic to LAS
using a F
OUNDATION fieldbus configuration tool.
2.0 QuickStart Installation
2.1 Getting Started
 
No special equipment or tools are required to install
E3 MODULEVEL. The following items are recommended:
Wrenches, flange gaskets and flange bolting appropriate for
process connection(s)
Flat-blade screwdriver
Level
1
8" Allen wrench
Fieldbus compatible power supply with proper termination
 
Some key information is needed to configure the
E3 MODULEVEL transmitter. Complete the following
operating parameters table before beginning configuration.
2.2 QuickStart Mounting
NOTE: Confirm the style and process connection size/type of the
E3 MODULEVEL transmitter. Ensure it matches the require-
ments of the installation before continuing with the QuickStart
installation.
 
1. If applicable, adjust and trim the adjustable hanger cable
assembly to the required length and mount it between the
stem and displacer.
2. Using a level, verify that the vessel mounting flange is level
in all directions within 3°.
7
  
LvlUnits What units of measurement will be used?
Lvl Ofst
What is the desired level reading when the
level is at the calibrated zero reference
(typically bottom of the displacer)?
Proc SG
What is the actual SG of the process liquid at
operating temperature?
ProcTemp What is the actual operating temperature?
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
3. Position the head flange gasket on the vessel flange and gen-
tly lower the displacer into the vessel. To prevent damage to
the stem/spring assembly, avoid tipping the unit or, in any
way, putting lateral forces on the stem.
4. Align the flanges and ensure that the gasket is seated properly.
5. Install the flange bolts and nuts and tighten alternating nuts
in a star pattern. Flange bolting torque specifications are
listed on page 12.
 
1. Remove the shipping strap and wire assembly which secures
the displacer in the chamber during shipment. This assem-
bly must be removed through the bottom connection or
drain.
2. Using a level, verify that the vessel mounting flanges are
level in all directions within 3°.
3. Align the MODULEVEL process connections with those
on the vessel and attach accordingly, based upon the con-
nection type. Appropriate gaskets and bolting will be
required for flanged connections. Install the flange bolts
and nuts and tighten alternating nuts in a star pattern.
Flange bolting torque specifications are listed on page 12.
2.3 QuickStart Wiring
WARNING: Explosion hazard. Do not connect or disconnect equip-
ment unless power has been switched off or the area is
known to be non-hazardous.
NOTE: Ensure that the electrical wiring to the E3 transmitter is com-
plete and in compliance with all regulations and codes.
1. Remove the cover of the upper wiring compartment of the
transmitter.
2. Attach a conduit fitting and mount the conduit plug in the
spare opening. Pull the power supply wire through the con-
duit fitting.
3. Connect an earth ground to the nearest green ground screw.
See Figure 2. Use a minimum 18 AWG rated up to 85 °C.
4. Connect the positive supply wire to the (+) terminal and the
negative supply wire to the (-) terminal. For Explosion
Proof Installations, see Wiring, Section 3.5.3.
5. Replace the cover and tighten.
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
8
Red (+)Black (-)
Green
Ground
Screws
Protective Conductor Terminal
(+)
(-)


9
2.4 QuickStart Configuration
The E3 MODULEVEL transmitter comes configured with
default values from the factory but can be reconfigured
in the shop. The minimum configuration instructions
required in the field follow. Use the information from
the operating parameters table in Section 2.1.2 before
beginning configuration.
1. Power up the transmitter.
The display changes every 5 seconds to show one of three
values: Status, PV-Lvl (or PV-Ifc or PV-SG) and AI Out.
2. Remove the cover of the lower electronic compartment.
3. Use the and keys to move from one step of the
configuration program to the next step, see Figure 3.
4. Press key. The last character in the
first line of the display changes to an
exclamation point (!).
5. Use the and keys to increase or decrease the value in
the display or to scroll through the choices.
6. Press key to accept a value and move to the next step of
the configuration program (the default password is 1).
7. After entering the last value, allow 10 seconds before
removing power from the transmitter.
The following two configuration entries are the minimum required for
configuration (the default password is 1 from the LCD/keypad).
The following two parameters must be entered if the default values are
not satisfactory.
Lvl Ofst
(xxx)
LvlUnits!
xxx
Proc SG
(xxx)
Enter the actual specific gravity of the process liquid at
operating temperature (N/A for Interface or Density).
Enter the actual operating temperature of the process
Select the desired level units
(inches, cm, m, feet).
Enter the desired level reading when level is at the calibrated
zero reference (typically bottom of the displacer).
¿
¡
ProcTemp
xxx
Enter
Down
Up
LvlUnit
(select)
Liquid
Level
In, cm, m, or ft.
Level Offset
Process S.G.
Operating
Temp.



Liquid
Level
Displacer
Level Offset
Process
S.G.
Operating
Temp.





48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
3.0 Complete Installation
3.1 Unpacking
Unpack the instrument carefully. Take care not to bend the
displacer stem or enclosing tube. Ensure all components
have been removed from the packing material. Check all the
contents against the packing slip and report any discrepan-
cies to the factory.
Before proceeding with the installation, do the following:
Inspect all components for damage. Report any damage to
the carrier within 24 hours.
On chambered units, remove the shipping strap and wire
assembly holding the displacer in place. This assembly must
be removed through the bottom chamber connection before
start-up.
 If reshipping to another location, the displacer must again
be secured using the same strap and wire assembly.
Check that the model number on the nameplate matches
the packing slip and purchase order.
Record the model and serial numbers for future reference
when ordering parts.
Model Number
Serial Number
3.2 Electrostatic Discharge (ESD)
Handling Procedure
MAGNETROL electronic instruments are manufactured
to the highest quality standards. These instruments use
electronic components which may be damaged by static
electricity present in most work environments.
The following steps are recommended to reduce the risk of
component failure due to electrostatic discharge.
Ship and store circuit boards in anti-static bags. If an anti-
static bag is not available, wrap the board in aluminum foil.
Do not place boards on foam packing materials.
Use a grounding wrist strap when installing and removing
circuit boards. A grounded workstation is recommended.
Handle circuit boards only by the edges. Do not touch
components or connector pins.
Ensure that all electrical connections are completely made
and that none are partial or floating. Ground all equipment
to a good, earth ground.
10
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
3.3 Before You Begin
 
Each E3 MODULEVEL transmitter is built to match the
physical specifications of the required installation. Ensure
that the process connection(s) on the vessel matches the
MODULEVEL process connection(s).
See Mounting, Section 3.4.
Ensure that the wiring between the power supply and
MODULEVEL transmitter are complete and correct for the
type of installation.
When installing the MODULEVEL transmitter in a general
purpose or hazardous area, local, state and federal regulations
and guidelines must be observed.
See Wiring, Section 3.5.3.
 
No special equipment or tools are required to install the
Electronic MODULEVEL. The following items are
recommended:
Wrenches, flange gaskets and flange bolting appropriate for
process connection(s)
Flat-blade screwdriver
Level
1
8" Allen wrench
Fieldbus compatible power supply with proper termination

The MODULEVEL transmitter should be located for easy
access for service, configuration, and monitoring. There
should be sufficient headroom to allow installation and
removal of the transmitter head and, in cases of tank top
configuration, the displacer. Special precautions should be
made to prevent exposure to corrosive atmosphere, excessive
vibration, shock, or physical damage.
The operating temperature range for the transmitter elec-
tronics is -40 to +176 °F (-40 to +80 °C). The operating
temperature range for the digital display is -5 to +160 °F
(-20 to +70 °C).
 Operation of all buoyancy type level devices should be
done in such a way as to minimize the action of dynamic
forces on the float or displacer sensing element. Good
practice for reducing the likelihood of damage to the con-
trol is to equalize pressure across the device very slowly.
11
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
3.4 Mounting
The E3 MODULEVEL transmitter can be mounted to a
tank using a variety of configurations and process connec-
tions. Generally, either a threaded, welded or flanged con-
nection is used with an external cage. A flanged connection
is always used on a tank top model. For information
about the sizes and types of connections available, see
Model Numbers, Section 8.7.
Ensure all mounting connections are in place on the tank
and properly sized for the specific unit being installed.
Compare the model on the nameplate with the product
information to ensure the MODULEVEL transmitter is
correct for the intended installation.
If the MODULEVEL must be insulated, DO NOT insulate
the transmitter head, e-tube or finned extensions.
 
Figure 6 illustrates a typical tank top installation.
Before installing, ensure that:
There is adequate headroom for the installation of the
MODULEVEL head and displacer and that it has unob-
structed entry into the vessel.
Using a level, the mounting flange is level within in all
directions.
If the adjustable hanger assembly (P/N 32-3110-001) is
used, it is cut to the required length and attached to the
displacer stem.
NOTE: The adjustable hanger assembly is used when the top of the
displacer and, therefore, the top of the measurement range
must be positioned in the vessel more than 9.31" below the
mounting flange. The standard hanger cable length is 8 feet.
Consult factory for longer cable.
12
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
  
E3A, E3B n/a
200 225 ft-lbs
E3C, E3D, E3E, E3F 150# 110–120 ft-lbs
E3C, E3D, E3E, E3F 300# 180–200 ft-lbs
E3C, E3D, E3E, E3F 600# 180–200 ft-lbs
E3C, E3D, E3E, E3F 900# 370–400 ft-lbs
E3C, E3D, E3E, E3F 1500# 400–450 ft-lbs
E3C, E3D, E3E, E3F 2500# 675–725 ft-lbs
Liquid
Level
Displacer




A stilling well is installed for applications where continuous
agitation is present. The stilling well must be vertically level
so as not to restrict displacer movement.
See Figure 7 for a typical stilling well installation.
The process temperature, pressure and specific gravity are
within the unit’s specifications for installation.
See Specifications, Section 8.6.
To install:
1. Position the head flange gasket on the vessel flange and gen-
tly lower the displacer into the vessel. To prevent damage to
the stem/spring assembly, avoid tipping the unit or, in any
way, putting lateral forces on the stem.
2. Align the flanges and ensure that the gasket is seated properly.
3. Install the flange bolts and nuts and tighten alternating nuts
in a star pattern. Flange bolting torque specifications are
listed on page 12.
 All MODULEVEL units are shipped from the factory with the
enclosing tube tightened and the transmitter head set
screws locked to the enclosing tube. Failure to loosen the
set screws prior to repositioning the supply and output con-
nections may cause the enclosing tube to loosen, resulting
in the possible leakage of the process liquid or vapor.
4. Loosen the transmitter head lock screws (socket type) and
position conduit outlet in the desired direction.
See Figure 8.
5. Retighten lock screws.
NOTE: Since the transmitter head is rotatable through 360º, it is impor-
tant to make certain that the controller locking screws are tight
before making electrical connections.
 
The chamber type MODULEVEL is mounted on the side
of the vessel with either a side/side or side/bottom connection,
as furnished. Figure 9 on page 14 illustrates a typical chamber
type installation.
Before installing, ensure that:
There is adequate room for installation of the MODULEVEL.
Using a level, the vessel mounting connections are level
within in all directions.
The process temperature, pressure and specific gravity are
within the unit’s specifications for installation.
See Specifications, Section 8.6.
If not already done, remove the shipping strap and wire
assembly holding the displacer in place in the chamber. This
assembly must be removed through the bottom chamber
connection or drain before start-up.
13
Size
Always unlock for
repositioning or removal
of head assembly
and always relock,
after final positioning



Use stilling well in
case of turbluent
medium



48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
To install:
1. Align the MODULEVEL process connections with
those on the vessel and attach accordingly, based upon the
connection type. Appropriate gaskets and bolting will be
required for flanged connections. Install the flange bolts and
nuts and tighten alternating nuts in a star pattern. Flange
bolting torque specifications are listed on page 12.
NOTE: It is recommended that shut-off valves be installed in each
equalizing line to the chamber, along with a drain valve (refer to
Figure 8). Equalizing lines should be sized at least as large as
the connections provided at the chamber.
2. Make sure that the chamber is vertically level within in
each direction to ensure frictionless operation of the internal
displacer.
 All MODULEVEL units are shipped from the factory with the
enclosing tube tightened and the transmitter head set
screws locked to the enclosing tube. Failure to loosen the
set screws prior to repositioning the supply and output con-
nections may cause the enclosing tube to loosen, resulting
in the possible leakage of the process liquid or vapor.
3. Loosen the transmitter head lock screws (socket type) and
position conduit outlet in the desired direction. See Figure 8.
4. Retighten lock screws.
NOTE: Since the transmitter head is rotatable through 360º, it is impor-
tant to make certain that the controller locking screws are tight
before making electrical connections.
3.5 Wiring
 FOUNDATION fieldbus E3 MODULEVEL transmitter operates
at voltages of 9–32 VDC. Higher voltage will damage the
transmitter.
Wiring between the power supply and the E3 MODULEVEL
transmitter should be made using minimum of 18 AWG
shielded twisted pair instrument cable. Wiring must be suit-
able for temperatures up to at least +85 °C. Within the
transmitter enclosure, connections are made to the terminal
strip and the ground connections. When installing a remote
mount E3 transmitter, refer to Figures 12 & 13 for wiring
connections.
WARNING! Explosion hazard. Do not disconnect equipment unless
power has been switched off or the area is known to be
non-hazardous.
14
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
Liquid
Level



Red (+)Black (-)
Green
Ground
Screws
Protective Conductor Terminal
(+)
(-)


 
A general purpose installation does not have flammable
media present. Areas rated non-incendive (Cl I, Div. 2) have
flammable media present only under abnormal conditions.
No special electrical connections are required so standard
installation methods may be followed.
To install General Purpose or Non-Incendive wiring:
1. Remove the cover to the wiring compartment of the trans-
mitter. Install the conduit plug in the unused opening. Use
PTFE tape/sealant to ensure a liquid-tight connection.
2. Install a conduit fitting and pull the supply wires.
3. Connect shield to an earth ground at power supply.
4. Connect an earth ground wire to the nearest green ground
screw. Use a minimum 18 AWG rated up to 85 °C.
5. Connect the positive supply wire to the (+) terminal and the
negative supply wire to the (-) terminal.
6. Replace the cover to the wiring compartment of the
transmitter.
To install Remote Mount wiring:
1. Install conduit from the remote mounted head to the
integral conduit connection of the E3 transmitter (refer to
local plant or facility procedures).
2. Remove the cover of the remote transmitter, terminal board
housing and of the integral terminal board housing.
3. Connect one end of the six conductor cable (P/N
037-3226-xxx or 037-3227-xxx) to the integral terminal
block and the other end to the terminal block within the
remote terminal board housing. Be sure to match the six
discrete numbered wires with the numbers on each terminal
block. See Figures 12 & 13.
4. Connect shield to an earth ground at the power supply.
5. Connect an earth ground wire to the nearest green ground
screw per local electrical code (not shown in illustration).
6. Connect the positive supply wire to the (+) terminal and the
negative supply wire to the (-) terminal.
7. Replace the covers to the wiring compartment of the
transmitter and to both terminal board housings. Ensure
that all covers are completely tightened down before apply-
ing power.
 
An intrinsically safe (IS) installation potentially has flamma-
ble media present. An approved IS barrier must be installed
in the non-hazardous (safe) area. Consult factory for agency
drawing.
15
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus




123456
W
hite
Black
G
reen
B
lack
R
ed
B
lack
To install Intrinsically Safe wiring:
1. Make sure the IS barrier is properly installed in the safe area
(refer to local plant or facility procedures). Complete the
wiring from the barrier to the E3 transmitter.
2. After IS barrier installation, follow General Purpose and
Non-incendive wiring procedure on page 15.
 
Explosion Proof (XP) is a method of designing equipment
for installation in hazardous areas. A hazardous location is
an area in which flammable gases or vapors are, or may be,
present in the air in quantities sufficient to produce explo-
sive or ignitable mixtures. The wiring for the transmitter
must be contained in Explosion Proof conduit extending
into the safe area.
To install Explosion Proof wiring Integral mount:
Due to the specialized design of the Integral E3 transmitter,
no Explosion Proof conduit fitting (EY seal) is required
within 18" of the transmitter. An Explosion Proof conduit
fitting (EY seal) is required between the hazardous and safe
areas. See Agency Approvals, Section 8.4.
1. Install Explosion Proof conduit from the safe area to the
conduit connection of the E3 transmitter (refer to local
plant or facility procedures).
2. Remove the cover to the wiring compartment of the
transmitter.
3. Connect shield to an earth ground at the power supply.
4. Connect an Earth ground wire to the nearest green ground
screw per local electrical code. Use a minimum 18 AWG
rated up to 85 °C.
5. Connect the positive supply wire to the (+) terminal and the
negative supply wire to the (-) terminal.
6. Replace the cover to the wiring compartment of the
transmitter before applying power.
 Instrument and conduit junction box covers must be in
place and tightly sealed at all times during operation.
To install Explosion Proof wiring Remote mount:
1. Install Explosion Proof conduit from the remote mounted
E3 transmitter head to the integrally mounted terminal
housing at the LVDT. An Explosion Proof conduit fitting
(EY seal) is required within 18" of the remote mounted
transmitter head wiring housing (see figure 13). Follow
steps 2 through 7 of Remote Mount wiring procedure on
page 15.
16
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
Integral
Terminal Board
Remote
Terminal Board
Conduit seal
within 18" of
this housing
entry for
explosion proof
installation
Integral Wiring &
LVDT Housings
Remote Wiring &
Transmitter Housings
White
Black
Green
Black
Red
Black
White
Black
Green
Black
Red
Black


17
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
4.0 Function Blocks
4.1 Overview
The E3 MODULEVEL Liquid Level Displacer Transmitter
operates on the Archemedes principle of buoyancy force.
Refer to Bulletin 48-635 for more detailed information on
the MODULEVEL transmitter.
The E3 MODULEVEL is a liquid level transmitter with
four F
O
UNDATION
fieldbus
Blocks (one Resource Block,
one Transducer Block, one Analog Input Function block,
and one PID Function block. The idea of Function Blocks,
which a user can customize for a particular application, is a
key concept of Fieldbus topology. Function Blocks consist
of an algorithm, inputs and outputs, and a user-defined
name.
The TRANSDUCER block output is available to the
network through the ANALOG INPUT block.
The ANALOG INPUT block (AI) takes the TRANSDUCER
block level or density value and makes it available as an
analog value to other function blocks. The AI block has
scaling conversion, filtering, and alarm functions.
 
The following are general descriptions of the parameters
common to all blocks. Additional information for a given
parameter is described later in that specific block section.
ST_REV (static data revision): a read only parameter that
gives the revision level of the static data associated with the
block. This parameter will be incremented each time a static
parameter attribute value is written and is a vehicle for
tracking changes in static parameter attributes.
TAG_DESC (tag descriptor): a user assigned parameter
that describes the intended application of any given block.
STRATEGY: a user assigned parameter that identifies
groupings of blocks associated with a given network connec-
tion or control scheme.
ALERT_KEY: a user assigned parameter which may be used
in sorting alarms or events generated by a block.
MODE_BLK: a structured parameter composed of the
actual mode, the target mode, the permitted mode(s), and
the normal mode of operation of a block.
The actual mode is set by the block during its execution to
reflect the mode used during execution.
The target mode may be set and monitored through the
mode parameter.
18
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
The permitted modes are listed for each block.
The block must be in an automatic mode for normal
operation.
NOTE: The MODE_BLK target parameter must be OOS (out of service)
to change configuration and calibration parameters in that func-
t
ion block (when in OOS, the normal algorithm is no longer exe-
cuted and any outstanding alarms are cleared).
All blocks must be in an operating mode for the device to oper-
ate. This requires the Resource Block to be in “AUTO” and the
Transducer Block to be in “AUTO” before the Function Blocks
can be placed in a mode other than OOS (out of service).
BLOCK_ERR: a parameter that reflects the error status of
hardware or software components associated with, and
directly affecting, the correct operation of a block.
NOTE: A BLOCK_ERR of “Simulation” in the Resource Block does not
mean simulation is active—it merely indicates that the simula-
tion enabling hardware jumper is installed.
4.2 Resource Block
The RESOURCE block contains data specific to the
E3 MODULEVEL transmitter, along with some
information about the firmware.
NOTE: The Resource Block has no control function.
MODE_BLK: Must be in AUTO in order for the remain-
ing blocks in the transmitter to operate.
NOTE: A Resource Block in “out of service” will stop all function block
execution in the transmitter.
RS_STATE (Resource State): identifies the state of the
RESOURCE block state machine. Under normal operating
conditions, it should be “On-Line.”
DD_RESOURCE: a string identifying the tag of the
resource that contains the Device Description for this device.
MANUFAC_ID: contains the MAGNETROL International,
Incorporated F
OUNDATION fieldbus
manufacturers ID
number, which is 0x000156.
DEV_TYPE: the model number of the E3 MODULEVEL
transmitter (0x0003). It is used by interface devices to
locate the Device Descriptor (DD) file for this product.
DEV_REV: contains the firmware revision of the
E3 MODULEVEL transmitter. It is used by interface
devices to correctly select the associated DD.
19
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
DD_REV: contains the revision of the DD associated with
the version of firmware in the E3 MODULEVEL transmitter.
It is used by interface devices to correctly select the associat-
ed DD.
RESTART: Default and Processor selections are available.
Default will reset the Model E3 to the default block
configuration.
NOTE: RESTART DEFAULT will not reset parameters to their default
values in the custom Transducer Block.
FEATURES: a list of the features available in the transmit-
ter. The Model E3 features include Reports, and Software
Write Locking.
FEATURES_SEL: allows the user to turn Features on or off.
CYCLE_TYPE: identifies the block execution methods that
are available.
CYCLE_SEL: allows the user to select the block execution
method.
MIN_CYCLE_T: the time duration of the shortest cycle
interval. It puts a lower limit on the scheduling of the
resource.
NV_CYCLE_T: the minimum time interval between copies
of non-volatile (NV) parameters to NV memory. NV mem-
ory is only updated if there has been a significant change in
the dynamic value and the last value saved will be available
for the restart procedure. A value of “0” means it will never
be automatically copied. Entries made by human interface
devices to NV parameters are copied to non-volatile memory
at the time of entry.
NOTE: After completing a large copy, allow several minutes before
removing power from the E3 MODULEVEL transmitter to ensure
that all data has been saved.
FREE_SPACE: shows the amount of available memory for
further configuration. The value is zero percent in a pre-
configured device.
FREE_TIME: the amount of the block processing time that
is free to process additional blocks.
SHED_RCAS: the time duration at which to give up com-
puter writes to function block RCas locations. Shed from
RCas will never happen when SHED_RCAS = 0.
SHED_ROUT: the time duration at which to give up com-
puter writes to function block ROut locations. Shed from
ROut will never happen when SHED_ROUT = 0.
20
48-640 E3 Modulevel
®
Displacer Level Transmitter - FOUNDATION fieldbus
FAULT_STATE, SET_FSTATE, CLR_FSTATE: these only
apply to output function blocks. (The E3 MODULEVEL
has no output function blocks).
MAX_NOTIFY: the maximum number of alert reports that
the transmitter can send without getting a confirmation.
The user can set the number low, to control alert flooding,
by adjusting the LIM_NOTIFY parameter value.
LIM_NOTIFY: the maximum numbers of unconfirmed
alert notify messages allowed. No alerts are reported if set
to zero.
CONFIRM_TIME: the time that the transmitter will wait
for confirmation of receipt of a report before trying again.
Retry will not occur if CONFIRM_TIME = 0.
WRITE_LOCK: When set to LOCKED, will prevent any
external change to the static or non-volatile data base in the
Function Block Application of the transmitter. Block con-
nections and calculation results will proceed normally, but
the configuration will be locked.
UPDATE_EVT (Update Event): is an alert generated by a
write to the static data in the block.
BLOCK_ALM (Block Alarm): is used for configuration,
hardware, connection, or system problems in the block. The
cause of any specific alert is entered in the subcode field.
The first alert to become active will set the Active status in
the Status attribute. As soon as the Unreported status is
cleared by the alert reporting task, another block alert may
be reported without clearing the Active status, if the sub-
code has changed.
ALARM_SUM (Alarm Summary): contains the current
alert status, the unacknowledged states, the unreported
states, and the disabled states of the alarms associated with
the block.
ACK_OPTION (Acknowledge Option): selects whether
alarms associated with the block will be automatically
acknowledged.
WRITE_PRI (Write Priority): the priority of the alarm
generated by clearing the write lock.
WRITE ALM (Write Alarm): the alert generated if the
write lock parameter is cleared.
ITK_VER (ITK Version): contains the version of the
Interoperability Test Kit (ITK) used by the Fieldbus
Foundation during their interoperability testing.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Magnetrol E3 Modulevel Foundation Fieldbus User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI