Trion 120 Series User manual

Category
Air purifiers
Type
User manual
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
SERIES
60/120
Electronic Air Purifiers
INSTRUCTION MANUAL
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
TRION
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
Contents
Introduction
Specification
Installation
Diagrams
Servicing / Maintenance
Parts List
Exploded Views
Wiring Diagrams
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
60/120
INTRODUCTION
The Trion 60 and 120 are commercial air purifiers that have been specifically designed to remove airborne pollutants
-including tobacco smoke, dust, pollen and mould spores- in rooms and areas where people work or relax. They
are designed to be either mounted onto a solid ceiling , semi-recessed for mounting into a suspended ceiling, or
wall mounted (60 only).Where appropriate they can also draw in additional fresh air.
Their features make them the ideal air purifier for installations into areas such as offices, conference rooms, public
houses, restaurants, designated smoking areas, institutions and waiting rooms or any other place where people
gather.
HOW THEY WORK
The Trion 60 and 120 utilise the principle of Electrostatic Precipitation. Air is drawn into the intake and through the
metal pre-filter, where lint and large dust particles are trapped. The remaining particles, some as small as 0.01
microns*, pass into a strong electrical field (ionising section) where the particles receive an electrical charge. The
charged particles pass onto a series of equally spaced parallel plates (collector section). Each alternate plate is
charged with the same polarity as the particles, which are repelled, while the interleaving plates are earthed, and
therefore attract and collect the particles.
* The diameter of a human hair is about 100 microns.
THE FILTER SYSTEM
There are two filters in your air cleaner: -
THE PRE-FILTER:This is the mechanical filter that lies behind the inlet grille.It is designed to remove large particles
and can be cleaned many times before replacement.
THE ELECTROSTATIC FILTER: This is the deep aluminium assembly immediately behind the pre-filter and is the
heart of your air cleaner. It uses an electrostatic charge to remove particles so small that it would take a pile of many
millions to cover a pinhead.When dirty it can be washed and reused indefinitely.
FILTER REMOVAL
TRION 60
Isolate unit from supply before removing cell.
Press the two cell access latches (fig 1) and the hinged door will swing down, remove pre-filter by turning pre-filter
clip through 90 degrees (fig 2).
Whilst supporting the weight of the filter, loosen the filter retaining screw (fig 3). The filter retaining plate will now
open and the filter can be lifted out (fig 4).
To refit filter simply reverse above procedure.
TRION 120
The two hinged doors are secured with fixing screws. Release screws and proceed as the TRION 60 above.
SITING
When siting, always remember that it is far easier to blow air than suck air. Consequently, locate the unit so that it
discharges the clean air into the dirty area, which will recirculate the dirty air back to the unit. Also, if more than one
unit is required, locate them so that they help each other circulate the air around the room, and do not act in
opposition to each other. However, it is appreciated that the overriding factor on siting is frequently where space is
available and so the above comments must be used for guidance only. If in doubt, consult your supplier.
This manual provides information for, installing, operation and maintenance of your Trion 60 and 120. Before
installation and use of the air cleaner, carefully read these instructions to ensure maximum benefits from the unit
and to avoid needless service costs that may result from improper installation and maintenance.
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
60/120
SPECIFICATION
TRION 60 TRION 120
Air Flow Multiple Discharge Multiple Discharge
Unit Weight 19 Kg 36 Kg
Dimensions Depth 242mm Depth 242mm
Width 572mm Width 572mm
Length 572mm Length 1144mm
Power Consumption 0.9 Amps, 130 Watts 1.6 Amps, 240 Watts
Input Power 220- 240 Volts 1 Phase 50Hz 230 Volts 1 Phase 50Hz
Controls 3 speed hard wired 3 speed hard wired
remote control. remote control.
Power to cell indicator Power to cell indicator
Safety Feature Interlock to cell access door Interlock to cell access doors
Features Anti-arc circuitry Anti-arc circuitry
Fresh Air inlet Fresh Air inlet
Forced Air dry Forced Air Dry
Optional Infrared remote control Infrared remote control
Fresh Air Damper System Fresh Air Damper System
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
60/120
INSTALLATION
WARNING:THIS APPLIANCE MUST BE EARTHED
Note
The unit is only designed to be permanently connected to fixed wiring. A plug or other means of disconnection from the supply
having a contact separation of at least 3mm in all poles must be fitted.
MECHANICAL
The unit has been designed so that it can fit either onto the ceiling , semi-recessed into a T-Bar suspended ceiling or wall mounted
(60). When installed with a T-Bar suspended ceiling NEVER support the unit from the T-Bars, the unit must be supported from
the permanent ceiling.
SUSPENDED CEILING Note: Requires suspended ceiling trim pack provided.
To hang the unit into a false ceiling, proceed as follows:
a) Unpack the unit, open filter access door and remove pre-filter and cell (see filter removal in section 2).
b) Install eyebolts as shown in sketch A. Alternatively use drop rods compatible with MB nuts located in
cabinet.
c) Install trims as shown in Fig 4.
d) Select and remove a ceiling tile near the centre of the area to be cleaned by the unit.
e) Attach a length of safety chain to each of the four eyebolts or fit threaded rod. Fasten securely.
f) Lift unit into place and support unit while securing to permanent ceiling, ceiling joists, etc. See sketch B.
IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE ADEQUATE FIXINGS ARE USED.
DO NOT ALLOW WEIGHT OF UNIT TO REST ON SUSPENDED CEILING
g) Make electrical connections as detailed in next section.
h) Re-install cell and pre-filter.
i) Close access door and unit is ready for operation.
SOLID CEILING MOUNTING
To mount the unit to a solid ceiling proceed as follows:
a) Unpack the unit, open filter access door and remove pre-filter and cell (see filter removal in section 2).
b) Select a location near the centre of the area to be cleaned. If you are fitting to wooden ceiling joists, locate the
position of joists.
c) Using the template provided, drill four holes into the ceiling and fit four screws. Hex-headed screws will give
easier access for final tightening. Do not tighten fully home.
d) Using the four keyhole slots in the unit, locate the unit on to screws and tighten fully home.
e) Fit Lock-down location screw as shown on template.
f) Make electrical connections as detailed in next section.
g) Re-install cell and pre-filter.
h) Close access door and unit is ready for operation.
WALL MOUNTED (60 Only)
To mount the unit to a wall proceed as follows:
To mount the unit to a solid ceiling proceed as follows:
a) Unpack the unit, open filter access door and remove pre-filter and cell (see filter removal in section 2).
b) Select a location near the centre of the area to be cleaned. Filter removal will be simpler if the unit is
mounted with the filter access door hinging on a vertical plane.
c) Using the template provided, drill four holes and fit four screws. Hex-headed screws will give easier access for final
tightening. Do not tighten fully home.
d) Using the four keyhole slots in the unit, locate the unit on to screws and tighten fully home.
e) Fit Lock-down location screw as shown on template.
f) Make electrical connections as detailed in next section.
g) Re-install cell and pre-filter.
h) Close access door and unit is ready for operation.
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
INSTALLATION continued
HARD WIRED REMOTE CONTROL
Two sets of wires are required for the unit viz.:
Mains supply 230 volt 50Hz 1 Phase 5 Amp, Live, Neutral and Earth, 5 core 5 Amp rated cable from the unit to the remote
control.
Run the 5 core cable and mains supply to the unit through the cable entry knockouts (see fig 5) into the input terminal blocks
(see fig 6). Remove the cover from the remote control and fix the base into the desired position. Connect the wires to the
numbered connectors in the remote control and the terminal block, taking care to connect proper colours together (see wiring
diagram).
INFRA RED
5 amp mains supply + earth is required to the unit.To install infrared proceed as follows:
1. Open fan access door.
2. Removal terminal block cover (see fig. 6) and retain screws.
3. Run supply cable through appropriate knockout and connect to the terminals marked E, L & N as shown in wiring
diagram.
4. Connect the flying leads from the I/R remote control board to the terminal block as per the wiring diagram..
5. Attach the mounting bracket to the unit using the screws previously used to attach the terminal block cover.
Please note the I/R control mounting bracket replaces the terminal block cover.
Infra Remote Control is an optional extra.
FRESH AIR COLLAR INSTALLATION
1. Remove fresh air inlet cover item 27 on exploded view.
2. The Trion fresh air collar part number G-234 has a mounting flange, which is formed like a screw thread. One full turn
of the collar in the fresh air inlet and it is installed.
3. Seal around the collar with duct tape.
4. Fit Trion duct hose part number 2615-P to the collar and tighten clamp (Part number 129389-007).
5. Cut duct hose as required. (Collar and duct hose are optional extras)
USE OF TEMPLATE
The Template is to be used when the unit is either wall mounted or mounted on to a solid ceiling.
1. The 1 x A hole is an alternative knockout for incoming power.
2. The 1 x B hole is an alternative knockout for Control Wiring.
3. The 4 x C holes are for the use of either 8mm eyebolts or 8mm drop rods.
4. The 1 x 6mm D hole is used for locking the unit to a solid ceiling.
5. The 4 x 6mm E holes are used for hanging the unit from the wall or solid ceiling.
6. The 1 x 152mm hole is used when the fresh air vent is required.0
SKETCH A
SKETCH B
EYEBOLT
NUT WASHER
UNIT
PERMANENT
CELING
SAFETY CHAIN
T-BAR CEILING
PERMANENT FLOATING
NUT LOCATED
IN CABINET
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
FIGURE 1. FIGURE 2.
FIGURE 3. FIGURE 4.
FIGURE 5. FIGURE 6.
CELL ACCESS LATCHES PRE-FILTER CLIP
FILTER RETAINING SCREW TRIMS / FILTER RETAING PLATE
CABLE ENTRY TERMINAL BLOCK
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
60/120
SERVICING & MAINTENANCE
Beyond an occasional wipe down with a damp cloth, the units need little in the way of maintenance.
However, the units are designed to collect airborne dirt and from time to time will require routine servicing to remove
the accumulation.
The service interval varies considerably between applications, but typically will range from six weeks in a busy bar
up to several months in a quiet office.
During normal operation the unit will make an occasional snapping noise. This is caused by large pieces of dirt
accumulating on the electronic filter and is not dangerous. The Trion 60 and 120 units have anti-arcing circuitry to
eliminate the nuisance of constant arcing. If, however, the arcing occurs every minute or two it is an indication that
the unit needs cleaning.
When a service is due proceed as follows:
a) Remove pre-filter and either vacuum clean or wash as described below.
b) To clean the electronic filter, soak it in a hot (not boiling), strong detergent solution - not caustic cleaner.
Trion can supply an excellent detergent- TRIDEX- obtainable through your Dealer. Alternatively a
dishwasher does an excellent job. After several hours soak, remove the filter and rinse with clean water.
Do not physically try to rub the dirt off since this can cause damage to the filter.
c) Allow the filter to dry thoroughly - preferably overnight- and replace into the unit or alternatively use force
air dry setting on the unit.
Trion Ltd., has a policy of continuous product improvement, and reserves the right to make changes in design and
specification without notice.
PARTS LIST
White Brown
Item Part Number Part Number Description Qty/Unit Qty/Unit
60 120
1 454027-001 454027-002 Cabinet Assembly 60 1 -
2 454028-001 454028-002 Cabinet Assembly 120 - 1
3 453844-001 453844-002 Cell Access Cover 2 2
4 453845-001 453845-002 Cell Access Cover - 2
5 153853-001 153853-001 Hinge Pin 2 4
6 453855-001 453855-002 Grill 4 6
7 453856-001 453856-002 Corner 4 4
8 453857-001 453857-002 Grill Filler - 2
9 253863-001 253863-001 Pre-filter 1 2
10 441730-103 441730-103 Collector Cell Assembly 1 2
11 150685-001 150685-001 Cell Retaining Clip 1 2
12 353842-001 353842-002 Cell Latch 1 2
13 153854-001 153854-001 Thumb Screw 1 2
14 244225-002 244225-002 Bolt Retainer 1 2
15 345109-001 345109-001 Cell Contact Assembly 1 2
16 243495-002 243495-002 Interlock Switch 2 4
17 147214-001 147214-001 Insulator 2 4
18 350950-003 350950-003 Power Supply Assembly 1 1
19 254167-002 254167-002 Stepdown Transformer 1 1
20 453847-001 453847-002 Motor Mounting Bracket 1 2
21 254026-001 254026-001 Motor, 230V/50Hz 1 2
22 133631-001 133631-001 Ground Contact 1 2
23 254101-001 254101-001 Fan 1 2
24 454858-001 454858-001 Inlet Ring 1 2
25 154164-009 154164-009 Terminal Block 1 1
26 253850-001 253850-002 Terminal Block Cover 1 1
27 253851-001 253851-001 Duct Cover Plate 1 2
28 153849-001 153849-002 Interlock Switch Actuator 1 2
29 253852-001 253852-001 Access Cover Latch 2 -
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
60/120
EXPLODED VIEWS
3
5
7
28
6
13
24
23
26
25
11
12
14
15
16
17
19
29
9
10
22
1
27 20 21
18
20 21
27 2
22
23
24
25
26
17
18
16
15
12
11
9
10
3
5
4
8
7
14
13
6
19
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
60
WIRING DIAGRAM
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
120
WIRING DIAGRAM
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
60
INFRA RED REMOTE CONTROL
WIRING DIAGRAMS
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Get In Touch
Call: 0845 6880112
120
INFRA RED REMOTE CONTROL
WIRING DIAGRAMS
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13

Trion 120 Series User manual

Category
Air purifiers
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI