JET 9400 metering stations accurately measure flow rates of non-hazardous liquids in various piping systems. They excel in diverse applications, including water distribution, heating and cooling systems, and industrial processes. These versatile devices provide reliable flow measurement, enabling efficient system monitoring and optimization.

JET 9400 metering stations accurately measure flow rates of non-hazardous liquids in various piping systems. They excel in diverse applications, including water distribution, heating and cooling systems, and industrial processes. These versatile devices provide reliable flow measurement, enabling efficient system monitoring and optimization.

JET 9400
1
MV95MS000.148-0
Wolseley UK
Harrison Way
Royal Leamington Spa
CV31 3HH
Tel : 01765 690690
How to use the JET 9400 Metering Stations
(Installation, Operating and Maintenance Instructions)
GENERAL INFORMATION
JET 9400 metering stations are used to measure
the flow passing through the pipework of a system
in which they are installed by measuring the
differential pressure between the test points.
The JET 9400 Metering Station is intended to be
used for non hazardous liquids only. These include
liquids in the Group 2 fluid classification as defined
by the Pressure Equipment Directive (Dir.
2014/68/EU). This, together with the
Pressure/Temperature rating shown overleaf
(Table 1), places the JET 9400 in the SEP
category, for which the CE logo is not required.
2
PRESSURE AND TEMPERATURE RATINGS
Non-shock pressure
at temp. range
Non-shock pressure
at maximum temp.
25 bar from -10°C (*) to 110°C
20 bar from 110°C to 130°C (**)
Table 1
(*) = Only for below zero water temperatures where antifreeze fluids have been added.
(**) = Only for water temperatures over 100°C where anti - boiling fluids have been added.
The operative conditions shown above are intended for non-shock operating
conditions: water hammer, impacts, stress loads, corrosive or erosive external
environmental elements and fluids with abrasive properties should be avoided.
INSTALLATION
JET 9400 valves ½” and ¾
have male/female end
threaded connections (ISO
228/1).
JET 9400 valves from 1” to
2” have male/female end
threaded connections (ISO
7/1 Rp).
It is important that the flow direction matches the direction of the arrow indicated
on the valve body. In order to obtain the best flow measurement accuracy, it is
advisable to install the JET 9400 valves:
- Using pipework of the same nominal size as the valve;
- With a minimum straight pipe length (equal to 5x Pipework Diameter) at the
inlet (10x when installed at the outlet of a pump) and a length of 2x Pipework
Diameter at the outlet.
- Avoid using any material to connect the pipes that may obstruct part of the flow
around the valve. Please ensure there are no burrs present on the pipe ends
themselves that protrude inside the bore and obstruct part of the flow (it’s
advisable to flush the line before installation or after subsequent maintenance
on the system).
The valves should be installed in such a way so that the pipeline does not subject
the valve to any torsion, bending or tension.
During the installation, please ensure to leave sufficient space around the test
points in order to allow enough room to connect the manometer probe.
3
FLOW MEASUREMENTS
Graph 1
The flow passing through the valve can be derived at any moment from the
differential pressure signal measured at the two test points (see flow chart
above). Versions for low flows are identified by a letter marked on the body, next
to the nominal diameter indication (L for low flows, U for very low flows).
VALVE TAG
JET 9400 valves are supplied with a data tag indicating:
- the Fig. Number of the valve type;
- the nominal size;
- the value of the flow coefficient Kvs
On the tag there is sufficient room to write the desired flowrate or the pressure
signal. The tag can be fixed to the valve with the provided plastic tie. By keeping
the tie long, it is possible to leave the tag on the outside of any thermal isolation,
thus simplifying the identification of the insulated device.
10,0
100,0
1,0
0,1
0,01
1
10
100
Q [l/s] = Flowrate
Δps [kPa] = Signal
U-½, Kvs 0,55
L-½, Kvs 1,15
½, Kvs 2,80
¾, Kvs 5,33
, Kvs 9,72
, Kvs 20,25
1”, Kvs 30,23
2”, Kvs 55,07
  • Page 1 1
  • Page 2 2
  • Page 3 3

JET 9400 User manual

Type
User manual

JET 9400 metering stations accurately measure flow rates of non-hazardous liquids in various piping systems. They excel in diverse applications, including water distribution, heating and cooling systems, and industrial processes. These versatile devices provide reliable flow measurement, enabling efficient system monitoring and optimization.