Isolation Valve Instructions
ELX-400 - 1000kBTUh Boiler Models Part # 7550P-985, ELX-1500 - 2000kBTUh Boiler Models Part # 7550P-986
272 Duchaine Blvd.
New Bedford, MA 02745
1(800) 323-9651
lp-754 Rev. 8.25.20
STOP! Follow these instructions or warranty will be void!
Installation Must Comply With:
1. National Electrical Code
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and CGA
No. B149 (latest version)
3. Local, state, provincial, and national codes, laws, regulations, and
ordinances.
This installation shall be done by a qualied service agency in
accordance with these instructions, all applicable codes, and
requirements of the authority having jurisdiction. Failure to follow
these instructions could result in substantial property damage,
severe personal injury, or death.
Included with Kit 7550P-985:
Item # Part # Description Quantity
1 7550P-615 BELIMO MOTORIZED ISOLATION VALVE 1
2 7550P-613 2” THREADED FLANGE 2
3 7550P-614 5/8” - 11 X 2 1/2” LONG BOLTS 8
4 7550P-612 WASHER FOR 5/8” BOLT 8
LP-754 Instructions 1
Tools Required (Not Included):
15/16” Ratchet, Socket driver, or Wrench
Flat Head Screwdriver
Remove all items from the packaging and ensure that all parts
and accessories are included in the kit. Any claims for damage
or shortage in shipment must be led immediately against the
transportation company by the consignee.
Installer - Read all instructions in this manual before installing.
Perform steps in the given order. Obey all local codes. Obtain all
applicable permits before installing this isolation valve.
NOTE: Install all components in such a manner that does not
reduce the performance of any re rated assembly.
User - These instructions are for use only by a qualied heating
installer / service technician.
FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE
CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE
PERSONAL INJURY, OR DEATH.
Figure 1 - Installed 400 - 1000kBTU Model Valve
Included with Kit 7550P-986:
Item # Part # Description Quantity
1 7550P-038 BELIMO MOTORIZED ISOLATION VALVE 1
2 7550P-614 5/8” - 11 X 2 1/2” LONG BOLTS 8
3 7550P-612 WASHER FOR 5/8” BOLT 8
LP-754 Instructions 1
Preparing for Installation:
When working on heating equipment, observe all precautions in the
literature, on tags, and on labels attached to the boiler. Follow all
safety codes. Wear safety glasses and work gloves. Have a re
extinguisher available.
DO NOT power or ll the boiler with water. It is best practice to install
this kit BEFORE powering or lling the boiler.
If the boiler IS powered and/or lled with water, turn o power to the
boiler, and valve it o to isolate it from the system. Then drain the
boiler. Close the drain valve after draining.
Valve Orientation:
The valve can be oriented in any position as long as the actuator does
not go below the horizontal plane. See the orientation guide from
Belimo attached to the valve.
Installing the Valve on ELX-400 - 1000 Models:
1. Use pipe dope / tape to thread one of the 2” anges onto the
supply pipe of the boiler.
2. Install the isolation valve using the supplied bolts and washers.
3. Install the other 2” ange to the isolation valve using the supplied
bolts and ange. See Figure 1.
NOTE: A separate service valve MUST be installed for each boiler.
Do not overtighten any of the bolts as this may damage the
threads and prevent the bolts from turning. Replacement bolts are
not included in this kit.
These valves DO NOT qualify as service valves.
Installing the Valve on ELX-1500 - 2000 Models:
Install the isolation valve using the supplied bolts and washers. See
Figure 2.
NOTE: A separate service valve MUST be installed for each boiler.
Figure 2 - Installed 1500 - 2000kBTU Model Valve