Westinghouse FG6T(A,K) Installation guide

Category
Stoves
Type
Installation guide

This manual is also suitable for

!
WARNING:
Improper installation, adjustment, al-
teration, service, or maintenance can
cause injury or property damage. Refer
to this manual. For assistance or
additional information consult a quali-
fied installer, service agency, or the
gas supplier.
!
FOR YOUR SAFETY:
Do not store or use gasoline or other
flammable vapors and liquids in the vi-
cinity of this or any other appliance.
Residential Gas Furnaces
Installation Instructions
*TA 80+ Upflow/Horizontal
*TA Series 80+ High Efficiency Upflow/Horizontal Two-Stage Furnace
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of
this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Read
all instructions carefully before starting the installation.
WHAT TO DO IF YOU
SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call
the fire department.
Extinguish any open flame.
2
Table of Contents
Furnace Specifications ................................................................................................................. 3-4
Upflow/Horizontal Models ....................................................................................................... 3
Capacities-Furnace Airflow Data ........................................................................................... 4
Safety Information ............................................................................................................................. 6
Installation Requirements ............................................................................................................... 7
Requirements and Codes ...................................................................................................... 7
Clearances to Combustibles .................................................................................................. 8
Venting and Combustion Air Requirements ............................................................................. 8-11
General ................................................................................................................................... 8
Combustion Air Quality ........................................................................................................... 8
Installation In An Unconfined Space .................................................................................... 9
Installation in a Confined Space ........................................................................................... 9
Horizontal Furnace Installation ................................................................................... 10
Air From Inside ............................................................................................................. 10
Outdoor Air Using Vertical Ducts ................................................................................ 11
Air Directly Through an Exterior Wall .......................................................................... 11
Outdoor Air Using A Crawl Space and Ventilated Attic ............................................ 11
Outdoor Air Through Horizontal Ducts ....................................................................... 11
Venting Requirements ............................................................................................................... 13-17
General ................................................................................................................................. 13
Category I - Common Venting ............................................................................................. 13
Category III - Horizontal Venting ......................................................................................... 13
Horizontal Power Venting .................................................................................................... 15
Location of Outdoor Terminations ....................................................................................... 17
Horizontal Installation ........................................................................................................... 17
Flexible Vent Systems .......................................................................................................... 17
Circulating Air Supply ............................................................................................................... 18-19
General ................................................................................................................................. 18
Return Air .............................................................................................................................. 18
Gas Supply and Piping .............................................................................................................19-22
General ................................................................................................................................. 19
Leak Check ........................................................................................................................... 19
Conversion ............................................................................................................................ 20
High-Altitude Application ...................................................................................................... 21
Natural Gas High Altitude Conversion ................................................................................ 21
LP/Propane Gas Sea Level and High Altitude Conversion .............................................. 22
Electrical Wiring ........................................................................................................................ 23-26
General ................................................................................................................................. 23
Line Voltage Wiring .............................................................................................................. 23
Low Voltage Wiring .......................................................................................................... 23-26
Start-up & Adjustments ............................................................................................................. 27-29
General ................................................................................................................................. 27
Start-Up Procedures .............................................................................................................27
Verifying and Adjusting Firing Rate .................................................................................... 28
Verifying and Adjusting Temperature Rise ......................................................................... 28
Selecting the Delay Profile .................................................................................................. 29
Optional Humidistat .............................................................................................................. 30
Verifying Burner Operation .................................................................................................. 30
Verifying Operation of Supply Air Limit Switch ................................................................... 30
Description of Components ........................................................................................................... 30
Maintenance................................................................................................................................31-33
Wiring Diagram ...................................................................................................................... 31
Combustion Air and Vent System ....................................................................................... 32
Air Filter(s) .............................................................................................................................. 32
Lubrication ............................................................................................................................ 33
Blower Compartment ............................................................................................................ 33
Heat Exchanger and Burner Maintenance ......................................................................... 33
System Operation Information ...................................................................................................... 33
Sequence of Operation ....................................................................................................... 33
Heating Mode ............................................................................................................... 34
Cooling Mode ............................................................................................................... 35
Fan Mode ..................................................................................................................... 35
Furnace Fails to Operate ..................................................................................................... 35
Installation/Performance Checklist ............................................................................................. 36
4
FURNACE SPECIFICATIONS - Upflow/Horizontal Models
Figure 1. Upflow/Horizontal Unit Dimensions
Table 1. Upflow/Horizontal Furnace Model Numbers, Dimensions,
and Shipping Weights
Unit Shown in Upflow
Position Rotate 90˚
Clockwise or Counter
Clockwise for Horizontal
Application
23
3/
4
19
3/
4
3/4
43
25
1/
8
25
1
/4
25
5/
8
23
27
5
/8
15
20
1/
2
25
1/
4
33
30
1/
4
A
B
C
FLUE
OUTLET
1
1/
2
X 3
1/
2
Cut-out for
Gas Connection
3/4 3/4
1
1/
4
3/4
7/8 Cut-out for Electric
Connection
1
1/
2
X 3
1/
2
Cut-out for
Gas Connection
7/
8
Cut-out for
Electric Connection
Return
Air Opening
(Side)
1 1/4
1 1/4D
23
Return Air Opening
(Bottom)
7/8
UPFLOW/HORIZONTAL FURNACE MODELS
FURNACE DIMENSIONS AND
SHIPPING WEIGHTS
Dimensions
Model No
High
Fire
Input
Low Fire
Input
AB C D
Flue
Outlet
Shipping
Weight
Btuh Btuh In. In. In. In. In. Lbs
*TA 072C-VB 72,000 50,000 19 3/4 18 1/4 3 3/4 17 1/4 4 152
*TA 100C-VB 96,000 67,000 19 3/4 18 1/4 3 3/4 17 1/4 4 174
*TA 120C-VC 120,000 84,000 22 1/2 21 3 3/4 20 4 182
5
Table 2b. Heating Airflow Settings
CAPACITIES —Furnace Airflow Data
Notes:
1. Recommended temperature rises are highlighted in bold.
2. Airflow rates of 1800 CFM or more require two return air connections. Data is for
operation with filter(s).
3. Temperature rises in the table are approximate. Actual temperature rises may vary.
4. Temperature rises that are shaded grey are for reference only. These conditions are
not recommended.
5. For single stage cooling, reference the CFM listed in the high column.
Table 2a. All Cooling/Heat Pump Airflow Settings
# Switch not used - Can be 0 or 1.
Nominal Airflow Rates (CFM) and Temperature Rises (Degree F)
*TA 072-VB Models *TA 100-VB Models *TA 120-VC Models
Switches Low Fire Input High Fire Input Low Fire Input High Fire Input Low Fire Input High Fire Input
567
00
#660
54
1090
50
660 73 1090 63 660 92 1090 84
10
# 750 48 1240 44 750
64
1240
58
750 80 1240 74
01
# 1220 30 1680 33 1220 40 1680 41 1220
50
1680
55
11
# 1300 28 1880 29 1300 37 1880 36 1300 47 1880 49
84,000 120,00050,000 72,000 67,000 96,000
Note: O = Off 1 = On
Switch Number Nominal A/C and H/P
LOW HIGH 1 2 3 4
56789
Capacity
500 720
0001
550 800
0000
610 880
0010
650 990
1001
720 1100
1000
800 1210
1010
900 1305
0101
1000 1450
0100
1060 1530
1101
1100 1595
0110
1170 1700
1100
1290 1870
1110
CFM
5 TON
4 TON
3.5 TON
3 TON
2.5 TON
2 TON
6
SAFETY INFORMATION
1. Use only with type of gas approved for this
furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position
as specified on Table 3 of these instructions.
3. Provide adequate combustion and ventilation
air to the furnace space as specified on Pages
8 through 11.
4. Combustion products must be discharged
outdoors. Connect this furnace to an approved
vent system only, as specified on Pages 13
through 17.
5. Never test for gas leaks with an open flame. Use
a commercially available soap solution made
specifically for the detection of leaks to check
all connections, as specified on Page 19 of
these instructions.
6. Always install furnace to operate within the
furnace’s intended temperature-rise range with
a duct system which has an external static
pressure within the allowable range, as speci-
fied on Table 2b of these instructions. See
furnace rating plate.
7. When a furnace is installed so that supply ducts
carry air circulated by the furnace to areas
outside the space containing the furnace, the
return air shall also be handled by duct(s)
sealed to the furnace casing and terminating
outside the space containing the furnace.
8. A gas-fired furnace for installation in a
residential garage must be installed as
specified on Page 8 of these instructions.
9. The furnace is not to be used for temporary
heating of buildings or structures under con-
struction.
Table 3. Minimum Clearances to Combustible Material
Allow 24" minimum clearance for servicing.
The recommended clearance is 36".
LEFT
SIDE
RIGHT
SIDE
Upflow/Horizontal Furnace Models
BOTTOM
UPFLOW APPLICATION
TOP
SIDE
BOTTOM
HORIZONTAL APPLICATION
SIDE
TOP
Vent Connector
Type
Standard Single
Wall Metal Vent
Type B-1 Double
Wall Metal Vent
LEFT SIDE
0" 0"
RIGHT SIDE
0" 0"
VENT
6" 1"
BACK
0" 0"
BOTTOM
0" 0"
TOP
1" 1"
FRONT
4"
4"
INSTALLATION CLEARANCES
7
INSTALLATION REQUIREMENTS
Requirements and Codes
This furnace must be installed in accordance
with these instructions, all applicable local build-
ing codes, current revision of the National Fuel
Gas Code (ANSI-Z223.1), and in Canada with
the CAN/CGA - B149 installation code. The
current revision of the National Fuel Gas Code
is available from:
American National Standards Institute, Inc.
1430 Broadway
New York, New York 10018
Additional helpful publications are:
NFPA-90A - Installation of
Air Conditioning and Ventilating Systems
NFPA-90B - Warm Air Heating
and Air Conditioning Systems
These publications are available from:
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, Massachusetts 02269
IMPORTANT NOTE
The Commonwealth of Massachusetts re-
quires compliance with regulation 248 CMR
4.00 and 5.00 for installation of through – the
– wall vented gas appliances as follows:
(a) For direct-vent appliances, mechanical-
vent heating appliances or domestic hot
water equipment, where the bottom of the
vent terminal and the air intake is installed
below four feet above grade the following
requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are
bedroom(s), a carbon monoxide de-
tector and alarm shall be placed in the
living area outside the bedroom(s).
The carbon monoxide detector shall
comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall be
located in the room that houses the
appliance or equipment and shall:
a. Be powered by the same electrical
circuit as the appliance or equip-
ment such that only one service
switch services both the appliance
and the carbon monoxide detector;
b. Have battery back-up power;
c. Meet ANSI/UL 2034 Standards and
comply with NFPA 720 (2005 Edi-
tion); and
d. Have been approved and listed by a
Nationally Recognized Testing Labo-
ratory as recognized under 527
CMR.
3. A Product-approved vent terminal must
be used, and if applicable, a Product-
approved air intake must be used.
Installation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions shall
remain with the appliance or equipment
at the completion of the installation.
4. A metal or plastic identification plate
shall be mounted at the exterior of the
building, four feet directly above the
location of vent terminal. The plate shall
be of sufficient size to be easily read
from a distance of eight feet away, and
read “Gas Vent Directly Below”.
(b) For direct-vent appliances, mechanical-
vent heating appliances or domestic hot
water equipment where the bottom of the
vent terminal and the air intake is installed
above four feet above grade the following
requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are
bedroom(s), a carbon monoxide de-
tector and alarm shall be placed in the
living area outside the bedroom(s).
The carbon monoxide detector shall
comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall:
a. Be located in the room that houses
the appliance or equipment;
b. Be either hard-wired or battery pow-
ered or both; and
c. Shall comply with NFPA 720 (2005
Edition).
3. A Product-approved vent terminal must
be used, and if applicable, a Product-
approved air intake must be used.
Installation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions shall
remain with the appliance or equipment
at the completion of the installation.
8
mm) above the floor, and the furnace must be
located or protected to avoid physical damage
by vehicles.
!
WARNING:
Do not place combustible material on or
against the furnace cabinet or within 6
inches of the vent pipe. Do not place
combustible materials, including gaso-
line and any other flammable vapors and
liquids, in the vicinity of the furnace.
VENTING AND COMBUSTION
AIR REQUIREMENTS
General
Provisions must be made in the installation of
this furnace to provide an adequate supply of air
for combustion. Detailed instructions for deter-
mining the adequacy of an installation can be
found in the current revision of the National Fuel
Gas Code (ANSI Z223.1 / NFPA54) or in appli-
cable local building codes. Consult local
codes for special requirements. For Cana-
dian installations consult Canadian Installations
Codes and (CAN/CGA B149.1 or .2).
If the furnace is operated with inadequate air for
combustion one of the flame roll-out switches
located in the burner compartment or the vent
switch will open, turning off the gas supply to the
burners. These safety devices are manually
reset switches. DO NOT install jumper wires
across these switches to defeat their function.
DO NOT reset a switch without identifying and
correcting the fault condition. If a switch must be
replaced, use only the correct part specified in
the Replacement Parts List.
Air openings in the furnace door, warm air
registers, and return air grilles must not be
restricted.
Combustion Air Quality
To maximize heat exchanger life, the combus-
tion air must be free of chemicals which form
corrosive acidic compounds in the combustion
gases. The recommended source of combus-
tion air is to use the outdoor air supply. How-
ever, the use of indoor air in most applications
is acceptable except as follows:
1. If the furnace is installed in a confined space it
is recommended that the necessary combus-
WARNING:
This furnace is not approved for installa-
tion in mobile homes. Installation in a
mobile home could cause fire, property
damage, and/or personal injury.
Location
Upflow gas furnaces are shipped ready for
installation in the upflow or horizontal right or left
positions. The furnace must be installed on a
level surface, located as close to the vent (or
chimney) and as close to the center of the air
distribution system as possible. See Figure 1
and Table 1 for overall dimensions to determine
the required clearances in hallways, doorways,
stairs, etc. to allow the furnace to be moved to
the installation point. The furnace must be
installed so that all electrical components are
protected from water. The furnace must be
installed upstream from a refrigeration system.
This furnace is not to be used for temporary
heating of buildings or structures under con-
struction.
Clearances to Combustibles
This furnace is Design Certified by CSA Inter-
national for the minimum clearances to com-
bustible material listed in Table 3. Refer to the
furnace rating plate, located inside of the fur-
nace cabinet, for the specific model number and
clearance information.
Access for positioning and servicing the unit
must be considered when locating unit. Twenty
four inches is the minimum required clearance
from the front of the unit for servicing it. Thirty
inches is the minimum required clearance from
the front of the unit for positioning it. Thirty six
inches is the recommended clearance from
the front of the unit. Please note that a panel
or door can be located such that the minimum
clearance on the rating plate is satisfied, but that
panel or door must be removable and allow the
appropriate clearance for your installation.
This furnace is certified for use on wood floor-
ing. This furnace must not be installed directly
on carpeting, tile, or any combustible material
other than wood flooring.
A gas-fired furnace installed in a residential
garage must be installed so the burners and the
igniter are located not less than 18 inches (457
!
9
tion air come from the outdoors by way of attic,
crawl space, air duct, or direct opening.
2. If outdoor combustion air is used, there must be
no exposure to the installations or substances
listed in Item 3 below.
3. The following types of installation may require
Outdoor Air for combustion, due to chemical
exposures:
Commercial buildings
Buildings with indoor pools
Furnaces installed in laundry rooms
Furnaces installed in hobby or craft rooms
Furnaces installed near chemical storage
areas
Exposure to the following substances in the
combustion air supply may also require Out-
door Air for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethyl-
ene)
Printing inks, paint removers, varnishes,
etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
!
CAUTION:
Combustion air must not be drawn from
a corrosive atmosphere.
!
WARNING:
Furnace installation using methods other
than those described in the following
sections must comply with the National
Fuel Gas Code and all applicable local
codes to provide sufficient combustion
air for the furnace.
Installation In An Unconfined Space
An unconfined space is an area including all
rooms not separated by doors with a volume
greater than 50 cubic feet per 1,000 Btuh of the
combined input rates of all appliances which
draw combustion air from that space. For
example, a space including a water heater rated
at 45,000 Btuh input and a furnace rated at
100,000 Btuh requires a volume of 7,250 cubic
feet [50 x (45 + 100) = 7,250] to be considered
unconfined. If the space has an 8 foot ceiling,
the floor area of the space must be 906 square
feet (7,250 / 8 = 906). In general, a furnace
installed in an unconfined space will not require
outside air for combustion. However, in “tight”
buildings (with weather stripping and caulk to
reduce infiltration), it may be necessary to
provide outside air to ensure adequate com-
bustion and venting, even though the furnace is
located in an unconfined space.
Installation In A Confined Space
A confined space is an area with volume less
than 50 cubic feet per 1,000 Btuh of the com-
Figure 2. *TA Horizontal Installation
Suspended in Attic or Crawl Space
Figure 3. *TA Horizontal installation on a
Platform
Gas Inlet
Electrical
Supply
Connection
Coil Plenum
Type “B” Vent
Combustible
Platform
Louver Door
Note: Line
Contact is Permissible
10
bined input rates of all appliances drawing com-
bustion air from that space. Furnace closets,
small equipment rooms and garages are con-
fined spaces. Furnaces installed in a confined
space which supply heated air to areas outside
the space must draw return air from outside the
space and must have the return air ducts tightly
sealed to the furnace. A confined space must
have two openings into the space for com-
bustion air. One opening must be within 12
inches of the ceiling, and the other must be
within 12 inches of the floor. The required
sizing of these openings is determined by
whether inside or outside air is used to support
combustion, the method by which the air is
brought to the space, and by the total input rate
of all appliances in the space.
Horizontal Furnace Installation
The *TA series furnaces can be installed hori-
zontally in an attic, basement, crawl space or
alcove. It can be suspended from a ceiling in a
basement or utility room in either a right to left
airflow or left to right airflow. (See Figures 2
and 3.)
If the furnace is to be suspended from the ceiling,
it will be necessary to use steel straps around
each end of the furnace. These straps should
be attached to the furnace with sheet metal
screws and to the rafters with bolts. The furnace
could also be suspended by an angle iron frame
bolted to the rafters. (See Figure 2.)
Access for positioning and servicing must be
considered when locating the unit. Refer to
Table 3, Minimum Clearances to Combustible
Material, for clearance specifications.
Keep all insulating materials away from the
louvered door. Insulating materials may be
combustible.
The *TA series furnace may be installed directly
on combustible wood flooring or supports, if
type "B-1" vent pipe is used (See Figure 8). It
is recommended for further reduction of fire
hazard that cement board or sheet metal be
placed between the furnace and the combus-
tible floor and extend 12 inches beyond the front
of the louvered door.
!
WARNING:
Furnaces installed with combustion air
drawn from a heated space which in-
cludes exhaust fans, fireplaces, or other
devices that may produce a negative
pressure should be considered con-
fined space installations.
See the venting section for venting guidelines
and specifications.
Air From Inside (See Figure 4)
If combustion air is taken from the heated
space, the two openings must
each
have a free
area of at least one square inch per 1,000 Btuh
of total input of all appliances in the confined
space, but not less than 100 square inches
of free area. For example, if the combined input
rate of all appliances is less than or equal to
100,000 Btuh, each opening must have a free
area of at least 100 square inches. If the
combined input rate of all appliances is 120,000
Btuh, each opening must have a free area of at
least 120 square inches.
Outdoor Air Using Vertical Ducts
(See Figure 5)
If combustion air is taken from outdoors through
vertical ducts, the openings and ducts must
have a minimum free area of one square inch
per 4,000 Btuh of total appliance input. In instal-
lations drawing combustion air from a ventilated
attic, both air ducts must extend above the attic
insulation.
If the unit is installed in an area with an exhaust
fan, provide sufficient ventilation to prevent
negative pressures from occurring in the room.
The combustion air openings must not be re-
stricted in any manner.
Total Input
Rating (Btu/hr)
40,000
60,000
80,000
100,000
120,000
140,000
160,000
Round Duct
Diameter
12"
12"
12"
12"
13"
14"
15"
Minimum
Free Area
(Each Opening)
100 sq. in.
100 sq. in.
100 sq. in.
100 sq. in.
120 sq. in.
140 sq. in.
160 sq. in.
Furnace
Openings to
adjacent space.
Each opening must
be at least 100 sq. in.
or 1 sq. in. per 1000
Btuh of total input
rating, whichever is
greater. See minimum
area per table.
12" Max.
12" Max.
Water Heater
Vent or
Chimney
Figure 4. Equipment in a Confined Space
with all Combustion Air
Drawn from the Inside
11
!
CAUTION:
Do not supply combustion air from an
attic space that is equipped with power
ventilation or any other device that may
produce a negative pressure.
Air Directly Through An Exterior Wall
(See Figure 6)
If combustion air is provided directly through an
exterior wall, the two openings must each have
Figure 7. Equipment in a Confined
Space with All Combustion Air Drawn
from a Crawl Space and Ventilated Attic
Outlet Air Duct
must be at least
1 sq. in. per 4000
Btuh of total input
rating. Must extend
above attic insulation.
Ventilation Louvers at
each end of attic
Attic Insulation
Ventilation Louvers for
unheated crawl space
Crawl Space
Inlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Furnace
Water Heater
Vent or
Chimney
free area of at least one square inch per 4000
Btuh of total appliance input.
Outdoor Air Using a Crawl Space and Ventilated
Attic (See Figure 7)
When directly communicating with the out-
doors, each opening shall have a minimum free
area of 1 square inch per 4,000 Btuh of total
appliance input. The openings shall communi-
cate directly, or by ducts, with the outdoor
spaces (crawl or attic) that freely communicate
with the outdoors.
Outdoor Air Using Horizontal Ducts (See Fig-
ure 8)
If combustion air is taken from outdoors through
horizontal ducts, the openings and ducts must
Figure 6. Equipment in a Confined
Space with all Combustion Air Drawn
from the Outside through Exterior Wall
Each openin
g
to out
side
mu
st be at lea
st
1 sq. in. per 4000
Btuh of total input
ratin
g.
12" Max
12" Max
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Furnace
Water Heater
Vent or
Chimney
Total Input
Rating (Btu/hr)
40,000
60,000
80,000
100,000
120,000
140,000
160,000
Minimum
Free Area
(Each Opening)
10 sq. in.
15 sq. in.
20 sq. in.
25 sq. in.
30 sq. in.
35 sq. in.
40 sq. in.
Round Duct
Diameter
4"
5"
5"
6"
6"
7"
8"
Inlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Inlet and Outlet
Ducts must
extend above
attic insulation.
Outlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Ventilation Louvers at
each end of attic
Attic
Insulation
12" Max
a. All Combustion Air from Ventilated Attic.
Furnace
Water Heater
Vent or
Chimney
Figure 5. Equipment in a Confined
Space with all Combustion Air Drawn
from the Outside through Vertical Ducts
Figure 8. Equipment in a Confined Space
with all Combustion Air Drawn from the
Outside through Horizontal Ducts
Each openin
g
to out
side
mu
st be at lea
st
1 sq. in. per 2000
Btuh of total input
ratin
g.
12" Max
12" Max
Total Input
Rating (Btu/hr)
40,000
60,000
80,000
100,000
120,000
140,000
160,000
Minimum
Free Area
(Each Opening)
20 sq. in.
30 sq. in.
40 sq. in.
50 sq. in.
60 sq. in.
70 sq. in.
80 sq. in.
Round Duct
Diameter
5"
6"
7"
8"
9"
10"
10"
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Furnace
Air Duct
Air Duct
Water Heater
Vent or
Chimney
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Total Input
Rating (Btuh)
40,000
60,000
80,000
100,000
120,000
140,000
160,000
Minimum
Free Area
(Each Opening)
10 sq. in.
15 sq. in.
20 sq. in.
25 sq. in.
30 sq. in.
35 sq. in.
40 sq. in.
Round Duct
Diameter
4"
5"
5"
6"
6"
7"
8"
12
have a minimum free area of one square inch
per 2,000 Btuh of total appliance input.
If the unit is installed in an area with an exhaust
fan, provide sufficient ventilation to prevent
negative pressures from occurring in the room.
The combustion air openings must not be
restricted in any manner.
!
WARNING:
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance con-
nected to the venting system being placed into operation could result
in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected
to the venting system being placed into operation, while all other
appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch,
as required in the
National Fuel Gas Code, ANSI Z223. 1/NFPA 54
or the CSA B149.1, Natural Gas and Propane Installation Codes
and these instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all
doors between the space in which the appliance(s) connected
to the venting system are located and other spaces of the
building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the
venting system. Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they are operating at maximum
speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being
inspected into operation. Adjust the thermostat so appliance is
operating continuously.
7. Test for spillage from draft hood equipped appliances at the
draft hood relief opening after 5 minutes of main burner opera-
tion. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the
venting system must be corrected in accordance with the
Na-
tional Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1,
Natural Gas and Propane Installation Codes
.
9. After it has been determined that each appliance connected to
the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, fireplace dampers
and any other gas-fired burning appliance to their previous
conditions of use.
13
VENTING REQUIREMENTS
General
This furnace must be vented in compliance
with, the current revision of the National Fuel
Gas Code (ANSI-Z223.1/NFPA54), with the
instructions provided below.
In Canada, venting shall conform to the require-
ments of the current (CAN/CGA B149.1 or .2)
installation codes. Consult local codes for
special requirements.
For Category I furnace installations, the fur-
nace shall be connected to a factory built
chimney or vent complying with a recognized
standard, or a masonry or concrete chimney
lined with a lining material acceptance to the
authority having jurisdiction. Venting into an
unlined masonry chimney or concrete chim-
ney is prohibited.
This furnace must never be vented to a chim-
ney flue servicing a fireplace or other appliance
designed to burn solid fuel. If the furnace vent
is to be connected to a chimney serving a
fireplace, the fireplace must be sealed off from
the chimney. Single wall metal vents shall not be
used for Category I venting, Category I fur-
naces must be vented vertically or near verti-
cally.
The furnace vent, if metal, may be insulated if
local codes allow. Any part of the vent system,
metal vent only, not exposed to weather, but
which are exposed to ambient temperatures
below 35° F must be insulated to prevent
condensation. All vent insulation shall be foil
backed fiberglass of one inch minimum thick-
ness.
Three sheet metal fasteners (field supplied)
should be used to secure the vent pipe to the
furnace flue. These fasteners should be evenly
spaced around the flue diameter, if possible.
Category I - Common Venting
When an existing furnace is removed from a
venting system serving other appliances, the
venting system is likely to be too large to
properly vent the remaining appliances. An
improperly sized venting system can result in
the formation of condensate, leakage, spillage,
etc.
The steps outlined in the warning below shall be
followed with each individual appliance con-
nected to the vent system placed in operation,
while all other appliances connected to the vent
system are not in operation:
The venting system should be designed to have
the minimum number of elbows or turns. All
horizontal runs shall be sloped upwards from
the furnace at 1/4 inch per running foot of vent.
Supports for the vent pipe must be installed a
minimum of every five feet along the vent run to
ensure no displacement after installation.
Under no circumstances shall any portion of the
vent system extend into or pass through any
return air duct, supply air duct, or plenum.
If the furnace is operated with blocked or re-
stricted venting, the blocked vent switch lo-
cated in the vent plate will open, turning off the
gas supply to the burners. The blocked vent
switch is a manually reset device. DO NOT
install a jumper wire across this switch to defeat
its function. DO NOT reset the switch without
identifying and correcting the fault condition
which caused the switch to trip. If this switch
must be replaced, use only the part specified in
the Replacement Parts List.
!
WARNING:
Upon completion of the furnace installa-
tion, carefully inspect the entire flue sys-
tem both inside and outside the furnace
to assure it is properly sealed. Leaks in
the flue system can result in serious
personal injury or death due to exposure
of flue products, including carbon mon-
oxide.
Category III: Horizontal Venting
NOTE: The reduced NOx models (eighth
character N) are not approved as a Category
III (Categorie III) furnace for use with horizontal
venting.
14
The furnaces are approved for use with 3"
single wall AL29-4C stainless steel vent pipe in
horizontal vent applications. This pipe is available
from the following manufacturers:
Z-FLEX Inc. - vent brand name (Z-VENT)
Heat-fab Inc. - vent brand name (Saf-T Vent)
Flex-L International - vent brand name (Star-
34 Vent)
This vent pipe must be used for the entire length
of the vent run. The installation must be in
accordance with all instructions supplied by the
vent manufacturer for use on Category III
appliances. When venting horizontal, this is
defined as a Category III furnace, the vent
pressure is positive, and the venting system
must be sealed in both horizontal and vertical
runs.
For horizontal venting installations in both the
United States and Canada the transition
assembly must be modified by adding a bleed
tube to the pressure switch tube and bypassing
the vent switch. All model furnaces will require
Vent Kit #903196 for horizontal venting.
Figure 10. *TA Vent Collar Detail
Cover
Plate
Nut
Covered Vent
Collar Hole
Figure 9. *TA Bleed Tube
Installation
Collector
Pan
Pressure
Switch
Sensor
Tubes
Bleed Tube
Bleed Tube
Orifice - Pres
s
switch opera
t
at high altitu
d
can be made
responsive b
y
covering ble
e
orifice
Figure 11. Limit Circuit Wiring
Wire Nut
Switch
Limit
Switch
Flame
Roll-Out
Switch
Vent
Limit
Blue
Blue
Horizontal Venting For *TA Models:
1. Remove the rubber tubing from the
pressure switch sensor tube and the
collector pan sensor tube. Cut 1/2 inch
from one end of the rubber sensor tube,
fold in half and cut along the bend line.
Discard the 1/2 inch long piece of tubing.
Select the correct bleed tube using the
table supplied with vent kit #903196 and
place the other two pieces of tubing on
both ends of the bleed tube. Do not
cover the hole in the bleed tube. Place
the assembly back on the pressure
switch sensor tube and the collector
pan sensor tube. (See Figure 9.)
2. Remove the nut and restrictor plate
from the vent collar assembly and
discard the restrictor plate. Select the
appropriate dilution cover plate as noted
with vent kit #903196. Fit the clearance
hole in the cover plate over the weld
stud. The cover plate must cover the
hole(s) on the vent collar assembly.
Tighten the nut securely while holding
the cover plate in position. (See Figure
10.)
3. Bypass the vent switch by removing
both wires from the vent switch and
attaching them to the wire nut. (See
Figure 11.)
!
CAUTION:
Do not drill holes through the vent pipe
or fittings on a horizontal vented fur-
nace. Do not use sheet metal screws, or
rivets. Drilling, screws, or rivets will
cause leaks.
15
Figure 12. Typical Horizontal Vent Installation
90˚ Elbow
3" Dia. Loop
Outside
Wall
Wall Thimble
(For combustible
wall material)
Termination
Tee
Support
Tee
0-6'
Drain
Plug
1
/4" Per
Foot Rise
Locking Band
Locking
Band
The components of the horizontal vent system
must not be penetrated with screws, rivets, or
other devices, either when joining pipes and
fittings or using support straps. All joints must
be sealed with high temperature silicone before
locking bands are installed. If the lengths of pipe
must be cut, the joint must still be sealed with
silicone and the locking band used. When
installing the condensate tube be sure to form
a trap by means of a 3" loop filled with water.
(See Figure 12.)
Keep the number of pipe fittings to a minimum.
Maintain a minimum of 6 inches of air space
between the vent and combustibles at all times,
this includes inside and outside the building.
NOTE: The direction of the male-female joints
from the drain tee to the termination tee is
opposite to standard gas appliance venting.
The male end of the pipes point towards the
furnace.
1. Apply an adhesive bead around the
outside of the pipe approximately 1/4"
from the end of the pipe. This includes
the first fitting or pipe attached to the
furnace.
2. Push the pipe and fitting together while
twisting the pipe or fitting. Twisting the
pipe or fitting spreads the adhesive
completely within the fitting socket.
3. When the pipe is at the socket bottom,
inspect the joint. Look for a complete,
uninterrupted ring of adhesive material
around the pipe at the fitting socket.
Additional adhesive or rotation of the
pipe or fitting may be required for a
complete seal. The complete adhesive
material ring provides the seal required
for the positive pressure vent.
4. All vent systems must include a tee and
drain plug for collection and disposal of
condensate. The drain tee must be
installed within the first 5 feet of vent run
to protect the furnace.
5. All horizontal sections must have a
slope toward the drain tee of not less
than 1/4" per foot to prevent the collection
of condensate at any location other than
at the tee.
6. Horizontal runs must be supported with
3/4" pipe strap at a maximum of 5 foot
intervals and at each point where an
elbow is used.
7. Maintain a 6 inch minimum air space to
combustibles from all sections of the
stainless steel vent system, except
when a wall thimble is used.
Horizontal Power Venting
The Tjerlund GPAK-
1TN horizontal kit is certified for use with this
furnace. The kit includes a power venter, a side-
wall vent hood and a barometric draft control. It
has an electrical interlock to assure that the
furnace will not operate when the power venter
is off.
The kit is for use only when exhaust is through
an exterior wall, normally with horizontal vent
16
piping. The power venter establishes negative
pressure in the vent piping and the furnace
operates as if connected to Category I vertical
venting.
Installation Instructions are provided with the
kit. Installation must conform to those instruc-
tions and applicable requirements of local
codes.
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
1
In accordance with the current CSA B149.1 Natural Gas and Propand Installation Code
2
In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA B149.1, one of the following statement shall be included:
“Clearance in accordance with local installation codes, and the requirements of the gas supplier and the manufacturer’s installation instructions.”
Canadian Installations
1
US Installations
2
A =
Clearance above grade, veranda, porch,
deck, or balcony
12 inches (30 cm) 12 inches (30 cm)
B =
Clearance to window or door that may be
opened
6 inches (15 cm) for appliances £ 10,000
Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (3 kW) and £
100,00 Btuh (30 kW), 36 inches (91 cm) for
appliances >100,00 Btuh (30 kW)
4 feet (1.2 m) below or to side of opening;
1 foot (300 mm) above opening
C =
Clearance to permanently closed window
**
D =
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal
**
E =
Clearance to unventilated soffit
**
F =
Clearance to outside corner
**
G =
Clearance to inside corner
**
H =
Clearance to each side of center line
extended above meter/regulator assembly
3 feet (91 cm) within a height 15 feet
above the meter/regulator assembly
*
I =
Clearance to service regulator vent outlet 3 feet (1.83 m)
*
J =
Clearance to nonmechanical air supply inlet
to building or the combustion air inlet to any
other appliance
6 inches (15 cm) for appliances £ 10,000
Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (3 kW) and £
100,00 Btuh (30 kW), 36 inches (91 cm) for
appliances >100,00 Btuh (30 kW)
4 feet (1.2 m) below or to side of opening;
1 foot (300 mm) above opening
K =
Clearance to a mechanical air supply inlet 6 feet (1.83 m) 3 feet (91 cm) above if within 10 feet (3 m)
horizontally
L =
Clearance above paved sidewalk or paved
driveway located on public property
7 feet (2.13 m) † 7 feet (2.13 m)
M =
Clearance under veranda, porch deck, or
balcony
12 inches (30 cm) ‡
*
Figure 13. Vent Termination Clearances
!
WARNING:
The entire vent system must be sealed
with a high temperature sealant which
will withstand temperatures of 450°F.
Recommended sealants: Dow Corning
Sealant 736 RTV; GE 106 RTV; High
Tech Ind., High TEMP RED.
17
Location of Outdoor Terminations
Horizontal Installation
The vent termination tee must be installed with
the following minimum clearances. (See Figure
13.) Vent termination clearances shall be con-
sistent with the
National Fuel Gas Code, ANSI
2223.1/NFPA 54 and/or the CSA B149.1,
Natural Gas and Propane Installation Code.
All minimum clearances specified must be
maintained to protect building materials from
degradation by flue gases.
1. The termination tee must be 12 inches
above snow level or grade level which
ever is higher. See Figure 14 for alter-
nate method to achieve 12" above snow
level.
2. The minimum distance from any door,
(openable) window, or gravity air inlet is
4 ft. below, 4 ft. horizontally, or 1 ft.
above.
3. The vent termination shall be a minimum
of 3 ft. above any forced air inlet within
10 ft. (See Figure 13.)
4. Recommended minimum distance from
an inside corner formed by two exterior
walls is 6 ft., but is not required.
5. The minimum distance from gas or
electric meter(s) is 4 ft.
6. Avoid areas where condensate drainage
may cause problems such as above
planters, patios, or adjacent to windows
where the steam from the flue gases
may cause fogging. Do not terminate
above any public walkway.
7. Select the point of wall penetration where
the minimum 1/4 inch per foot of upward
slope can be maintained.
8. When penetrating a noncombustible
wall, the hole through the wall must be
large enough to maintain the pitch, pipe
clearance for passage, and provide for
proper sealing. Penetrating a com-
bustible wall requires the use of a wall
thimble. (See Figure 14.) A 6-1/2 inch
square framed opening is required to
insert the thimble halves. The thimble
is adjustable to varying wall thickness
and is held in place by applying sealant
to the male sleeve before assembly.
Also run a bead of sealant around the
outer wall thimble.
9. The vent pipe must extend 1-1/4 inches
through the outer thimble half for a
combustible wall. Be sure to check this
carefully before cutting the vent pipe.
10. Attach a 3 inch coupling to the end of the
pipe that extends through the wall or
thimble. This prevents the vent pipe
from being pushed inward.
11. Cut an 8 inch minimum piece of vent
pipe and connect the coupling to the
termination tee. The inside of the tee
must be a minimum of 12 inches from
the outside of the wall. (See Figure 15.)
Flexible Vent Systems
Flexible gas vent is approved for use in vertical
single vent or common vent installations only.
The minimum distance to combustibles is 1" for
type B insulated and 6" for single wall. The
venting system must be installed in accor-
dance with the local authorities, the vent
manufacturer's instructions and the instruc-
tions listed below.
The flexible vent must be installed in accor-
dance with the venting tables for vertical or
common venting only. The vent system must
be supported in horizontal runs with 3/4" pipe
strap at a maximum of 5 foot intervals. All
horizontal sections must have a slope toward
the furnace of not less than 1/4" per foot. The
vent must not sag, or have any bends greater
than 90 degrees.
Horizontal Venting Requirements
Table 4. Horizontal
Venting Requirements
Furnace
Model Number Pipe Reducer Maximum Max. Feet
*TA Size Needed # Elbows Vent Pipe
072C-VB 3" 4" to 3" 4 35
096-VS 3" 4" to 3" 4 35
120C-VB(C ) 3" 4" to 3" 4 35
Use Wall Thimble at
Vent Points
Support vent pipe
every 5 feet
Ground Level
Termination Tee
Figure 14. Alternate Horizontal Vent
Installation
18
CIRCULATING AIR SUPPLY
General
Plenums and air ducts must be installed in
accordance with the Standard for the Installa-
tion of Air Conditioning and Ventilating Systems
(NFPA No. 90A) or the Standard for the Instal-
lation of Warm Air Heating and Air Conditioning
Systems (NFPA No. 90B).
It is recommended that the outlet duct be pro-
vided with a removable access panel. This
opening should be accessible when the furnace
is installed in service and shall be of a size that
smoke or reflected light may be observed inside
the casing to indicate the presence of leaks in
the heat exchanger. The cover for the opening
shall be attached in such a manner as to prevent
leaks.
If outside air is used as return air to the furnace
for ventilation or to improve indoor air quality, the
system must be designed so that the return air
is not less than 50° F (10° C) during operation.
If a combination of indoor and outdoor air is
used, the ducts and damper system must be
designed so that the return air supply to the
furnace is equal to the return air supply under
normal, indoor return air applications.
When a cooling system is installed which uses
the furnace blower to provide airflow over the
indoor coil, the coil must be installed down-
stream (on the outlet side) of the furnace or in
parallel with the furnace.
If a cooling system is installed in parallel with the
furnace, a damper must be installed to prevent
chilled air from entering the furnace and con-
densing on the heat exchanger. If a manually
operated damper is installed, it must be de-
signed so that operation of the furnace is
prevented when the damper is in the cooling
position and operation of the cooling system is
prevented when the damper is in the heating
position.
Return Air
In applications where the supply ducts carry
heated air to areas outside the space in which
the furnace is installed, the return air must be
delivered to the furnace by duct(s) sealed to the
furnace casing, running full size and without
interruption.
!
WARNING:
The solid base of the furnace must be
in place when the furnace is installed
with side return air ducts. Removal of
all or part of the base could cause
products of combustion to be circu-
lated into the living space and create
potentially hazardous conditions, in-
cluding carbon monoxide poisoning
that could result in personal injury or
death.
For upflow/horizontal installations: The return
air ductwork may be connected to any or all of
the following: left side return, right side return,
or bottom return. NOTE: Do not use the back
of the furnace for return air. Table 2a and 2b, in
the front pages of these instructions, contains
the airflow data for each furnace model. Where
maximum airflow is 1800 CFM or more, two
openings must be used for return air.
Wall Thimble
(Inner Half)
Inner Shield
4
1
/
2
" Dia.
Wall Thimble Outer Half
Outer Overlapping
Shield 6
1
/
2
" Dia.
3" Termination
Te e
Protective
Screen
Inside
Combustible
Wall
Inside
Combustible
Wall
3" Vent
Pipe
Outside
Combustible
Wall
Inner
Overlapping
Shield 6
3
/
8
" Dia.
Locking Band
12" Min
Figure 15. Typical Termination
*TA- Left Side Entry
Figure 16. Typical Gas
Service Connection
Ground Joint
Union
Dripleg
Shut-Off Valve
Manifold
Some utilities
require Shut-Off
Valve to be
4 to 5 feet
above floor
Automatic Gas
Valve (with manual
shut-off)
Burner
Assembly
19
!
WARNING:
Products of combustion must not be
allowed to enter the return air ductwork
or the circulating air supply. Failure to
prevent products of combustion from
being circulated into the living space can
create potentially hazardous conditions
including carbon monoxide poisoning
that could result in personal injury or
death.
All return ductwork must be secured to
the furnace with sheet metal screws. For
installations in confined spaces, all re-
turn ductwork must be adequately sealed
and joints must be taped. When return air
is provided through the bottom of the
furnace, the joint between the furnace
and the return air plenum must be air
tight.
The floor or platform on which the fur-
nace is mounted must provide sound
physical support of the furnace with no
gaps, cracks, or sagging between the
furnace and the floor or platform.
Return air and circulating air ductwork
must not be connected to any other heat
producing device such as a fireplace in-
sert, stove, etc. Doing so may result in fire,
explosion, carbon monoxide poisoning,
personal injury, or property damage.
GAS SUPPLY AND PIPING
General
This furnace may be installed for either left or
right side gas entry. A typical gas service
hookup is shown in Figure 16. When making the
gas connection provide clearance between the
gas supply line and the entry hole in the furnace
casing to avoid unwanted noise and/or damage
to the furnace.
All gas piping must be installed in compliance
with local codes and utility regulations. Some
local regulations require the installation of a
manual main shut-off valve and ground joint
union external to the furnace. The shut-off
valve should be readily accessible for service
and/or emergency use. Consult the local utility
or gas supplier for additional requirements re-
garding placement of the manual main gas shut-
off. In the absence of local codes the gas line
installation must comply with the latest edition of
the National Fuel Gas Code (ANSI Z223.1) or
(CAN/CGA B149.1 or .2) Installation Codes.
An 1/8 inch NPT tap must be installed in the gas
line to the unit for use when measuring the gas
supply pressure. The tap should be readily
accessible for service use. A drip leg should be
installed in the vertical pipe run to the unit. Table
5 lists gas flow capacities for standard pipe
sizes as a function of length in typical applica-
tions based on nominal pressure drop in the line.
IMPORTANT NOTES:
1. Gas piping must not be run in or through air
ducts, chimneys, gas vents, elevator shafts,
etc.
2. Compounds used on threaded joints of gas
piping must be resistant to the actions of lique-
fied petroleum gases.
3. The main manual gas valve and main power
disconnect to the furnace must be properly
labeled by the installer in case emergency
shutdown is required.
Leak Check
After the gas piping to the furnace is complete,
all connections must be tested for gas leaks. To
check for leaks in gas piping systems, use only
a soap and water solution or other approved
method.
!
CAUTION:
Do not use matches, lighters, candles,
or other sources of open flame to check
for gas leaks.
IMPORTANT NOTE:
When pressure testing the gas supply lines
at pressures greater than 1/2 psig (14 inch
W.C.), the furnace must be disconnected
from the gas supply piping system to pre-
vent damage to the gas control valve. If the
test pressure is less than or equal to 1/2 psig
(14 inch W.C.), the furnace must be
isolated from the gas supply line by closing
the manual shut-off valve.
20
!
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings ex-
actly could result in serious injury, death
or property damage.
Never test for gas leaks with an open
flame. Use a commercially available soap
solution made specifically for the detec-
tion of leaks to check all connections. A
fire or explosion may result causing prop-
erty damage, personal injury or loss of
life.
Manifold Pressure Adjustment
Manifold pressures for low and high stages are
independently adjustable. Adjustment tap loca-
tions on the valve are shown in Figure 17 and
18. Manifold pressure would be adjusted below
procedue:
- Turn off gas shut off valve outside
furnace.
- Install manometer on the gas valve at
the outlet pressure tap.
- Turn on the shut off and gas valves and
then adjust manifold pressure.
- Ensure plug is tight after removing
manometer.
Conversion
Conversion of this furnace to use LP/propane
gas must be made by qualified service person-
nel, using only approved parts.
IMPORTANT NOTE: When converting a low
NOx furnace from Natural to LP/Propane
Gas, it is necessary to remove the NOx
baffles from the furnace.
!
WARNING:
This furnace was equipped at the factory
for use with natural gas only. A special
kit, supplied by the manufacturer, is re-
quired to convert the furnace to operate
on LP/propane gas. Failure to use the
proper conversion kit can cause fire, ex-
plosion, property damage, carbon mon-
oxide poisoning, personal injury, or
death.
(4) Quick Disconnect Terminals
Inlet Pressure Post
Set Screw: 3.32” Hex Head
(.339 Dia. + DFT.)
Accepts 5/16 ID Hose
Connection
Control Label
Outlet Pressure Post
Set Screw: 3/32 Hex Head
(.339 Dia. + DFT.)
Accepts 5/16 Hose
Connection
2nd Stage Regulator cover
Regulator Adjust Beneath
This Screw
1st Stage Reg
ulator Cover
Regulator Adjust Beneath
This Screw
Vent (.330 Dia. +DFT. Post)
Accepts 5/16 Hose Connection
Figure 18. Gas Valve (White Rodgers)
Table 5. Capacity of Black Iron Gas Pipe
(cu. ft. per hour) for Natural Gas
(specific gravity = .60)
NOMINAL LENGTH OF PIPE RUN
BLACK IRON (feet)
PIPE DIAMETER
(in.) 1020304050607080
1/2
130
90
75
6
5555
0
4
5
40
3/4
280
190
1
5
0
130
11
5
10
5
9
5
90
1
5
20
3
5
0
28
5
24
5
21
5
19
5
180
1
7
0
1
1/4
10
5
0
7
30
5
90
5
00
440
400
3
7
0
3
5
0
1
1/2
1600
1100
890
7
60
6
7
0
610
5
60
5
30
The cubic feet per hour listed in the table above must be greater than the cubic feet
per hour of gas flow required by the furnace.
To determine the cubic feet per hour of gas flow required by the furnace, divide the
input rate of the furnace by the heating value of the gas:
Cubic Feet Per Hour Re
q
uired Input To Furnace (Btu/hr)
Heating Value of Gas (Btu/Cu. Ft.)
CAPACITY OF BLACK IRON GAS PIPE (CU. FT. PER HOUR)
FOR NATURAL GAS (SPECIFIC GRAVITY - 0.60)
Figure 17. Gas Valve (Honeywell shown)
VENT FITTING FOR 90 PLUS
EFFICIENT APPLIANCES
LOW STAGE ADJUSTMENT
UNDER VENT CAP
HIGH STAGE ADJUSTMENT
UNDER VENT CAP
OUTLET PRESSURE TAP
1/8 NPT
INLET PRESSURE TAP
1/8 NPT
2-STAG E
OPERATOR
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Westinghouse FG6T(A,K) Installation guide

Category
Stoves
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI