puravent Thermozone AR 300 E/W Water Heat Air Curtain User manual

Type
User manual
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
R
AR 300
0,1 m
3,5 m
2,0 m
3,0 m
1,0 m
10 m/s
4,1 m/s
5,4 m/s
3,5 m/s
AMCA*2
13,3 m/s
4,8 m/s
6,7 m/s
3,7 m/s
3,3 m/s3,4 m/s
Peak*1
2
3
Thermozone AR 300 E/W
Thermozone® AR 300 E/W
Application
AR300 is especially suited for environments with high
demands in respect of design. The recessed installation
is very discreet and the built-in control contributes
further to the concealed appearance.
Comfort
Several factors need to cooperate to create a comfort-
able indoor climate. With Thermozone Technology
an efficient air separation is created in combination
with a low sound level. The dual functionality as air
curtain when the door is open and part of the heating
system when the door is closed also contributes to good
comfort.
Operation and economy
The air curtain has a low energy consumption thanks to
Thermozone Technology and the extra function as heat
source means further savings. Built-in controls, easy
installation and maintenance minimizes the cost and
the risk for errors.
Design
AR300 is designed for recessed installation and
colouring is possible to make it blend even better with
the premises.
Water heat
Electrical heat
Air velocity profile
Product specifications
*1)
*2)
Recessed air curtains for installation heights up to 3.5 metres.
Optimized airflow with Thermozone Technology.
Intelligent, built-in control, operating both when
the door is open and when it is closed gives the air
curtain dual functionality.
Possibility to integrate the air curtain with a BMS
system.
The frame and hatch can be painted in an optional
colour.
Corrosion proof housing made of hot zinc plated and
powder enamelled steel panels. Colour (frame and
hatch): RAL 9016, NCS 0500.
Peak values
Mean values. Measurements made according to AMCA 220 "Test methods
for Air Curtain Units"
Lengths 1, 1.5 and 2 metres
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
Thermozone AR 300 E/W
Control
The built-in control of AR300 is designed to give
the highest level of functionality while minimizing
installation and daily operation. No additional wiring or
external controls are needed. If the distance between
the eye and the reflector is too long, it is possible to use
an external door contact instead (accessory).
The air curtain operates at its maximum performance
in all situations and is not dependent on day-to-day
adjustments.
When the door is open the air curtain separates
outdoor and indoor air and provides heat if it is needed.
When the door is closed the air curtain operates as
part of the heating system supplying additional heat if
indoor temperature falls below desired temperature.
There are also possibilities to connect the air curtain to
a BMS system for on/off control and alarm indication.
The IR-eye detects when the door
is open and closed. The thermostat
is located by the air intake and heat
or ambient mode is set by a push
button. Alarm indication by LED.
The thermostat setting
and open door fan speed
selection is hidden under the
cover.
Design and specifications are subject to change without notice.
Protection class AR300E/W recessed mounting: above false ceiling – splash-proof design (IP44), below false ceiling:
normal design (IP20).
Approved by SEMKO and CE compliant.
Technical specifications | Thermozone AR 300 E electrically heated 3
Type Output steps
[ kW]
Airflow
[m3/h]
t*1
[°C]
Sound level*2
[dB(A)]
Voltage
Amperage
(control)
Voltage
Amperage
(heat)
LxHxW
[mm]
Weight
[kg]
AR310E09 0/4,5/9 1000/2000 27/14 43/59 230V~ / 2,1A 400V3~ / 13A 1057x302x595 42
AR315E14 0/7/13,5 1400/2800 29/15 43/60 230V~ / 2,9A 400V3~ / 19,5A 1567x302x595 58
AR320E18 0/9/18 2000/4000 27/14 46/63 230V~ / 4,2A 400V3~ / 26A 2073x302x595 78
Technical specifications | Thermozone AR 300 W water heated 2
Type Output steps*3
[ kW]
Airflow
[m3/h]
t*1,3
[°C]
Sound level*2
[dB(A)]
Voltage
[V]
Amperage
[A]
LxHxW
[mm]
Weight
[kg]
AR310W 16 1000/2000 30/23 43/58 230V~ 2,1 1057x302x595 42
AR315W 23 1400/2800 31/24 43/59 230V~ 2,9 1567x302x595 58
AR320W 33 2000/4000 31/25 46/62 230V~ 4,2 2073x302x595 78
*1) t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*2) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m2.
*3) Applicable at water temperature 80/60 oC, air temperature, in +15 oC.
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
A
302
B
C
638
523
595
Thermozone AR 300 E/W
Dimensions
Type A
[mm]
B
[mm]
C
[mm]
AR310E/W 1057 1016 1067
AR315E/W 1567 1526 1577
AR320E/W 2073 2031 2083
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
1
2
3
4
5
6
From below
From side/below
5
0
°
2
0
°
Thermozone AR 300 E/W
Mounting and connection
Mounting
AR300 unit is installed horizontally with the supply air
grille facing downwards as close to the door as possible,
concealed in the false ceiling. The only visible part of the
unit is the underside that is level with the ceiling.
For the protection of wider doorways, several units can
be mounted next to each other. Ensure that the service
hatch is accessible and can be fully opened.
Minimum distance from outlet to floor is 1800 mm, see
Fig. 1.
Adjusting
An IR-eye is mounted on AR300. A piece of reflector
tape is also supplied. The door sensor can be directed
up/down to ”see” the tape, see Fig. 1. The maximum
distance between the IR-eye and the reflecting tape is
1,8 m. If higher degrees are needed should the reflecting
tape be angled towards the IR-eye. This is easily done
with the enclosed cylinder cut to the right angle.
When the distance between the eye and the reflector is
too far, an external door contact (AR300DS) can be used.
Connection AR 300 E 3
Connection is made on the top or on the side of the unit
with a five-wired cable with earth. The supply terminal
block is intended for a cable of maximum 16 mm². See
wiring diagrams.
Connection AR 300 W 2
Connection is made with cable and plug. Connection
of water pipes to the water heating coil is of type DN20
(3/4”), inside thread. Cable glands can be made from the
back, top or the sides of the unit. There are premarked
holes for drilling at these locations. See Fig. 2 and wiring
diagrams.
Fig. 2: Water connections
Fig. 1: Adjustment of the IR-eye downwards/upwards and minimum
distance to floor.
Reflecting tape
Door
Min. 1,8 m
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
Thermozone AR 300 E/W
Electrical 3
The IR-eye detects when the door is open and closed.
Airflow and heat output are controlled automatically
based upon room temperature and whether the door
is open or closed. High speed can be set on 4 different
speeds.
When the door is open the fan runs on high speed,
when the door closes the fan will continue to run on
high speed for 60 seconds and then on low speed for 60
seconds. When the door is closed the fan runs on low
speed if there is a need for heating, if not the fan will be
switched off. If the temperature decreases further, the
fan will run on high speed.
The built-in room thermostat controls the heat
output. E.g. the thermostat is set on 20 °C and the
difference between the stages 2 °C. The thermostat will
activate below 20 °C when the door is closed. When the
door opens, the thermostat will activate below 22 °C
and normally the heat is switched on.
Possibility to choose between heat/ambient mode
(summer case). Alarm, door status and heat/ambient
mode is indicated with diodes on the IR-unit.
Complete control kit:
- Built-in control, controls the airflow and heat output
in 2 steps.
Water 2
The IR-eye detects when the door is open and closed.
Airflow and heat output are controlled automatically based
upon room temperature and whether the door is open or
closed. High speed can be set on 4 different speeds.
When the door is open the fan runs on high speed, when
the door closes the fan will continue to run on high speed
for 60 seconds and then on low speed for 60 seconds. When
the door is closed the fan runs on low speed if there is a
need for heating, if not the fan will be switched off. If the
temperature decreases further, the fan will run on high
speed.
The built-in room thermostat controls the heat output.
E.g. the thermostat is set on 20 °C and the difference
between the stages 2 °C. The thermostat will activate below
20 °C when the door is closed. When the door opens, the
thermostat will activate below 22 °C and normally the heat
is switched on.
Possibility to choose between heat/ambient mode
(summer case). Alarm, door status and heat/ambient mode
is indicated with diodes on the IR-unit.
Water flow has to be regulated by using the VR20/25
Valve Set, see table below (accessory).
Complete control kit:
- Built-in control, controls the airflow and heat output.
- VR20/25, valve set.
Control kits
Accessories
AR300ERS, external room sensor
If an external room sensor is needed, use the
AR300ERS. The external room sensor is supplied with
7 m cable and a modular contact for easy and quick
installation (no other adjustments are needed to get
the accessories working). The connection of the room
sensor is done on the control box accessible by opening
the service hatch of the AR300.
AR300DS, external door contact
When the distance between the eye and the reflector is
too long an external door contact AR300DS is needed.
The external door contact is supplied with 7 m cable
and a modular contact for easy and quick installation
(no other adjustments are needed to get the accessories
working). The connection of the door contact is done on
the control box accessible by opening the service hatch
of the AR300.
Type VR20 VR25
AR310W 60/40 X
80/60 X
AR315W 60/40 X
80/60 X
AR320W 60/40 X
80/60 X
Type Description HxWxD
[mm]
AR300ERS External room sensor 80x80x31
AR300DS External door contact
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
Frico AB
031 336 86 00
www.frico.se
Thermozone AR 300 E/W
Output charts water
Incoming / outgoing water temperature 90/70 °C
Incoming air temp.= +15 °C Incoming air temp. = +20 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
AR310W high 2000 19 43 0,23 17 46 0,21
low 1000 12 51 0,15 11 53 0,14
AR315W high 2800 28 44 0,34 25 47 0,31
low 1400 18 52 0,22 16 54 0,20
AR320W high 4000 40 44 0,49 36 47 0,45
low 2000 25 52 0,31 23 54 0,28
Incoming / outgoing water temperature 80/60 °C
Incoming air temp.= +15 °C Incoming air temp. = +20 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
AR310W high 2000 16 38 0,19 14 41 0,17
low 1000 10 45 0,13 9 47 0,11
AR315W high 2800 23 39 0,29 21 42 0,26
low 1400 15 46 0,18 13 48 0,16
AR320W high 4000 33 40 0,41 30 42 0,37
low 2000 21 46 0,26 19 48 0,23
Incoming / outgoing water temperature 60/40 °C
Incoming air temp.= +15 °C Incoming air temp. = +20 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
AR310W high 2000 9 29 0,12 8 32 0,10
low 1000 6 33 0,08 5 35 0,06
AR315W high 2800 14 30 0,17 11 32 0,14
low 1400 9 34 0,11 7 36 0,09
AR320W high 4000 20 30 0,25 17 33 0,21
low 2000 13 34 0,16 11 36 0,13
Incoming / outgoing water temperature 60/30 °C
Incoming air temp.= +15 °C Incoming air temp. = +20 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
AR310W high 2000 7 25 0,06 5 28 0,04
low 1000 5 29 0,04 3 31 0,03
AR315W high 2800 10 26 0,08 8 28 0,06
low 1400 7 29 0,06 5 31 0,04
AR320W high 4000 15 26 0,13 12 29 0,09
low 2000 10 30 0,08 8 32 0,06
Incoming / outgoing water temperature 55/35 °C
Incoming air temp.= +15 °C Incoming air temp. = +20 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
AR310W high 2000 8 27 0,10 6 29 0,08
low 1000 5 30 0,06 4 32 0,05
AR315W high 2800 11 27 0,14 9 30 0,11
low 1400 7 31 0,09 6 33 0,07
AR320W high 4000 17 28 0,21 13 30 0,16
low 2000 11 31 0,13 9 33 0,11