Weil-McLain 633500203 User manual

Category
Water heaters & boilers
Type
User manual

This manual is also suitable for

Part number 633-500-230/0918
• Installation
• Startup
• Maintenance
• Parts
Product Manual
PRO
This manual must only be used by a qualified heating installer/service technician. BEFORE installing, read all instructions
in this manual and all other information shipped with the water heater. Perform steps in the order given. Failure to comply
could result in severe personal injury, death or substantial property damage.
User Read important user safety information found on page 3, page 27 and page 28. Installation and service should only be
performed by a qualified service technician. Retain this manual for future reference.
®
Indirect-Fired Water Heaters
Part number 633-500-230/0918
2
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Please read before proceeding 3
When servicing water heater . . . . . . . . . . . . . . . . . . . . 3
Operating restrictions . . . . . . . . . . . . . . . . . . . . . . . . 3
Boiler water restrictions . . . . . . . . . . . . . . . . . . . . . . . 3
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Pre-installation 4
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Code restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Water heater placement . . . . . . . . . . . . . . . . . . . . . . . 4
Install levelling legs . . . . . . . . . . . . . . . . . . . . . . . . . 4
Domestic water piping requirements. . . . . . . . . . . . . . . . 5
Water heater operating restrictions. . . . . . . . . . . . . . . . . 5
Boiler water restrictions . . . . . . . . . . . . . . . . . . . . . . . 5
Hot Water Can Scald! . . . . . . . . . . . . . . . . . . . . . . . . 5
Domestic water piping 6
Piping overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Recirculation 8
Maintaining domestic water temperature in the supply piping . 8
Time delay at fixtures . . . . . . . . . . . . . . . . . . . . . . . . 8
Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Components required . . . . . . . . . . . . . . . . . . . . . . . . 8
Connecting to the water heater . . . . . . . . . . . . . . . . . . . 8
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Potential problems. . . . . . . . . . . . . . . . . . . . . . . . . 10
Boiler-side piping 11
Connecting to a low-pressure steam boiler 18
Filling the piping . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Boiler-side wiring and controls 20
Wiring requirements. . . . . . . . . . . . . . . . . . . . . . . . 20
Circulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Zone Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Wiring to the water heater. . . . . . . . . . . . . . . . . . . . . 20
Wiring options . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Use domestic priority . . . . . . . . . . . . . . . . . . . . . . . 20
Wiring — zoning with circulators 23
Wiring — zoning with zone valves 23
Mounting and wiring the Control - New Installations 24
Setting the Control 25
Water heater filling and start-up 26
Boiler water restrictions . . . . . . . . . . . . . . . . . . . . . . 26
Maximum boiler-side flow rate . . . . . . . . . . . . . . . . . . 26
Filling the domestic water tank . . . . . . . . . . . . . . . . . . 26
Start-up and operation . . . . . . . . . . . . . . . . . . . . . . 26
Start-up checklist . . . . . . . . . . . . . . . . . . . . . . . . . 26
Water heater temperature adjustment 27
Setting the control . . . . . . . . . . . . . . . . . . . . . . . . . 27
Hot Water Can Scald! . . . . . . . . . . . . . . . . . . . . . . . 27
Water heater maintenance 28
ANNUAL start-up by qualified service technician . . . . . . . 28
Drain the water heater if necessary during shutdown periods . 28
Troubleshooting 29
Troubleshooting procedures . . . . . . . . . . . . . . . . . . . . . 29
Preparation for troubleshooting . . . . . . . . . . . . . . . . . . . 29
Replacement parts 38
Rating – Aqua Pro
TM
39
Dimensions 40
Contents
Failure to adhere to the guidelines on this page can
result in severe personal injury, death or substantial
property damage.
Read all instructions before installing. Failure to follow all instruc-
tions in proper order can cause severe personal injury, death or
substantial property damage.
When servicing water heater
To avoid electric shock, disconnect electrical supply before
performing maintenance.
To avoid severe burns, allow water heater to cool before per-
forming maintenance.
Operating restrictions
Maximum domestic hot water temperature: residential sizes
160°F, commercial sizes — 180°F. Pay attention to the
water temperature warnings throughout this manual.
Maximum boiler water temperature — 200°F.
Maximum working pressure for tank — 150 PSIG.
Boiler water restrictions
Thoroughly flush the boiler system (without water heater
connected) to remove sediment.
The water heater heat exchanger can be damaged by build-up
or corrosion due to sediment.
Boiler water (including additives) must be practically non-
toxic, having toxicity rating or class of 1, as listed in Clinical
Toxicology of Commercial Products.
If antifreeze is used in boiler system:
Local codes may require a backflow preventer on cold
water supply line.
Use antifreeze specifically intended for hydronic heating
systems. Inhibited propylene glycol is recommended.
Follow boiler manual instructions for antifreeze usage.
Do not use automotive, ethylene glycol or petroleum-
based antifreeze. Do not use any undiluted antifreeze.
Location
This water heater is not intended for outdoor installation.
Install the water heater so if the tank or any connections
should leak, the water flow will not cause damage to area
near water heater, or to lower floors of structure. When such
locations cannot be avoided, install a suitable drain pan under
water heater. Drain pans are available at your local plumbing
supply store.
This product is designed for vertical installation only.
When calling or writing about the water
heater — Please have the water heater se-
rial number from the serial number label,
located on the back side of the water
heater, adjacent to the rating plate.
Any claims for damage or shortage in
shipment must be filed immediately
against the transportation company by
the consignee.
Hazard definitions
The following defined terms are used throughout this
manual to bring attention to the presence of hazards
of various risk levels or to important information
concerning the life of the product.
Indicates presence of hazards that will
cause severe personal injury, death or
substantial property damage.
Indicates presence of hazards that can
cause severe personal injury, death or
substantial property damage.
Indicates presence of hazards that will
or can cause minor personal injury or
property damage.
Indicates special instructions on installa-
tion, operation or maintenance that are
important but not related to personal
injury or property damage.
This manual provides installation and
operation guidelines for Weil-McLain
Aqua Pro
TM
indirect water heaters. The
installer is responsible for ensuring
that the installation complies with this
manual, the boiler manual and all ap-
plicable codes.
Massachusetts installations — The
water heater must be installed by a li-
censed plumber. The installation must
follow all Massachusetts code require-
ments. The domestic water piping must
comply with the piping shown in this
manual. See “Domestic water piping,
page 6, for details and code requirements.
Part number 633-500-230/0918
3
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Please read before proceeding
Pre-installation
Part number 633-500-230/0918
4
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Figure 1 Clearance recommendations
Codes
1. Installation must conform with instructions in this
manual and, where applicable:
local, state, provincial, and national codes, laws,
regulations and ordinances.
in Canada — B149.1 or B149.2 Installation
Code - latest edition.
2. Aqua Pro
TM
water heaters are exempt from ASME
Section VIII, Division 1 Code construction per
Interpretation VIII-1-86-136. Check with local
codes for applicability.
3. Where recommendations in this manual differ from
local or national codes, local or national codes take
precedence.
Code restrictions
National Standard Plumbing Code
1. Single-wall heat exchanger in water heater complies
with National Standard Plumbing Code, provided
that:
a. boiler water (including additives) is practically
non-toxic, having toxicity rating or class of 1,
as listed in Clinical Toxicology of Commercial
Products, and
b. boiler water pressure is limited to maximum 30
PSIG by approved relief valve.
Uniform Plumbing Code
1. Single-wall heat exchangers are permitted if they
satisfy all of the following requirements —
a. The heat transfer medium is potable water or
contains only substances which are recognized
as safe by the U. S. Food and Drug Adminis-
tration.
b. The pressure of the heat transfer medium is
maintained less than the normal minimum
operating pressure of the potable water system.
c. Exception: Steam complying with #a, above.
d. The equipment is permanently labeled to indi-
cate that only additives recognized as safe by the
FDA shall be used in the heat transfer medium.
2. Other heat exchanger designs may be permitted
where approved by the Administrative Authority.
Recommended clearances
Installation location must provide adequate clearances for servicing and
proper operation of the water heater. See Figure 1.
1” clearance is permissible to either side of water heater, but the Instruc-
tion label or other labels may be hidden.
Top (vertical) clearance is
A minimum.
Clearance for the servicing the replacement Heat Exchanger are as follows:
A” minimum
Models Aqua Pro
TM
30 & 55 — 36”
Models Aqua Pro
TM
80 — 48”
Models Aqua Pro
TM
119 — 66”
Clearance to combustible materials
1. Provide at least ½” clearance between all hot water pipes and combus-
tible materials.
Water heater placement
1. Read and comply with “Location, page 3 of this manual.
2. Select a convenient location for the water heater, based on domestic
and boiler piping hook-ups.
3. Keeping the distance between boiler and water heater short will:
reduce piping heat loss.
provide minimum friction loss.
Pre-installation
(continued)
Hot Water Can Scald!
Water heated to temperature for clothes washing,
dish washing and other sanitizing needs can scald
and cause permanent injury.
Children, elderly, and infirm or physically handi-
capped persons are more likely to be permanently
injured by hot water. Never leave them unattended
in bathtub or shower. Never allow small children to
use a hot water tap or draw their own bath.
If anyone using hot water in the building fits
the above description, or if state laws or local
codes require certain water temperatures at
hot water taps, you must take special precau-
tions:
Use lowest possible temperature setting.
Install some type of tempering device, such
as an automatic mixing valve, at hot water
tap or water heater. Automatic mixing valve
must be selected and installed according
to valve manufacturer’s recommendations
and instructions.
Water passing out of drain valves may be extremely
hot. To avoid injury:
Make sure all connections are tight.
Direct water flow away from any person.
Protection must be taken against excessive tem-
perature and pressure! Installation of a tem-
perature & pressure (T&P) relief valve (provided
with water heater) and a thermostatic mixing valve
(provided by installer) is required.
Part number 633-500-230/0918
5
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Domestic water piping requirements
1. Install unions on all piping for easy removal of water heater.
2. Use dielectric unions or couplings to protect hot and cold water
fittings from corrosion when connecting dissimilar materials such
as copper and galvanized iron pipe.
3.
When the supply pressure is higher than 70 PSIG, install a pres-
sure reducing valve on cold water supply line to prevent water loss
through T&P relief valve. A thermal expansion tank is also required.
4. If the water heater will replace a tankless coil in the boiler, discon-
nect piping to coil or remove coil from boiler and replace with
a cover plate. Allow water to drain from coil.
Do not plug the
tankless coil.
Plugging tankless coil inlet and outlet will result in severe
personal injury, death or substantial property damage.
Studies have indicated that dangerous bacteria,
including
legionella pneumophila, can form in
the potable water distribution system if certain
minimum water temperatures are not maintained.
Contact your local health department for more
information.
Boiler water restrictions
1. Read the WARNINGS under “Boiler water restrictions, page 3.
Domestic water piping
Figure 2 DHW piping
Piping overview
THERMAL EXPANSION TANK — If a
backflow preventer, check valve, or pres-
sure reducing valve is piped on cold water
inlet of water heater, you must install an
expansion tank on cold water supply line
to prevent normal thermal expansion
from repeatedly forcing open T&P relief
valve.
The T&P relief valve is not intended for
constant duty, such as relief of pressure
due to repeated normal system expan-
sion. Refer to expansion tank manufac-
turer’s instructions for proper sizing.
Failure to comply could result in severe
personal injury, death or substantial
property damage.
General applications
1. Figure 2 — This piping configuration can be used in
most cases, except where local codes require special
components or piping not illustrated.
2. Some codes may require the items listed as optional,
such as a vacuum breaker on the inlet line, or re-
circulation piping.
Massachusetts applications
1. For Massachusetts code applications, or as
required elsewhere by local codes, install the fol-
lowing options.
a. Thermal siphon on DHW inlet and outlet.
b. Vacuum breaker on domestic water inlet line.
c. Recirculation
Massachusetts code applica-
tions require recirculation piping or heat-traced
piping if the distance from the water heater to
the furthest fixture exceeds 100 feet. See page 8
for details.
Figure 3
Piping connection sizes
Model
Aqua Pro
TM
Connections
(inches MNPT)
DHW
in/out
Boiler
water
in/out
30
¾¾
55
¾¾
80
1 ½ 1
119
1 ½ 1
Part number 633-500-230/0918
6
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Domestic water piping
(continued)
Part number 633-500-230/0918
7
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
LEGEND for Figure 2, page 6
Domestic water supplied to fixtures that could pose
an injury hazard due to high temperature, such as
showers and faucets, should be equipped with a
temperature regulating device, such as an anti-scald
mixing valve
.
When the supply pressure is higher than 70 PSIG,
install a
pressure reducing valve on cold water
supply line to prevent water loss through T&P relief
valve. A thermal expansion tank is also required.
This symbol, where used in this manual, indicates the
item is required by Massachusetts code.
This symbol indicates the item is optional, unless
required by applicable codes.
1 Domestic cold water inlet connection — see Fig-
ure3,page6 for size
2 Domestic hot water outlet connection — see Fig-
ure3,page6 for size
3 Boiler water inlet to coil — see Figure3,page6 for size
4 Boiler water outlet from coil — see Figure3,page6 for
size
5 Drain valve — provided by installer
Install a drain valve on the DHW inlet to the water heater
as shown.
6 Piping from drain valve
Pipe from drain to floor drain, if available.
7
T&P relief valve — supplied with water heater
Use only the T&P valve supplied with the water heater.
See Replacement parts for part number.
Install the T&P relief valve in the top left tapping, as
shown.
8
T&P relief valve discharge piping —
must be made of material serviceable for temperatures
of 250°F or greater.
must be directed so that hot water flows away from all
persons.
must be directed to a suitable place for disposal.
must be installed so as to allow complete draining of the
T&P relief valve and discharge line.
must NOT be excessively long — using more than 2
elbows or 15 feet of piping can reduce discharge capacity.
must NOT be directly connected to a drain — terminate
discharge piping within 6” from floor — refer to local
codes.
must NOT be plugged, reduced or restricted.
must NOT be subjected to freezing.
Do not install any valve between T&P relief valve and
tank connection, or on T&P relief valve discharge
piping. Do not plug T&P relief valve or its discharge
piping. Improper placement and piping of T&P re-
lief valve can cause severe personal injury, death or
substantial property damage.
9
Temperature - Electronic Control
10 Mixing valve — RECOMMENDED
See Replacement parts for thermostatic mixing valves
available from Weil-McLain.
11
Domestic cold water supply
When the water supply pressure is higher than
70 PSIG, install a pressure-reducing valve on the cold
water supply line to prevent leakage from the T & P
relief valve. A thermal expansion tank is also required.
12
Domestic mixed-temperature water supply to
system
(when used — requires mixing valve)
13 Domestic high-temperature hot water supply to
system
14 Heat trap loops (12” minimum) —
15 Isolation valves
16 Thermal expansion tank —
REQUIRED if cold water line is equipped with a backflow
preventer or pressure reducing valve — see
EXPANSION
TANK WARNING
on page 6.
17
Shock arrester —
Dishwashers, clothes washers, and fast-closing positive
shutoff valves incorporated in the system all contrib-
ute to creating water shock. Install a water hammer
arrester to prevent damage to pipes and appliances.
See control manufacturer’s instructions for applica-
tion and installation.
18
Unions
Use dielectric unions or couplings to protect hot and cold
water fittings from corrosion when connecting dissimilar
materials such as copper and galvanized iron pipe.
19
Backflow preventer — (required
for Commonwealth of Massachusetts)
20 Vacuum breaker —
21 Pressure reducing valve —
REQUIRED when the supply pressure is higher than
70 PSIG — A thermal expansion tank is also required.
Recirculation
Massachusetts code applications require recircu-
lation piping or heat-traced piping if the distance
from the water heater to the furthest fixture exceeds
100 feet.
Maintaining domestic water
temperature in the supply piping
1. Recirculation is used to reduce wait time for water use, to
minimize hot water and energy waste caused during the
waiting period, and to prevent degradation of the system
supply water temperature. ASPE recommends recirculation
when the distance from the water heater to the furthest fix-
ture exceeds 100 feet or the time lag for hot water to reach a
fixture(s) exceeds 30 seconds.
2. Consult local codes and American Society of Plumbing
Engineers (ASPE) Domestic Water Heating Design Manual,
1998, for further information.
Time delay at fixtures
1. Figure 4, page 9 is from the ASPE Domestic Water Heating
Design Manual, 1998. It shows the time required for usable
hot water to arrive at a fixture based on the fixture flow rate
(available from industry and manufacturer’s data) and the
length and diameter of the dead-end branch pipe supplying
the fixture.
2. The time lag should generally not exceed 30 seconds.
3. For residential and office applications, the owner may prefer
a limit of 10 seconds.
4. You can use Figure 5 as a guide to determining the location
of circulation return lines relative to fixtures.
Balancing
1. When multiple branches are connected to the supply pip-
ing, each branch must be connected to the recirculation
system.
a. At each of these connections to the return piping, install
shutoff valves, a flow metering device, check valve and a
strainer as shown in Figure 4, page 9.
b. Check local codes for specific installation require-
ments.
2. These branches must be balanced to prevent pipe erosion
and unacceptable time delays at some fixtures.
3. Balancing options include circuit setters, memory stop valves
or factory preset devices (with flow metering provision in
the piping).
Components required
1. For residential applications, consult circulator manufacturer’s
data for circulator selection and additional components
required.
2. On most commercial systems, install the devices shown in
Figure 5, page 9, and any other devices or piping methods
required by local codes.
a. The check valves are required to prevent fixtures from
taking hot water through the return lines.
b. Shutoff valves are needed to allow cleaning and replacing
balancing devices.
c. Include strainers to remove sediment which could
damage the circulator and / or affect the flow balancing
devices.
3. Size the circulator and piping based on the temperature drop
allowed between the water available at the water heater and
the water delivered at the fixture.
a. The return piping will almost always be smaller than the
supply piping, but should never be smaller than ½” to
prevent problems with the circulator.
4. Make provision for removal of air in all return lines. Where
the returns cannot be vented by topmost fixtures in the
system, install automatic air venting at the top of the return
piping.
Connecting to the water heater
1. Install the domestic water components as shown in Fig-
ure 2, page 6.
2. See Figure 6, page 10 for the piping required to the water
heater.
— Continued on page 10 —
Part number 633-500-230/0918
8
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Recirculation
(continued)
Part number 633-500-230/0918
9
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Time in seconds required to get hot water at fixture (from ASPE)
Fixture flow rate (GPM) - 0.5 1.5 2.5 4.0
Piping length (feet) - 10 25 10 25 10 25 10 25
Copper pipe ½” 25 63 8 21 5 13 3 8
¾” 48 119 16 40 10 24 6 15
Steel pipe ½” 63 157 21 52 13 31 8 20
¾” 91 228 30 76 18 46 11 28
CPVC pipe ½” 64 159 21 53 13 62 8 20
¾” 95 238 32 79 19 48 12 30
NOTE: Select branch size and length for less than 31 seconds delay.
Figure 4 Time lag to obtain hot water at fixture for branch lengths of 10 and 25 feet (ASPE Domestic Water Heating Design Manual)
Figure 5 Recirculation components
Recirculation
(continued)
Figure 6 Recirculation piping
Components
Circulator (Figure 6, item 1)
1. Little flow is required to maintain a temperature
in the piping.
2. Size of circulator depends on minimum flow re-
quirements of the tempering valve.
3. Minimum flow rates of the tempering valve must
be maintained.
Aquastat (Figure 6, item 2)
1. Used to control the on-off position of the circula-
tor. Aquastat is set 5° to 10° lower than mixed water
outlet of the mixing valve (#7).
2. The circulator cannot run continuously as bypass
through the mixing valve will eventually allow the
temperature on the piping to climb to the water
heater temperature during draw periods.
Check valves (Figure 6, items 3–6)
1. Assure the flow of water in one direction.
2. Each check valve functions as follows:
a. #3 and #4 prevent bypass in the event of pres-
sure drop.
b. #5 prevents thermal siphoning of hot water to
the cold water supply.
c. #6 prevents flow of cold water to the tempered
water supply. A draw of tempered water will not
result in flow of cold water into the return loop.
Operation
1. During period of normal use (fixtures on) — Circu-
lator is off. There is no flow through #6, there is flow
through #5 equal to the flow at the fixtures, there is
flow through #3 and/or #4 equal to flow at fixture.
2. When all fixtures are off — Circulator is off. There is
no flow through #3, #4, #5 or #6. Water temperature
in piping is cooling.
3. When temperature at aquastat #2 falls 10° below
temperature to be maintained — Circulator is on.
There is flow through #6 equal to the minimum
required by the mixing valve, flow through #3 and
#4 equals the flow of the circulator. There is no
flow through #5.
4. Aquastat reaches temperature — Circulator is off.
There is no flow through #3, #4, #5 or #6.
Potential problems
1. Missing check valves #3 or #4 — Extreme pressure drop can cause
reverse flow of water; hot to cold supply or cold to hot supply.
2. Missing check valve #5 — Hot water can migrate from the water heater
back through the cold water supply.
3. Missing check valve #6 — Cold water can be forced back through the
tempered water supply when a fixture is opened.
4. No aquastat #2 — Circulator runs continuously. Small amount of
water will pass through mixing valve. Eventually all hot water is flow-
ing through valve. Recirculated water through cold port, hot water
through hot port.
5. Circulator too small — Mixing valve performance erratic.
Part number 633-500-230/0918
10
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Figure 7 Zoning with circulators — direct-connected system piping
Boiler-side piping
Part number 633-500-230/0918
11
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Maximum boiler-side flow rate
Recommended flow rate and minimum boiler-side pipe size
Select the boiler-side circulator carefully. The flow rate
through the boiler side of the water heater must not
exceed the values below. Higher flow rates could result
in an input above the rating of the T&P valve.
Models Aqua Pro
TM
30 & 55 do not exceed 12 GPM.
Models Aqua Pro
TM
80 &119 do not exceed 16 GPM.
Heater model GPM Pipe size Heater model GPM Pipe size
30
8.00 3/4”
80
14.00 1” *
55
8.00 3/4”
119
14.00 1” *
*Requires 1¼”x1” reducers at water heater
Notes
Place circulators at begin-
nings of zones. Placing
them at the ends of zones
could result in heating idle
zones.
Size manifold piping for
total flow of all zone cir-
culators.
Locate flow / check valves
as close as possible to water
heater boiler side connec-
tions — to reduce heat loss
between cycles.
Wiring
WMCR zone controller,
optional priority — Fig-
ure 25, page 23.
1. This drawing is conceptual
only. It shows representative
piping components and lay-
out. Weil-McLain does not
represent that this drawing
meets any particular me-
chanical or building codes.
The installer is responsible
for inclusion of all required
safety devices, or other mis-
cellaneous piping hardware
not shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.
2. See boiler manual for spe-
cific details on installing the
boiler.
Boiler-side piping
(continued)
Figure 8 Zoning with circulators — primary/secondary system piping
Part number 633-500-230/0918
12
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Notes
Place circulators at begin-
nings of zones. Placing
them at the ends of zones
could result in heating idle
zones.
Size manifold piping for
total flow of all zone cir-
culators.
Locate flow / check valves
as close as possible to water
heater boiler side connec-
tions — to reduce heat loss
between cycles.
Wiring
WMCR zone control-
ler, optional priority —
Figure 25, page 23.
Maximum boiler-side flow rate
Recommended flow rate and minimum boiler-side pipe size
Select the boiler-side circulator carefully. The flow rate
through the boiler side of the water heater must not
exceed the values below. Higher flow rates could result
in an input above the rating of the T&P valve.
Models Aqua Pro
TM
30 & 55 do not exceed 12 GPM.
Models Aqua Pro
TM
80 &119 do not exceed 16 GPM.
Heater model GPM Pipe size Heater model GPM Pipe size
30
8.00 3/4”
80
14.00 1” *
55
8.00 3/4”
119
14.00 1” *
*Requires 1¼”x1” reducers at water heater
1. This drawing is conceptual
only. It shows representative
piping components and lay-
out. Weil-McLain does not
represent that this drawing
meets any particular me-
chanical or building codes.
The installer is responsible
for inclusion of all required
safety devices, or other mis-
cellaneous piping hardware
not shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.
2. See boiler manual for spe-
cific details on installing the
boiler.
Boiler-side piping
(continued)
Figure 9 Zoning with zone valves — direct-connected system piping
Part number 633-500-230/0918
13
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Notes
Place circulators at begin-
nings of zones. Placing
them at the ends of zones
could result in heating idle
zones.
Size manifold piping for
total flow of all zone cir-
culators.
Locate flow / check valves
as close as possible to water
heater boiler side connec-
tions — to reduce heat loss
between cycles.
Wiring
WMZV zone control-
ler, optional priority —
Figure 26, page 23.
Maximum boiler-side flow rate
Recommended flow rate and minimum boiler-side pipe size
Select the boiler-side circulator carefully. The flow rate
through the boiler side of the water heater must not
exceed the values below. Higher flow rates could result
in an input above the rating of the T&P valve.
Models Aqua Pro
TM
30 & 55 do not exceed 12 GPM.
Models Aqua Pro
TM
80 &119 do not exceed 16 GPM.
Heater model GPM Pipe size Heater model GPM Pipe size
30
8.00 3/4”
80
14.00 1” *
55
8.00 3/4”
119
14.00 1” *
*Requires 1¼”x1” reducers at water heater
1. This drawing is conceptual
only. It shows representative
piping components and lay-
out. Weil-McLain does not
represent that this drawing
meets any particular me-
chanical or building codes.
The installer is responsible
for inclusion of all required
safety devices, or other mis-
cellaneous piping hardware
not shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.
2. See boiler manual for spe-
cific details on installing the
boiler.
Boiler-side piping
(continued)
Figure 10 Zoning with zone valves — primary/secondary system piping
Part number 633-500-230/0918
14
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Notes
Place circulators at begin-
nings of zones. Placing
them at the ends of zones
could result in heating idle
zones.
Size primary piping for
total flow of all zone cir-
culators.
Locate flow / check valves
as close as possible to water
heater boiler side connec-
tions — to reduce heat loss
between cycles.
Wiring
WMZV zone controller,
optional priority — Fig-
ure 26, page 23.
Maximum boiler-side flow rate
Recommended flow rate and minimum boiler-side pipe size
Select the boiler-side circulator carefully. The flow rate
through the boiler side of the water heater must not
exceed the values below. Higher flow rates could result
in an input above the rating of the T&P valve.
Models Aqua Pro
TM
30 & 55 do not exceed 12 GPM.
Models Aqua Pro
TM
80 &119 do not exceed 16 GPM.
Heater model GPM Pipe size Heater model GPM Pipe size
30
8.00 3/4”
80
14.00 1” *
55
8.00 3/4”
119
14.00 1” *
*Requires 1¼”x1” reducers at water heater
1. This drawing is conceptual
only. It shows representative
piping components and lay-
out. Weil-McLain does not
represent that this drawing
meets any particular me-
chanical or building codes.
The installer is responsible
for inclusion of all required
safety devices, or other mis-
cellaneous piping hardware
not shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.
2. See boiler manual for spe-
cific details on installing the
boiler.
Boiler-side piping
(continued)
Figure 11 Dedicated single-boiler piping
Part number 633-500-230/0918
15
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Notes
Place circulators at beginnings
of zones. Placing them at the
ends of zones could result in
heating idle zones.
Size manifold piping for total
flow of all zone circulators.
Locate flow / check valves as
close as possible to water heater
boiler side connections — to
reduce heat loss between cycles.
Wiring
Connect water heater control
wires to boiler’s T-T terminals
or heat demand connection.
Maximum boiler-side flow rate
Recommended flow rate and minimum boiler-side pipe size
Select the boiler-side circulator carefully. The flow rate
through the boiler side of the water heater must not
exceed the values below. Higher flow rates could result
in an input above the rating of the T&P valve.
Models Aqua Pro
TM
30 & 55 do not exceed 12 GPM.
Models Aqua Pro
TM
80 &119 do not exceed 16 GPM.
Heater model GPM Pipe size Heater model GPM Pipe size
30
8.00 3/4”
80
14.00 1” *
55
8.00 3/4”
119
14.00 1” *
*Requires 1¼”x1” reducers at water heater
1. This drawing is conceptual
only. It shows representative
piping components and lay-
out. Weil-McLain does not
represent that this drawing
meets any particular me-
chanical or building codes.
The installer is responsible
for inclusion of all required
safety devices, or other mis-
cellaneous piping hardware
not shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.
2. See boiler manual for spe-
cific details on installing the
boiler.
Boiler-side piping
(continued)
Figure 12 Multiple water heaters — domestic water piping
Figure 13 Alternate methods of revers-return piping and Easy-Fit® Manifold detail
Part number 633-500-230/0918
16
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Failure to install automatic
mixing valve where recom-
mended can result in severe
personal injury or death.
1. This drawing is conceptual
only. It shows representative
piping components and lay-
out. Weil-McLain does not
represent that this drawing
meets any particular me-
chanical or building codes.
The installer is responsible
for inclusion of all required
safety devices, or other mis-
cellaneous piping hardware
not shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.
2. Wire water heater controls
in series when connecting
to boiler controller or boiler
T-T terminals.
3. Install automatic mixing
valve at either the system
hot water connection or at
each water heater.
4. See page 8 through page 10
for additional recirculation
information and piping
details.
Boiler-side piping
(continued)
Figure 14 Multiple water heaters and dedicated multiple boilers — boiler water piping
Part number 633-500-230/0918
17
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Notes
See legend and details in
Figure 12, page 16.
1. This drawing is conceptual
only. It shows representative
piping components and lay-
out. Weil-McLain does not
represent that this drawing
meets any particular me-
chanical or building codes.
The installer is responsible
for inclusion of all required
safety devices, or other mis-
cellaneous piping hardware
not shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.
2. See boiler manual for spe-
cific details on installing the
boiler.
Connecting to a low-pressure steam boiler
Special considerations
When designing steam and domestic hot water systems, there are some
key issues that must be taken into consideration during the initial de-
sign phase. By designing the system properly from the start, you can
avoid problems and have a hot water loop in a steam boiler system.
The domestic water demand should preferably not exceed 1/3
of the steam boiler capacity. Larger demand may cause difficulty
obtaining steam as needed.
Keep the loop temperature below the flash point. Flashing can result
in noise and circulator damage or shortened life.
Be sure the loop is completely closed, with no automatic or manual
air vents, or anything that could allow air to enter the system when
the pump shuts off.
Pipe supply from one side of the boiler, return to the opposite
side as shown.
Supply from a tapping that is high enough to prevent introducing
sediment into the piping and circulator yet still below the water
line. Avoid the mud leg of the boiler.
Use an all bronze circulator.
Avoid wet rotor circulators. Select a circulator with a large
volute, such as a typical 3-piece circulator.
This will reduce clogging and will resist the corrosion potential
from the steam condensate.
Make sure the circulator is properly sized. If the circulator runs too
far out on its curve, cavitation potential increases significantly.
Use (2) flow / check valves as shown to reduce the potential for
gravity circulation.
DO NOT use spring-loaded check valves in place of the
flow / check valves shown in Figure 16, page 19.
Installation and start-up of water heaters
connected to steam boilers
1. See Figure 16, page 19, for suggested piping schematic.
2. Pipe the domestic water connections to the water heater per “Do-
mestic water piping, page 6.
Boiler connections for the water heater must be below
the water line. DO NOT use the gauge glass tapping or a
low water cut-off tapping if a LWCO is installed there.
For steam piping, refer to the steam boiler manual.
DO NOT install an air vent anywhere in the piping. The
piping must be air tight.
3. Wire the water heater and circulator to the boiler per suggested
wiring in Figure 15. The water heater must be wired and ready to
operate before proceeding. Note that the L4006A aquastat is located
in the boiler and sets a boiler operating temperature when there is
no call for steam heating.
To fill the boiler and water heater:
1. Follow the procedure given in Figure 16, page 19 to fill the water
heater piping.
2. Follow the boiler manual instructions to fill the steam boiler.
Figure 15 Typical wiring for connection to low-pressure
steam boiler
Install the Honeywell L4006A aquastat in the boiler,
below the water line. Set for a temperature of 180 to
190°F to control boiler temperature when there is no
call for steam heating.
Valve 7, the memory stop valve, must
be supplied, piped and adjusted as in-
structed. This valve allows cooler return
water to mix with the hot water from
the steam boiler. The valve is set to yield
approximately 180°F water entering the
circulator. Higher temperature water
could cause cavitation in the circulator,
damaging the impeller and shortening
circulator life.
DO NOT connect the piping to the boil-
er’s mud leg. This would probably cause
excessive sediment to enter the water
heater piping, damaging the circulator.
The strainer in the circulator suction line
must be serviced regularly. NOTE that
noise from the circulator is a likely sign
that the strainer is restricting circulator
flow, causing cavitation.
Part number 633-500-230/0918
18
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Connecting to a low-pressure steam boiler
(continued)
Figure 16 Low pressure steam boiler application — Domestic water heating using water pumped from steam boiler
Part number 633-500-230/0918
19
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Notes
Locate flow / check valve as
close as possible to water
heater boiler side connec-
tions — to reduce heat loss
between cycles.
Use memory stop valve 7 to
blend some of the water re-
turning to the boiler with the
hot water coming from the
boiler. This will reduce the
possibility of flashing (cavita-
tion) in the circulator. Slowly
open valve 7 until temperature
gauge 8 reads 200°F.
Set the memory stop on valve 7
after adjusting. Attach a tag to
the valve warning no to close
or change valve position.
NOTE —
If the boiler water
level should drop below ei-
ther the water heater boiler
water supply or return line,
the filling procedure will
have to be repeated.
1. This drawing is conceptual
only. It shows representative
piping components and lay-
out. Weil-McLain does not
represent that this drawing
meets any particular me-
chanical or building codes.
The installer is responsible
for inclusion of all required
safety devices, or other mis-
cellaneous piping hardware
not shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.
2. See boiler manual for spe-
cific details on installing the
boiler.
Filling the piping
1. Parts of the boiler water piping to the water
heater may be higher than the water line,
depending on the height of the water heater
boiler supply connection. The piping must be
air tight to prevent air from pocketing at the
top of the piping, stopping flow.
2. The boiler MUST be filled and ready to
operate before proceeding. Follow the boiler
manual to fill the boiler.
3. Follow the procedure below to fill the boiler-
to-water heater piping. See Figure 16.
Step 1 Close isolation valves 5 and 6 to isolate
the boiler.
Step 2 Close valve 3 and open valve 4. Con-
nect a cold water supply hose to
valve 3. Connect a hose from valve 4
to a drain able location.
Step 3 Close valve 10. Open valve 7.
Step 4 Open valve 3. Water will flow through
valve 7 and out through valve 4 to
drain. Open valve 11. Let water run
until all air has been removed from
the line through valve 11. Close valve
11. Close valve 4. Then close valve 3.
Step 5 Close valve 7. Then open valve 10.
Step 6 Open valve 3. Water will flow through
the circulator line, the water heater
coil and the return piping, then out
through valve 4 to drain. Let water run
until all air has been removed from the
line. Close valve 4. Then close valve 3.
Remove hoses.
Step 7 Follow the instructions in “Water
heater filling and start-up, page 26,
to fill the domestic water side of the
water heater.
Step 8 Open valve 7 about ¼ turn for an
initial setting.
Step 9 Open isolation valves 5 and 6. Make
sure the boiler water level is correct
per the boiler manual.
Step 10 Start the boiler per instructions given
in the boiler manual. Allow boiler to
begin steaming.
Step 11 Start the DHW circulator. Watch the
temperature at gauge 8. Adjust valve 7
until gauge 8 reads about 180°F with
system at steady operation.
Step 12 Continue checking under varying
DHW demand conditions to ensure
system will operate as required.
Part number 633-500-230/0918
20
AQUA PRO
TM
INDIRECT-FIRED WATER HEATERSProduct Manual
Electrical shock hazard — Can cause
severe personal injury, death or substantial
property damage. Disconnect power before
installing and / or servicing.
Wiring requirements
1. All wiring must be a minimum of 18 gauge and installed
in accordance with:
U.S.A. — National Electrical Code, ANSI/NFPA 70
- latest edition and any other national, state or local
code requirements having jurisdiction.
Canada — CSA C22.1 Canadian Electrical Code Part
1 - latest edition and any other national, provincial and
local code requirements having jurisdiction.
2. If original wire as supplied with appliance must be re-
placed, Type 90° C or its equivalent must be used.
3. Refer to control component instructions packed with
boiler for application information.
4. An optional service switch may be installed in water heater
electrical circuit. This switch would only shut off the water
heater, not the home heating system. Do not shut off water
heater if there is a chance of freezing.
5. All electrical contacts are shown with no power applied
— off-the-shelf condition.
Circulators
Size priority relay for total amp draw of all circulators.
Zone Valves
Size transformer for maximum load of all zone valves.
Wiring to the water heater
Field connections to the water heater control are for 24VAC
only, connecting to the two-pole terminal block shown in
Figure 17.
Wiring options
1. This manual shows wiring only for use of typical Circula-
tor Zone Controller or Zone Valve Zone Controller, wire
per manufacturer’s instructions.
2. Other wiring methods may be acceptable and are left to
the installer.
Use domestic priority
1. When possible, set controls to provide domestic priority
— that is, on a call for domestic water the control switches
from space heating to DHW only.
2. Domestic priority ensures the fastest possible response to
the DHW call for heat.
3. The smaller the water heater, the greater the need for
rapid response.
Figure 17 Wiring the control “General Connection”
Figure 18 Wiring tank control to the AquaBalance
®
boiler control.
Boiler-side wiring and controls
1. Connect a 24VAC power source to the “24VAC Input” termi-
nals.
2. Connect the “Output Contacts to the zone or boiler control’s
domestic water input.
3. Eliminate stray voltage in the power circuit by connecting the
24VAC power to AC2 and grounding AC1. Confirm correct con-
nections by verifying 24VAC between AC1 and AC2.
The “Output Contacts are isolated contacts that close
when the control calls for heat.
9$&
,QSXW
7R=RQH
RU
%RLOHU
&RQWURO

7RWDQN
WHPSHUDWXUHVHQVRU
9$&,1387
$& $&
287387&217$&76
9$&
,QSXW
7R
%RLOHU
&RQWURO
$FX7HPS
:0
FRQWURO
$TXD%DODQFHERLOHU
&RQWUROWHUPLQDOV


7HUPLQDOV
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

Weil-McLain 633500203 User manual

Category
Water heaters & boilers
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI