HTP Elite XL Boiler Operating instructions

Type
Operating instructions
Isolation Valve Instructions
ELX-400 - 1000kBTUh Boiler Models Part # 7550P-985, ELX-1500 - 2000kBTUh Boiler Models Part # 7550P-986
272 Duchaine Blvd.
New Bedford, MA 02745
1(800) 323-9651
lp-754 Rev. 8.25.20
STOP! Follow these instructions or warranty will be void!
Installation Must Comply With:
1. National Electrical Code
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and CGA
No. B149 (latest version)
3. Local, state, provincial, and national codes, laws, regulations, and
ordinances.
This installation shall be done by a qualied service agency in
accordance with these instructions, all applicable codes, and
requirements of the authority having jurisdiction. Failure to follow
these instructions could result in substantial property damage,
severe personal injury, or death.
Included with Kit 7550P-985:
Item # Part # Description Quantity
1 7550P-615 BELIMO MOTORIZED ISOLATION VALVE 1
2 7550P-613 2” THREADED FLANGE 2
3 7550P-614 5/8” - 11 X 2 1/2” LONG BOLTS 8
4 7550P-612 WASHER FOR 5/8” BOLT 8
LP-754 Instructions 1
Tools Required (Not Included):
15/16” Ratchet, Socket driver, or Wrench
Flat Head Screwdriver
Remove all items from the packaging and ensure that all parts
and accessories are included in the kit. Any claims for damage
or shortage in shipment must be led immediately against the
transportation company by the consignee.
Installer - Read all instructions in this manual before installing.
Perform steps in the given order. Obey all local codes. Obtain all
applicable permits before installing this isolation valve.
NOTE: Install all components in such a manner that does not
reduce the performance of any re rated assembly.
User - These instructions are for use only by a qualied heating
installer / service technician.
FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE
CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE
PERSONAL INJURY, OR DEATH.
Figure 1 - Installed 400 - 1000kBTU Model Valve
Included with Kit 7550P-986:
Item # Part # Description Quantity
1 7550P-038 BELIMO MOTORIZED ISOLATION VALVE 1
2 7550P-614 5/8” - 11 X 2 1/2” LONG BOLTS 8
3 7550P-612 WASHER FOR 5/8” BOLT 8
LP-754 Instructions 1
Preparing for Installation:
When working on heating equipment, observe all precautions in the
literature, on tags, and on labels attached to the boiler. Follow all
safety codes. Wear safety glasses and work gloves. Have a re
extinguisher available.
DO NOT power or ll the boiler with water. It is best practice to install
this kit BEFORE powering or lling the boiler.
If the boiler IS powered and/or lled with water, turn o power to the
boiler, and valve it o to isolate it from the system. Then drain the
boiler. Close the drain valve after draining.
Valve Orientation:
The valve can be oriented in any position as long as the actuator does
not go below the horizontal plane. See the orientation guide from
Belimo attached to the valve.
Installing the Valve on ELX-400 - 1000 Models:
1. Use pipe dope / tape to thread one of the 2” anges onto the
supply pipe of the boiler.
2. Install the isolation valve using the supplied bolts and washers.
3. Install the other 2” ange to the isolation valve using the supplied
bolts and ange. See Figure 1.
NOTE: A separate service valve MUST be installed for each boiler.
Do not overtighten any of the bolts as this may damage the
threads and prevent the bolts from turning. Replacement bolts are
not included in this kit.
These valves DO NOT qualify as service valves.
Installing the Valve on ELX-1500 - 2000 Models:
Install the isolation valve using the supplied bolts and washers. See
Figure 2.
NOTE: A separate service valve MUST be installed for each boiler.
Figure 2 - Installed 1500 - 2000kBTU Model Valve
lp-754 Rev. 8.25.20
2
Valve Wiring:
The valves are supplied with 16 feet of power cable. The power cable is
permanently connected to the valve and cannot be removed.
NOTE: Avoid excess wire length. The power cable may be cut, stripped,
and connected to reduce length. Ensure enough slack to avoid wire
damage.
Figure 3 - Piping Drawing
Figure 4 - Valve Wiring
Figure 5 - 400 - 1000kBTU Model Wiring
Piping Example:
Field
Supplied
Jumper
Figure 6 - 1500 - 2000kBTU Model Wiring
WARNING! LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components.
Have a qualied licensed electrician or other individual who has
been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions
when exposed to live electrical components could result in serious
personal injury or death.
Wiring 400 - 1000kBTU Models:
Wiring 1500 - 2000kBTU Models:
NOTE: Requires a small eld supplied 120V jumper from L1 to center
common terminal on the CH pump output.
The thermostat (TT) must always be closed when the pumps are
running.
lp-754 Rev. 8.25.20
3
Starting the Boiler, Test Instructions, and Instructions for Opening the Valve if Valve Fails:
1. Turn the water supply on and rell the boiler. Check for leaks around the boiler, installed components, and associated piping. Fill and purge
as described in the boiler installation manual. Ensure all air is purged before proceeding.
WARNING
!
The boiler must be full of water before it is powered. Failure to ensure the boiler is full of water could result in substantial property damage,
serious personal injury, or death.
2. Power on the boiler.
To Test the Valve:
1. Enter Service Mode.
Service Mode can be
accessed from the
Home Screen or by
scrolling through the
Installer Settings. Input
Access Code 928 when
prompted to enter
Service Mode.
2. Toggle the Boiler
Pump ON. The isolation
valve will open when
the pump engages.
3. If the isolation valve
does not open, toggle
the Boiler Pump OFF.
Turn power o to the
boiler and check wiring.
4. After wiring is
corrected, restore
power to the boiler,
enter Service Mode, and
toggle the Boiler Pump
ON again.
Pump Service Mode
Internal LWCO Test
Service Mode
On/O
Boiler
Pump
READY
DWH
Pump
4500
5000
1700
4500
Setpoint
MAX
MIN
Actual
Test
OFF
ON
ON
Reset
OFF
System
Pump
PWM
40%
PRESS SERVICE RESET
AFTER PERFORMING
REQUIRED SERVICE
0V
0-10 Volt
OFF
OFF
ON
ON
ON
OFF
Service Mode
ON
141 F
74 F
Gas Valve: ON
Flame Current: 4.7 uA
PREVIOUS
Service Mode - Pump Test
Toggle to test Pump / Valve operation.
Maintenance Reset
Supply
Return
Figure 7 - Service Mode Screen - Pump Test
If the Valve or Valve Power Should Fail:
1. Insert the included handle into the valve. See Figure 8.
2. Turn the handle clockwise until the valve fully opens (until the handle will not turn any more). Then toggle the switch on the valve to lock it
open. See Figure 9. Heat transfer uid will now be able to circulate through the system.
3. To close the valve, simply toggle the switch from locked to unlocked. The valve will return to the open position. See Figure 10.
Figure 8 - Handle Installed in Valve
Figure 9 - Valve Open and Locked Figure 10 - Valve Closed and Unlocked
Locked
Open
Closed
Unlocked
  • Page 1 1