COLD WEATHER HANDLING - If the boiler has been stored in
a very cold location (BELOW 0
o
F) before installation, handle
with care until the components come to room temperature.
Failure to do so could result in damage to the boiler.
This boiler is certied for indoor use only. DO NOT INSTALL
OUTDOORS. Outdoor installations ARE NOT covered by
warranty. Failure to install the boiler indoors could result in
property damage, severe personal injury, or death.
A. Locating the Boiler
Incorrect ambient conditions can lead to damage to the
heating system and put safe operation at risk. Ensure that
the installation location adheres to the information included
in this manual. Failure to do so could result in property
damage, serious personal injury, or death. Failure of boiler
or components due to incorrect operating conditions IS NOT
covered by product warranty.
1. Installation Area (Mechanical Room) Operating Conditions
• Ensure ambient temperatures are higher than 32
o
F /
0
o
C and lower than 104
o
F / 40
o
C
• Prevent the air from becoming contaminated by the
products, places, and conditions listed in this manual
• Avoid continuously high levels of humidity
• Never close existing ventilation openings
• Ensure a minimum 1” clearance around hot water and
exhaust vent pipes
• NOTE: To prevent condensing in the fan, it is
recommended to avoid prolonged exposure to
temperatures below 45
o
F
This boiler has a condensate disposal system that may
freeze if exposed to sustained temperatures below 32
o
F.
Precautions should be taken to protect the condensate trap
and drain lines from sustained freezing conditions. Failure
to take precautions could result in property damage, severe
personal injury, or death.
2. Check for nearby connections to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power
• Condensate drain
Failure to keep the boiler area clear and free of combustible
materials, liquids, and vapors can result in substantial property
damage, severe personal injury, or death.
High heat sources (generating heat 100
o
F / 37
o
C or greater,
such as boiler ue pipes, space heaters, etc.) may damage
plastic components of the boiler as well as plastic vent pipe
materials. Such damages ARE NOT covered by warranty. It is
recommended to keep a minimum clearance of 8” from high
heat sources. Observe heat source manufacturer instructions,
as well as local, state, provincial, and national codes, laws,
regulations, and ordinances when installing this boiler and
related components near high heat sources.
Locate the boiler where any leakage from the relief valve,
related piping, tank, or connections will not result in damage
to surrounding areas or lower oors of the building. The boiler
should be located near a oor drain or installed in a drain pan.
Leakage damages ARE NOT covered by warranty.
The service life of the boiler’s exposed metallic surfaces, such
as the casing, as well as internal surfaces, such as the heat
exchanger, are directly inuenced by proximity to damp and
salty marine environments. In such areas higher concentration
levels of chlorides from sea spray coupled with relative humidity
can lead to degradation of boiler components. In these
environments, boilers must not be installed using direct vent
systems which draw outdoor air for combustion. Such boilers
must be installed using room air for combustion. Indoor air
will have a much lower relative humidity, and hence potential
corrosion will be minimized.
Failure of the boiler or components due to incorrect operating
conditions IS NOT covered by product warranty.
Carefully consider installation when determining boiler
location. Please read the entire manual before attempting
installation. Failure to properly take factors such as boiler
venting, piping, condensate removal, and wiring into account
before installation could result in wasted time, money, and
possible property damage and personal injury.
4. Gas control system components must be protected from
dripping water during operation and service.
5. If the boiler is to replace an existing boiler, check for and
correct any existing system problems, such as:
• System leaks
• Location that could cause the system and boiler to freeze
and leak
• Incorrectly sized expansion tank
6. Clean and ush system when reinstalling a boiler.
NOTE: When installing in a minimum clearance location, it
may not be possible to read or view some product labeling. It
is recommended to make note of the boiler model and serial
number.
Use extreme care not to drop the boiler or cause bodily injury
while lifting the boiler. Failure to follow these instructions could
result in property damage, severe personal injury, or death.
This boiler must be installed upright in the vertical position
as described in this manual. DO NOT attempt to install this
boiler in any other orientation. Doing so will result in improper
boiler operation and property damage, and could result in
serious personal injury or death.
3. Check area around boiler. Remove any combustible materials,
gasoline, and other ammable liquids.