Low Ambient Control Kit #918797 (Replaces Kit #917163)
This Low Ambient Control Kit monitors the Stage 1 com-
pressor discharge pressure and cycles the outdoor fan(s)
On and OFF as required to maintain a high evaporator
temperature. Outdoor fan cycling allows the system to
operate without freezing the evaporator coil and losing
capacity during low ambient conditions.
Read these instructions in their entirety before pro-
ceeding with the installation of the pressure control
switch and wiring.
Installation (See Figure 1)
R4G*-090/120 Series
1. Set indoor thermostat to “OFF” position.
2. Disconnect all electrical power to appliance.
3. Remove compressor access and control access panel
covers.
4. Assemble the copper connecting tube, one end to the
head pressure control assembly and the other end to
the open service port of the “T” adapter provided with
this kit. Remaining port with schrader valve will be
used for service. Tighten as required to ensure leak
free connections.
5. Locate the head pressure control assembly on
compressor side of the compressor/blower divider
panel. Mount the pressure control in the vicinity of the
outdoor motor capacitor(s) using self drilling screws
provided or drill 1/8" diameter holes on 2-3/4" centers.
6. Attach the “T” adapter to Stage 1 compressor discharge
service port. Care should be taken not to kink the
copper tube while extending. Position tube away from
other components in the unit and leave a minimum of
one loop in coil for vibration dampening. Tighten “T”
adapter as required to ensure a leak free connection.
7. Run pressure control wiring up through the unit wiring
entrance of the control panel. Secure wires to existing
wire bundle to ensure no interference with condenser
fan blade(s).
These instructions are primarily intended to assist qualified
individuals experienced in the proper installation of this
appliance. Some local codes require licensed installation/
service personnel for this type of equipment.
NOTE: Application of this kit is designed for ambient
conditions no lower than 35°F.
Kit includes:
1 Pressure control with mounting box, cover, and wiring
1 36" length of copper tubing with flare nuts
4 Mounting screws- #10 x 1/2" SHWH self drilling
2 Cover screws - #8 x 3/8" SHWH
1 Service Valve “T” assembly
6 6" wire ties
3 Closed end connectors
1 Mounting Bracket (Used on 150/180 Series only)
WARNING:
All electrical wiring must comply with the
latest edition of the National Electrical Code
ANSI/NFPA 70.
WARNING:
This kit is to be installed by a qualified
service technician in accordance with these
instructions and all codes having jurisdiction.
Failure to follow these instructions could result
in serious injury, property damage, or death.
Figure 1.
Cover Plate
Low Pressure
Control
Copper
Connecting
Tube
Service
"T" Adapter
Compressor/
Blower Divider
Panel
Stage 1
Compressor
2
STAGE 1 EVAP
FREEZESTAT
BLUE YELLOW
SWITCH
TO "ECONOMIZER PLUG-PIN2"
SWITCH
HIGH PRESSURE
FAN
RELAY
T2 T1
24V (COM)
OUTDOOR
L2
L1
LOW PRESSURE
24V (COM)
L1L2L3
T3 T2 T1
THERMOSTAT
OUTDOOR
RED
BLACK
1ST STAGE
COMPRESSOR RELAY
TERMINALS
INSULATED
NOT USED
WHEN KIT IS
INSTALLED
LOW AMBIENT
PRESSURE CONTROL
RED
Electrical Wiring – R4GM-090* Series
Note: Outdoor thermostat (located on right inside wall of
control panel) must be disconnected when installing this kit.
1. Remove “Blue” low voltage wire from outdoor fan 24V
contactor coil. Cut off wire termination and strip wire
approximately 3/8". Remove “Yellow” low voltage
wire from outdoor fan 24V contactor coil, strip and
terminate with closed end connector (provided) to
eliminate the possibility of touching other electrical
components (See Figure 2a).
2. Locate closed end wire connection with two “Yellow”
wires, one marked “Low Ambient Kit Connection” and
remove closed end connector. Strip “Yellow” wire
marked for kit approximately 3/8" and twist together
with “Blue” wire from Step 1. Secure using closed
end connector provided (See Figure 2b).
3. Terminate end of remaining “Yellow “ wire with closed
end connector to eliminate the possibility of touching
other electrical components.
4. Attach one Pressure Control switch Red wire to the
24V hot terminal (Single Black lead) of the Stage 1
compressor contactor coil.
5. Attach the remaining Pressure Control Red wire to
the Outdoor Fan 24V contactor coil terminal where
the two wires were removed in Step 1.
6. Check all connections and tighten as required.
7. Replace all panels
8. Reconnect power to unit and thermostat.
Figure 2b. R4GM-090* Low Ambient Wiring
Figure 2a. R4GM-090* Factory Wiring
SWITCH
HIGH PRESSURE
L1
T1
L2
T2
OUTDOOR
SWITCH
LOW PRESSURE
FREEZESTAT
STAGE 1 EVAP
FAN
RELAY
L3
T3 T2
L2 L1
T1
BLUE
YELLOW
YELLOW
24V (COM) 24V (COM)
YELLOW
TO "ECONOMIZER PLUG-PIN2"
OUTDOOR
THERMOSTAT
1ST STAGE
COMPRESSOR RELAY
Electrical Wiring - R4GM-120* Series
1. Remove the two “Red” outdoor fan low voltage control
circuit wires (one insulated) from the top terminal of
the side auxiliary switch on the STAGE 1 compressor
contactor (See Figure 3a).
2. Remove “Red” wire with piggy-back terminal from
Outdoor Fan 24V contactor coil terminal and replace
using Red wire with insulated spade terminal. Discard
wire with piggy-back terminal.
3. Attach one Pressure Control switch Red wire to either
of the two condenser fan contactor 24V coil terminals
with Red wires already attached.
4. Take remaining "Red" pressure control switch wire
and attach to the top (N.O.) terminal of the STAGE 1
compressor contactor auxiliary switch.
5. Check all connections and tighten as required.
6. Replace all panels
7. Reconnect power to unit and thermostat.
PRESSURE SWITCH
LOW AMBIENT
RED W/INSULATED SPADE TERMINAL
TO "R" ON L.V.T. BOARD
AUX.
SWITCH
T1
T2T3
TO "TRANSFORMER"
COMPRESSOR RELAY
L3 L1L2
1ST STAGE
OUTDOOROUTDOOR
FAN
RELAY
T2 T1
T1T2
RELAY
FAN
L2 L1
24V (COM)
L2 L1
RED RED
N.O.
N.O.
Figure 3b. R4GM-120* Low Ambient Wiring
Figure 3a. R4GM-120* Factory Wiring
L1
T1
L2
T2
1ST STAGE
OUTDOOR
FAN
RELAY
COMPRESSOR RELAY
L1
T1T2
L2
FAN
OUTDOOR
RELAY
L3
T3 T2
L2 L1
T1
24V (COM)
AUX.
SWITCH
RED W/INSULATED SPADE TERMINAL
RED W/PIGGYBACK TERMINAL
TO "TRANSFORMER"
TO "R" ON L.V.T. BOARD
N.O.
N.O.
DISCARD THIS WIRE
3
1. Set indoor thermostat to “OFF” position.
2. Disconnect all electrical power to appliance.
3. Remove both compressor access covers and the
condenser section wiring junction box cover. Open
the motor access and electrical control access doors.
4. Assemble the copper connecting tube, one end to the
head pressure control assembly and the other end to
the open service port of the “T” adapter provided with
this kit. Remaining port with schrader valve will be
used for service. Tighten as required to ensure leak
free connections.
5. Attach the pressure control mounting bracket to the
compressor mounting panel using self-drilling screws
provided. (See Figure 4) Next, mount the pressure
control to mounting bracket using remaining screws
provided.
Figure 4.
Installation (See Figure 4)
R4GM-150/180 Series
6. Attach the “T” adapter to Stage 1 compressor discharge
service port. Care should be taken not to kink the
copper tube while extending. Position tube away from
other components in the unit and leave a minimum of
one loop in coil for vibration dampening. Tighten “T”
adapter as required to ensure a leak free connection.
7. Route pressure control wiring through grommet on
mounting plate and back to the junction box. Secure
to existing unit wire bundle using wire ties provided.
Pass wires up through knockout in the bottom of the
junction box and then through the knockout of the
divider panel following the unit wiring back into the
control panel. Ensure wiring has no interference with
moving parts or sharp edges.
Cover Plate
Pressure Control
Mounting Bracket
Copper
Connecting
Tube
Service "T"
Adapter
Stage 1
Compressor
Low Pressure
Control
STAGE 1 EVAP
FREEZESTAT
BLUE YELLOW
SWITCH
TO "ECONOMIZER PLUG-PIN2"
SWITCH
HIGH PRESSURE
FAN
RELAY
T2 T1
24V (COM)
OUTDOOR
L2
L1
LOW PRESSURE
24V (COM)
L1L2L3
T3 T2 T1
RED
1ST STAGE
COMPRESSOR RELAY
LOW AMBIENT
PRESSURE CONTROL
RED
COMPRESSOR
LOCKOUT
RELAY
RED
Figure 5b. R4GM-150/180* Low Ambient Wiring
Figure 5a. R4GM-150/180* Factory Wiring
SWITCH
HIGH PRESSURE
L1
T1
L2
T2
OUTDOOR
SWITCH
LOW PRESSURE
FREEZESTAT
STAGE 1 EVAP
FAN
RELAY
L3
T3 T2
L2 L1
T1
BLUE
YELLOW
24V (COM) 24V (COM)
TO "ECONOMIZER PLUG-PIN2"
1ST STAGE
COMPRESSOR RELAY
COMPRESSOR
LOCKOUT
RELAY
RED
Electrical Wiring-R4G*-150/180* Series
1. Remove both the Blue and Yellow wire from the Outdoor
Fan 24V contactor coil. Cut off wire terminations and
strip both wires approximately ½”. Connect together
and terminate using closed end wire connector pro-
vided.
2. Attach one Pressure Control Red wire to Outdoor
Fan 24V contactor coil terminal where wires were
removed in Step 1.
3. Attach remaining Pressure Control Red wire to Stage 1
Compressor 24V contactor coil with Red wire already
attached.
4. Check all connections and tighten as required.
5. Replace and close all panels.
6. Reconnect Power to Unit and Thermostat.
Control Adjustment (See Figure 6)
The low pressure control switch comes factory set to
Cut-In at approximately 280 PSIG and to Cut-Out at ap-
proximately 140 PSIG. (140 Lb. differential) If required,
the pressure control switch may be adjusted as follows:
1. Rotate the round adjustment screw on top of the
control to the new Cut-In (High Event) pressure. The
Cut-In pressure is indicated by the set of numbers on
the right of the control front cover.
2. Rotate the square differential adjustment screw on
top the control to correspond to the new Cut-Out
pressure. Differential pressure is indicated by the
set of numbers on the left of the control front cover
NOTE: New Cut-Out pressure is switch Cut-In (High
Event) pressure minus Differential pressure.
DIFF.
HIGH EVENT
150
250
350
450
150
100
40
Figure 6. Control
7083920 (Replaces 707804A)
Specifications & illustrations subject to change without notice or incurring obligations (06/15).
O’Fallon, MO, © Nortek Global HVAC LLC 2015. All Rights Reserved.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Unbranded Low Ambient Kit, R-22 Only, 918797 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI