  • Hello! I am an AI chatbot trained to assist you with the hussman TY4ECRC-6 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
/CHINO
TY4 ECSQ (ENTYCE)
ISLAND CASE
Installation
&Operation
Manual
REV. 1023
TY4ECSQ
TY4ECRC
(ENTYCE)
ISLAND CASE
INSTALLATION & OPERATION GUIDE
Table of Contents
Warning 3
General Information 5
Cut and Plan Views 6
Installation 7
Plumbing 9
Refrigeration Piping 10
Specications 11
Electrical 13
Wiring Diagrams Index 13
Wiring Diagrams 14
Entyce Joint Checklist 24
User Information 25
Troubleshooting 26
Appendix 28
2
1. Do Not Push, Pull, Adjust, or Manipulate the TY case by any glass component.
• Doing so will result in severe damage to such components
• Glass breakage may result in serious injury
2. Never stand on the TYTop, Deck, or any Shelves for any reason.
• Misusing these surfaces as steps will result in damage to the case
• Misusing these surfaces as steps may result in serious injury to the user
• These surfaces are intended for the storage and merchandising of food products
• Use a ladder or designed structure to work above the case (Do not lean on case)
3. DO NOT remove shelves. WARNING! will adversely impact case performance
when merchandising.
NOT A
MERCHANDISING
AREA
3
36”
36”
36”
36”
AISLE 1 AISLE 2
SALAD BAROPEN BREAD STAND SLUSH
MACHINE
Warning
Minimum Clearances for TY cases are to be followed as instructed for proper placement inside store locations.
- A minimum clearance of 15' from door opening must be maintained in order for case to remain in optimal performance.
- Side clearances are to be a minimum of 8' when placed next to a solid wall.
- Height clearance measured from oor follows as a minimum of 10' vertically.
- Minimum of 36" clearance if near an open aisle is required for optimal Air Curtain cycling.
(Assumed 8' clearance from solid wall)
SERVICE DELI
8’
10’
The folowing gure demonstrates
proper clearances for
Entyce cases assuming the
surrounding walls are solid to ensure
optimal performance of the cases Air
Curtain.
4
General Information
Case Description:
This Booklet specically covers the
following models:
Entyce TY4
Description: Entyce A multi deck air curtain SelfService case designed to display prepackaged Deli, Bakery,
Meat, Seafood, and/or Beverage products.
Shipping Damage: All equipment should be thoroughly examined for shipping damage before and during
unloading. This equipment has been carefully inspected at our factory and the carrier has assumed
responsibility for safe arrival. If damaged, either apparent or concealed, claim must be made to the carrier.
Apparent Loss or Damage: If there is an obvious loss or damage, it must be noted on the freight bill or express
receipt and signed by the carrier’s agent; otherwise, carrier may refuse claim. The carrier will supply necessary
claim forms.
Concealed Loss or Damage: When loss or damage is not apparent until after all equipment is uncrated, a claim
for concealed damage is made. Make request in writing to carrier for inspection within 15 days, and retain all
packaging. The carrier will supply inspection report and required claim forms.
Location/Store Conditions: The refrigerated merchandisers have been designed for use only in air conditioned
stores where temperature and humidity are maintained at 80°F and 55% relative humidity or 75°F and 55%
relative humidity. DO NOT allow air conditioning, electric fans, ovens, open doors or windows (etc.) to create
air currents around the merchandiser, as this will impair its correct operation.
Shortages: Check your shipment for any possible shortages of material. If a shortage should exist and is found
to be the responsibility of Hussmann Chino, notify Hussmann Chino. If such a shortage involves the carrier,
notify the carrier immediately, and request an inspection. Hussmann Chino will acknowledge shortages within
ten days from receipt of equipment.
Hussmann Chino Product Control: The serial number and shipping date of all equipment has been recorded
in Hussmann’s les for warranty and replacement part purposes. All correspondence pertaining to warranty
or parts ordering must include the serial number of each piece of equipment involved, in order to provide the
customer with the correct parts.
Keep this booklet with the case at all times for future reference.
This equipment is to be installed
to comply with the applicable
NEC, Federal, State , and Local
Plumbing and Construction
Code ha ving jurisdiction.
Keep this booklet with the case at all times for future reference.
/CHINO
A publication of HUSSMANN®Chino
13770 Ramona Avenue Chino, California 91710
(909) 628-8942 FAX
(909) 590-4910
(800) 395-9229
5
Cut and Plan Views
Drain 1
Drain 2
C
L715/8
(1819)
base panel
Refrig
31/2 (11/2 for 8' only )
for 8' only )
open
(11/2 for 8' only )31/2
(11/2 for 8' only )31/2
Elec
open
31/2 (11/2 for 8' only )
71/8
(181)
71/8
(181)
45/8 (
(117)
45/8
(117)
(for 8' only )
TY4ECRC-6I - Island
“D1”
“D2”
“A”
“B”
“B”
“A” 96 120 144 168 192
(2438) (3048) (3658) (4267) (4877)
“B” 121/2 121/2 155/8 155/8 155/8
(318) (318) (387) (387) (387)
713/4
(1822)
953/4
(2432)
“D1” N/A N/A 713/4
(1822)
713/4
(1822)
713/4
(1822)
667/8*883/8*473/4
(1699) (2245) (1213)
*same for 2nd drain l oca tio n
“D2”
36(914)
471/2
(1206)
711/2
(1816)
12
(305)
355/8
(905)
12(305)
14(356)
16(406)
15
(381)
571/2
(1461)
17
(432)
27(686)
383/8
(975)
Plex Product Stop
-optional
Angled Shelf Insert
-optional
6
Lift Zones
Installation
TY Lifting and Transport Instructions
1. The Entyce can be lifted by a forklift at typical
lifting points.
Lift Zones
Insert Forks
Underneath
Deck
WARNING
Improper placement of forks may damage
drainage piping. Use a spotter when placing
forks. Make sure that piping will not be dam-
aged. Use J-Bars or Jacks if forks cannot be
used safely
2. Ensure lower body panels are removed be-
fore lifting with a forklift. Serious damage will
occur if the body panels are not removed.
3. Make sure that fork spacing and width will not
damage drain or come in contact with piping,
or electrical lines
4. Be sure that the forks are long enough to
support beyond the center of the case but not
damage near components. Check for proper
balance before moving. A minimum fork
length of 36" is recommended for 68" wide
cases
5. The TY merchandiser can be raised at one
end underneath the deck with a forklift to al-
low the placement of rollers or dollies.
6. Evenly support the entire base structure on
rollers or dollies before attempting to move.
Each Base Leg must have its own dollie to
properly support the case.
Lifting Points are typical and dependent upon
size of case and refrigeration application, drain-
age congurations will call for altercations in
Lifting Zones.
Below are the following drainage congurations
and lifting should be altered to the expected
model.
Center Drain
Drain 1
Drain 2
C
L715/8
(1819)
base pan el
Refrig
31/2 (1 8' )
(for 8' only )
(11/2 for 8' only )32/1 open
)(11/2 for 8' ) 3
only 1/2
1/2 for only
Elec
open
31/2 (11/2 for 8' only
71/8
(181)
71/8
(181)
45/8
(117)
45/8
(117)
(for 8' only )
TY4ECRC-6I - Island
“D2”
“D1”
“A”
“B”
“B”
“A” 96 120 144 168 192
(2438) (3048) (3658) (4267) (4877)
“B” 121/2 121/2 155/8 155/8 155/8
(318) (318) (387) (387) (387)
713/4 713/4 953/4
(1822) (1822) (2432)
“D1” N/A N/A
“D2” 667/8*883/8*473/4 713/4 713/4
(1699) (2245) (1213) (1822) (1822)
*same fo r 2nd drai n l o c a t i o n
715/8
(1819)
73
(1854)
96
(2438)
48
(1219)
Optional
End
Panel
11/8
(29)
Refrig
Drain
Drain
CL
71/8
(181)
31/2 (89)
15 5/8
(387)
31/2 (89)
open
15 5/8
(387)
63/4
(171)
open
31/2 (89)
31/2 (89)
Elect
48
(1219)
ba se panel
TY4ECRC-6X8C - Center
Elec
Drain
C
L715/8
(1819)
73
(1854)
Refrig
71/8
(181)
31/2 (89)
15 5/8
(387)
31/2 (89)
11/8
(29)
Optional
End
Panel
15 5/8
(387)
ba s e panel
*consult Cadblock for 2nd drain location
Drain
“B”
TY4ECRC-6E - Flat End
144
(3658)
120
(3048)
96
(2438)
37
(940)
49 727/8*
(1245) (1851)
“B”
“A”
“A”
7
Installation
Location
The refrigerated merchandisers have been designed for
use only in air conditioned stores where temperature and
humidity are maintained at or 75°F and 55% relative humidity
or below 80°F and 55% relative humidity. DO NOT allow air
conditioning, electric fans, ovens, open doors or windows
(etc.) to create air currents around the merchandiser, as this
will impair its correct operation.
Leveling
A LEVEL CASE IS NECESSARY TO INSURE PROPER
OPERATION AND WATER DRAINAGE. Note: A. To avoid
removing concrete ooring, begin lineup leveling from the highest
point of the store oor.
Uncrating the Stand
Place the fixture as close to its permanent position as
possible. Detach the walls from each other and remove from
the skid. Unstrap the case from the skid. The xture can now
be lifted off the crate skid. Lift only at base of stand!
Exterior Loading
Do NOT walk on top of the merchandisers or damage to
the merchandisers and serious personal injury could occur.
They are not structurally designed to support excessive
external loading such as the weight of a person. Do not place
heavy objects on the case.
It is the contractor’s responsibility to install
case(s) according to local construction and
health codes.
8
Plumbing
Waste Outlet and P-TRAP
The waste outlet is located in front and center of the case
on both sides which allows for suitable access to each drain
allowing drip piping to be run lengthwise under the xture.
P-traps must be installed at the base of all refrigerated
cases. The 1 ½” P-TRAP and threaded adapter must be
installed to prevent air leakage and insect entrance into the
fixture.
Installing Condensate Drain
Poorly or improperly installed condensate drains can
seriously restrict the operation of this refrigerator, and result
in costly maintenance and product losses. Please follow the
recommendations listed below when installing condensate
drains to insure a proper installation:
1. Never use pipe for condensate drains smaller than the
nominal diameter of the pipe or P-TRAP supplied with
the case.
2. When connecting condensate drains, the P-TRAP
must be used as part of the condensate drain to
prevent air leakage or insect entrance. Store
plumbing system oor drains should be at least 14" off
the center of the case to allow use of the P-TRAP pipe
section. Never use two water seals in series in any one
line. Double P-TRAPS in series will cause a lock and
prevent draining.
3. Always provide as much down hill slope (“fall”) as pos-
sible; 1/8" per foot is the preferred minimum. PVC pipe,
when used, must be supported to maintain the 1/8"
pitch and to prevent warping.
4. Avoid long runs of condensate drains. Long runs make
it impossible to provide the “fall” necessary for good
drainage.
5. Provide a suitable air break between the ood rim of
the oor drain and outlet of condensate drain. 1" is
ideal.
6. Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should
be insulated with a nonabsorbent insulation mate-
rial such as Armstrong’s Armaex.
b. Where condensate drains are located in dead air
spaces (between refrigerators or between a refrig-
erator and a wall), provide means to prevent freez-
ing. The water seal should be insulated to prevent
condensation.
Center Drain
TY4ECRC-6I - Island
Drain 1
Drain 2
C
L715/8
(1819)
base panel
Refrig
3(11/2 for 8'
1/2 only
31/2 (11/2 for 8' only )
for 8' only )
open
(11/2 for 8' only )31/2
only
)(11/2 for 8' ) 31/2
Elec
open
71/8
(181)
71/8
(181)
45/8 (
(117)
45/8
(117)
(for 8' only )
“D2”
“D1”
“A”
Note: Cases are typical, length of cases
vary
“B”
“B”
144 168 192
(3658) (4267) (4877)
“B”
“A” 96 120
(2438) (3048)
155/8
(387)
155/8
(387)
155/8
(387)
713/4
(1822)
953/4
(2432)
121/2 121/2
(318) (318)
N/A N/A
“D1” 713/4
(1822)
713/4
(1822)
713/4
(1822)
667/8*88
3/8*473/4
(1699) (2245) (1213)
*same for 2nd drain location
“D2”
9
Refrigeration Piping
The standard refrigerant will be R-404 unless otherwise
specied on the customer order. Check the serial plate on
the case for information. Refrigeration outlet access and
the refrigeration components for the Entyce are situated on
the left hand side near the centerline of the case to deliver
optimal access which provides for easy installation and
maintenance purposes without the probability of damaging
any components.
Refrigeration Lines
Liquid Suction
3/8" O.D. 5/8" O.D.
Refrigerant lines should be sized as shown on the refrigeration
legend furnished by the store.
Oil traps must be installed at the base of all suction line
vertical risers on refrigerated cases.
Pressure drop can rob the system of capacity. To keep the
pressure drop to a minimum, keep refrigerant line run as
short as possible, using the minimum number of elbows.
Where elbows are required, use long radius elbows only. All
refrigeration components are located underneath the left
hand side case deck pans.
10
Specications
11
Specications
12
Electrical
Field Wiring and Serial Plate Amperage
Field Wiring must be sized for component amperes printed
on the serial plate. Actual ampere draw may be less
than specied. Field wiring from the refrigeration control
panel to the merchandisers is required for refrigeration
thermostats. Case amperes are listed on the wiring
diagram, but always check the serial plate.
BEFORE SERVICING
ALWAYS DISCONNECT ELECTRICAL
POWER AT THE MAIN DISCONNECT
WHEN SERVICING OR REPLACING ANY
ELECTRICAL COMPONENT.
This includes (but not limited to) Fans, Heaters
Thermostats, and Lights.
CASE MUST BE GROUNDED
NOTE: Refer to label afxed to case to determine the actual
conguration as checked in the “TYPE INSTALLED” boxes.
Standard lighting for all refrigerated models will be full length
LED Lights located within the case at the top.
Wiring Diagrams Index
TY4 ECRC-5X7I-R 7’ 3144548
TY4ECRC-6X8I-R ULTRA LED TOP, 10",12",16" 8' 3123818
TY4ECRC-6X8C-R HO CANOPY LIGHTS 8' 3064025
TY4ECRC-6X8E-R W/LEDGE LIGHTS ALSO 8' 3160163
TY4ECRC-6X10E-R W/10",12",14" & LEDGE LT 10' 3067655
TY4ECRC-6X12E-R 10", 12", 14" SHELVES 12' 3058530
TY4ECRC-6X12I-R 10",12" & 14" SHELVES 12' 3080512
TY4ECRC-6X14I-R 14' 3047157
TY4ECRC-6X16I-R 16' 3043948
TY4ECRC-6X18I-R W/LEDGE LIGHTS ALSO 18' 3160164
13
NOTES:
1. PRINTED DOCUMENT REQUIRED SETTING: ALL COLORS BLACK & WHITE
2. CASE & ANY REMOVABLE PANEL WITH ELECTRICAL PARTS MUST BE GROUNDED.
3. WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
CNO_1.0 WIIRE DIAGRAM SIZE C
3144548 A
DIAGRAM-
TY4ECRC- 5X7I-R
P/N REV
R
RED = RD
BLACK = BK
BLUE = BL
YELLOW =
YL GRAY =
GY
WHITE = WT
GREEN = GN
BROWN = BN
ORANGE =
OR VIOLET =
VT
UL COLOR CODES / ABBREVIATIONS
DO NOT SCALE DRAWING
SHEET 1 OF 1
FACTORY 14GA WIRE
FACTORY 10GA WIRE
FIELD WIRE
REV BY CHKD BYREV
A
ECN
ECN-COD-0012732
DATE
2-25-21
REVISION HISTORY
REVISION DESCRIPTION
RELEASED TO PRODUCTION CB CB
APPR BY
CB
CIRCUIT #1
LOADING
120V
3.5L1
TOGGLE SWITCH
125-01-0307
LN
~120 VAC - 60 Hz.
BUNDLE
ORANGE
MCA= 1.29A
MOP= 15A
LIGHT CIRCUIT= 1.03A 111.6W
BLK#14
WHT#14
RED +
BLUE -
LED DRIVER
BUNDLE
BROWN
LN
M M
~120 VAC - 60 Hz.
MCA= 2.3A
MOP= 15A
BLK#14
WHT#14
EVAPORATOR FANS
12W 0.3A @ 120VAC (10)
(6) 0477655
M
RED +
BLUE -
LED DRIVER
CIRCUI T#2
~120 VAC - 1Ø -60 Hz
CIRCUIT #2
NOTE:
CASE MUST BE
GROUNDED
LOADING
120
V
15.0L1
L2
L3
GFCI DUPLEX
125-01-3178
BLK # 14
WHT # 14
TAG PURPLE
HEATER CIRCUITL1 N
ANTI-SWEAT HEATER
30W .27A@ 120 VAC
(2) 0495006
~120 VAC - 60 Hz.
MCA= 0.68A
MOP= 15A
T-STAT
225-01-0707
BUNDLE
WHITE/BLACK
SOLENOID VALVE
.14A @ 120VAC
LN
~120 VAC - 60 Hz.
MCA= .20A
MOP= 15A
M M M
OPTIONAL
WG BK
SOLENOID
.14A @ 120VAC
T-STAT
BUNDLE
WHITE/BLACK
NL1
~120 VAC - 60 Hz
BLACK #14
WHITE #14
SENSOR
BLK/WHT STRIPE#14
WHITE #14
LN
120
LC
LNO
OPTIONAL
18" LED LIGHT ULTRA
18" LED LIGHT ULTRA
3' LED LIGHT ULTRA
3' LED LIGHT ULTRA
3' LED LIGHT ULTRA
3' LED LIGHT ULTRA
CANOPY LIGHTS
18" LED LIGHT
18" LED LIGHT
18" LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
2' LED LIGHT
2' LED LIGHT
2' LED LIGHT
2' LED LIGHT
18" LED LIGHT
NOTES:
1. PRINTED DOCUMENT REQUIRED SETTING: ALL COLORS BLACK & WHITE
2. CASE & ANY REMOVABLE PANEL WITH ELECTRICAL PARTS MUST BE GROUNDED.
3. WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
CNO_1.0 WIIRE DIAGRAM SIZE C
3123818 A
DIAGRAM-
TY4ECRC- 6X8I-R
W/10",12" &
16" SHELVES
P/N REV
R
RED = RD
BLACK = BK
BLUE = BL
YELLOW =
YL GRAY =
GY
WHITE = WT
GREEN = GN
BROWN = BN
ORANGE =
OR VIOLET =
VT
UL COLOR CODES / ABBREVIATIONS
DO NOT SCALE DRAWING
SHEET 1 OF 1
FACTORY 14GA WIRE
FACTORY 10GA WIRE
FIELD WIRE
REV BY CHKD BYREV
A
ECN
ECN-CAP-0021402
DATE
4-30-20
REVISION HISTORY
REVISION DESCRIPTION
RELEASED TO PRODUCTION CB CB
APPR BY
CB
CIRCUIT
#1
LOADING
120V
3.5L1
BUNDLE
ORANGE
EVAPORATOR FAN
12W 0.30A @ 120VAC
(6) 0477655
LIGHT SWITCH
125-01-0307
L1 N
BLK#14
WHT#14
LED DRIVER
RED +
BLUE -
MM
BUNDLE
BROWN
MM
LED DRIVER
RED +
BLUE -
L1 N
L1 N
L1 N
120V/60/1
MCA-2.3A
MOP-15.0A 120V/60/1
MCA-1.43A
MOP-15.0A
120V/60/1
MCA-0.68A
MOP-15.0A
T-STAT
225-01-0707
BUNDLE
WHITE/BLACK
SOLENOID VALVE
.14A @ 120VAC
LN
~120 VAC - 60 Hz.
MCA= .20A
MOP= 15A
OPTIONAL
BLK # 14
WHT # 14
TAG PURPLE
HEATER CIRCUIT
ANTI-SWEAT HEATER
120 VAC
(2) 0495006 30W, .27A
M
M
3' L.E.D. LIGHT-ULTRA
2' L.E.D. LIGHT
CANOPY LIGHTS ES-CANOPY
3' L.E.D. LIGHT-ULTRA
3' L.E.D. LIGHT-ULTRA
3' L.E.D. LIGHT-ULTRA
18" L.E.D. LIGHT-ULTRA
18" L.E.D. LIGHT-ULTRA
10" SHELVES LIGHTS
LIGHT CIRCUIT
1.14A 123.2W @ 120V
12" SHELVES LIGHTS
16" SHELVES LIGHTS
1' L.E.D. LIGHT
2' L.E.D. LIGHT
1' L.E.D. LIGHT
1' L.E.D. LIGHT
1' L.E.D. LIGHT
18" L.E.D. LIGHT
18" L.E.D. LIGHT
1' L.E.D. LIGHT
2' L.E.D. LIGHT
2' L.E.D. LIGHT
18" L.E.D. LIGHT
18" L.E.D. LIGHT
1' L.E.D. LIGHT
1' L.E.D. LIGHT
1' L.E.D. LIGHT
1' L.E.D. LIGHT
2' L.E.D. LIGHT
2' L.E.D. LIGHT
1' L.E.D. LIGHT
HUSSMANN_GDF_1.1 SHEET SIZE D
THIRD
ANGL
E
PROJECTION
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES.
APPROVED BY - CRAIG BOOREY
TOLERANCES ARE:
DECIMALS .XX
u
.03, .XXX
u
.010 ANGLES
u
2
v
MATERIAL - N/A
DATE DRAWN - 5-25-18
DRAWN BY -CRAIG BOOREY
REVIEWED BY -CRAIG BOOREY
ECN-CAP-0012696
REF -
3064025
DIAGRAM-
TY4ECRC- 6X8C-R
REV ECN DATE
A ECN-CAP-0012696 2018/05/25
REV BY
CB
CHKD BY
CB
APPR BY
CB
REVISION HISTORY
REVISION DESCRIPTION
RELEASED TO PRODUCTION
NOTES:
CASE MUST BE GROUNDED
WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
A
SHEET 1 OF 1
CIRCUIT
#1
LOADING
120V
4.7L1
BUNDLE
ORANGE
EVAPORATOR FAN
12W 0.30A @ 120VAC (8)
0477655
LIGHT SWITCH
125-01-0307
L1 N
BLK#14
WHT#14
LED DRIVER
RED +
BLUE -
LIGHT CIRCUIT
1.60A 172.4W @ 120V
MMM
BUNDLE
BROWN
MMM
LED DRIVER
RED +
BLUE -
L1 N
4' L.E.D. LIGHT
L1 N
L1 N
120V/60/1
MCA-3.0A
MOP-15.0A 120V/60/1
MCA-2.0A
MOP-15.0A
120V/60/1
MCA-0.83A
MOP-15.0A
T-STAT
225-01-0707
BUNDLE
WHITE/BLACK
SOLENOID VALVE
.14A @ 120VAC
LN
~120 VAC - 60 Hz.
MCA= .20A
MOP= 15A
OPTIONAL
BLK # 14
WHT # 14
TAG PURPLE
HEATER CIRCUIT
ANTI-SWEAT HEATER
120 VAC
(2) 0495007 40W, .33A
M
M
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
LED DRIVER
RED +
BLUE -
4' L.E.D. LIGHT HO
4' L.E.D. LIGHT HO
LED DRIVER
RED +
BLUE -
4' L.E.D. LIGHT HO
4' L.E.D. LIGHT HO
CANOPY LIGHTS HIGH OUTPUT
NOTES:
1. PRINTED DOCUMENT REQUIRED SETTING: ALL COLORS BLACK & WHITE
2. CASE & ANY REMOVABLE PANEL WITH ELECTRICAL PARTS MUST BE GROUNDED.
3. WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
CNO_1.0 WIIRE DIAGRAM SIZE C
3160163 A
DIAGRAM-
TY4ECRC- 6X8E-R
P/N REV
R
RED = RD
BLACK = BK
BLUE = BL
YELLOW =
YL GRAY =
GY
WHITE = WT
GREEN = GN
BROWN = BN
ORANGE =
OR VIOLET =
VT
UL COLOR CODES / ABBREVIATIONS
DO NOT SCALE DRAWING
SHEET 1 OF 1
FACTORY 14GA WIRE
FACTORY 10GA WIRE
FIELD WIRE
BLACK = MBK
BLUE = MBL
BROWN = MBR
DARK BLUE =
MDB GREEN = MG
LIGHT BLUE = MLB
MAROON =
MMR ORANGE =
MO PINK = MPI
PURPLE = MP
RED = MR
YELLOW = MYL
WIRE MARKER COLORS/ABBREVIATIONS
REV BY CHKD BYREV
A
ECN
ECN-COD-0015266
DATE
1-13-22
REVISION HISTORY
REVISION DESCRIPTION
RELEASED TO PRODUCTION CB CB
APPR BY
CB
LIGHT SWITCH
125-01-0307 BUNDLE
BROWN
MBR
LN
LN
~120 VAC - 60 Hz.
BUNDLE
ORANGE
MO
MCA= 2.2A
MOP= 15A
LIGHT CIRCUIT= 1.8A 190.5W
M M
BLK#14
WHT#14
~120 VAC - 60 Hz.
MCA= 1.5A
MOP= 15A
BLK#14
WHT#14
EVAPORATOR FANS
PER COIL
12W 0.3A @ 120VAC
(4) 0477655
M M
RED +
BLK -
LED DRIVER
CIRCUI T#2
~120 VAC - 1Ø -60 Hz
NOTE:
CASE MUST BE
GROUNDED
15.0L1
L2
L3
CIRCUIT #2
LOADING
120 V
GFCI DUPLEX
125-01-3178
ANTI-SWEAT HEATER
120 VAC
(1) 0495006 30W .27A
(1) 0495007 40W .36A
L1 N
BLK # 14
WHT # 14
~120 VAC - 50/60
Hz MCA= 0.79A
MOP= 15A
T-STAT
225-01-0707
BUNDLE
WHITE/BLACK
LIQUID LINE SOLENOID
.14A @ 120VAC
LN
~120 VAC - 60 Hz.
MCA= 0.18A
MOP= 15A
OPTIONAL
CANOPY LIGHTS
RED +
BLK -
LED DRIVER
OPTIONAL LEDGE
LIGHTS
RED +
BLK -
LED DRIVER
WGBK
LIGHT SWITCH
125-01-0307
4' LED LIGHT-ULT
4' LED LIGHT-ULT
4' LED LIGHT-ULT
4' LED LIGHT-ULT
5' LED LIGHT-ULT
3' LED LIGHT-ULT
3' LED LIGHT-ULT
3' LED LIGHT-ULT
3' LED LIGHT-ULT
3' LED LIGHT-ULT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
18" LED LIGHT
1' LED LIGHT
1' LED LIGHT
18" LED LIGHT
BUNDLE
PURPLE
MP
BUNDLE
BROWN
MBR
LN
M M
~120 VAC - 60 Hz.
MCA= 1.5A
MOP= 15A
BLK#14
WHT#14
EVAPORATOR FANS
PER COIL
12W 0.3A @ 120VAC
(4) 0477655
M M
5' LED LIGHT
5' LED LIGHT
5' LED LIGHT
5' LED LIGHT
5' LED LIGHT
5' LED LIGHT
LOADING
120 V
4.8L1
CIRCUIT #1
HUSSMANN_GDF_1.1 SHEET SIZE D
THIRD
ANGL
E
PROJECTION
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES.
APPROVED BY - CRAIG BOOREY
TOLERANCES ARE:
DECIMALS .XX
u
.03, .XXX
u
.010 ANGLES
u
2
v
MATERIAL - N/A
DATE DRAWN -7-2-18
DRAWN BY -CRAIG BOOREY
REVIEWED BY -CRAIG BOOREY
ECN-CAP-0013270
REF -
3067655
DIAGRAM-
TY4ECRC- 6X10E-R
REV
A
B
ECN
ECN-CAP-0013270
ECN-COD-0015266
DATE
2018/07/02
2022/01/13
REV BY
CB
CB
CHKD BY
CB
CB
APPR BY
CB
CB
REVISION HISTORY
REVISION DESCRIPTION
RELEASED TO PRODUCTION
REVISED LIGHTS
NOTES:
CASE MUST BE GROUNDED
WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
B
SHEET 1 OF 1
LIGHT SWITCH
125-01-0307 BUNDLE
BROWN
LN
LN
~120 VAC - 60 Hz.
BUNDLE
ORANGE
MCA= 2.74A
MOP= 15A
LIGHT CIRCUIT= 2.2A 237W
M M
BLK#14
WHT#14
~120 VAC - 60 Hz.
MCA= 1.5A
MOP= 15A
BLK#14
WHT#14
EVAPORATOR FANS
PER COIL
12W 0.3A @ 120VAC
(4) 0477655
M M
RED +
BLUE -
BUNDLE
BROWN
LN
M M
~120 VAC - 60 Hz.
MCA= 1.5A
MOP= 15A
BLK#14
WHT#14
EVAPORATOR FANS
PER COIL
12W 0.3A @ 120VAC
(4) 0477655
M M
RED +
BLUE -
LED DRIVER
CIRCUI T#2
~120 VAC - 1Ø -60 Hz
NOTE:
CASE MUST BE
GROUNDED
15.0L1
L2
L3
CIRCUIT #2
LOADING
120 V
GFCI DUPLEX
125-01-3178
ANTI-SWEAT HEATER
120 VAC
(1) 0495006 30W .27A
(1) 0495008 60W .54A
L1 N
BLK # 14
WHT # 14
~120 VAC - 50/60
Hz MCA= 1.01A
MOP= 15A
T-STAT
225-01-0707
BUNDLE
WHITE/BLACK
LIQUID LINE SOLENOID
.14A @ 120VAC
LN
~120 VAC - 60 Hz.
MCA= 0.18A
MOP= 15A
OPTIONAL
LED DRIVER
RED +
BLUE -
LED DRIVER
CANOPY LIGHTS
4' LED LIGHT-HO
4' LED LIGHT-HO
3' LED LIGHT-HO
4' LED LIGHT-HO
4' LED LIGHT-HO
RED +
BLUE -
LED DRIVER
5' LED LIGHT
5' LED LIGHT
5' LED LIGHT
5' LED LIGHT
5' LED LIGHT
OPTIONAL LEDGE
LIGHTS
RED +
BLUE -
LED DRIVER
WGBK
4' LED LIGHT
4' LED LIGHT
3' LED LIGHT
3' LED LIGHT
3' LED LIGHT
4' LED LIGHT
4' LED LIGHT
4' LED LIGHT
3' LED LIGHT
3' LED LIGHT
3' LED LIGHT
4' LED LIGHT
1' LED LIGHT
1' LED LIGHT
18" LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
18" LED LIGHT
10", 12", 14" SHELVES
LIGHT SWITCH
125-01-0307
LOADING
120 V
5.5L1
CIRCUIT #1
HUSSMANN_GDF_1.1 SHEET SIZE D
THIRD
ANGL
E
PROJECTION
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES.
APPROVED BY - CRAIG BOOREY
TOLERANCES ARE:
DECIMALS .XX
u
.03, .XXX
u
.010 ANGLES
u
2
v
ECN-CAP-0011915
REF -
3058530
DIAGRAM-
TY4ECRC- 6X12E-R
REV
A
B
ECN
ECN-CAP-0011915
ECN-COD-0013667
DATE
2018/03/19
2021/06/04
REV BY
CB
CB
CHKD BY
CB
CB
APPR BY
CB
CB
NOTES:
CASE MUST BE GROUNDED
WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
B
SHEET 1 OF 1
CIRCUIT
#1
LOADING
120V
6.1L1
LIGHT SWITCH
125-01-0307
BUNDLE
BROWN
L1 N
LN
~120 VAC - 60 Hz.
BUNDLE
ORANGE
MCA= 2.69A
MOP= 15A
LIGHT CIRCUIT= 2.15A 232.5W
M M
BLK#14
WHT#14
~120 VAC - 60 Hz.
MCA= 1.87A
MOP= 15A
BLK#14
WHT#14
EVAPORATOR FANS
PER COIL
12W 0.3A @ 120VAC
(5) 0477655
MATERIAL - N/A
DATE DRAWN -3-19-18
DRAWN BY -CRAIG BOOREY
REVIEWED BY -CRAIG BOOREY
M M M
RED +
BLUE -
LED DRIVER
BUNDLE
BROWN
LN
M M
~120 VAC - 60 Hz.
MCA= 1.87A
MOP= 15A
BLK#14
WHT#14
EVAPORATOR FANS
PER COIL
12W 0.3A @ 120VAC
(5) 0477655
M M M
CIRCUI T#2
~120 VAC - 1Ø -60 Hz
CIRCUIT #2
NOTE: CASE MUST BE
GROUNDED
LOADING
120
V15.0L1
L2
L3
GFCI DUPLEX
125-01-3178
WGBK
ANTI-SWEAT HEATER
50W .42A@ 120 VAC
0497590
L1 N
ANTI-SWEAT HEATER
60W .55A@ 120 VAC
0495008
~120 VAC - 60 Hz.
MCA= 1.21A
MOP= 15A
RED +
BLUE -
LED DRIVER
T-STAT
225-01-0707
BUNDLE
WHITE/BLACK
SOLENOID VALVE
.14A @ 120VAC
LN
~120 VAC - 60 Hz.
MCA= 0.18A
MOP= 15A
REVISION HISTORY
REVISION DESCRIPTION
RELEASED TO PRODUCTION
ADDED OPTIONAL LEDGE LIGHTS
OPTIONAL
BLK#14
WHT#14
RED +
BLUE -
LED DRIVER
5' LED LIGHT
5' LED LIGHT
1' LED LIGHT
4' LED LIGHT
4' LED LIGHT
CANOPY LIGHTS
RED +
BLUE -
LED DRIVER 5' LED LIGHT
5' LED LIGHT
18" LED LIGHT
18" LED LIGHT
1' LED LIGHT
4' LED LIGHT
4' LED LIGHT
6' LED LIGHT
6' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
14" SHELF LIGHTS
6' LED LIGHT
6' LED LIGHT
4' LED LIGHT
4' LED LIGHT
1' LED LIGHT
6' LED LIGHT
6' LED LIGHT
10" SHELF LIGHTS
12" SHELF LIGHTS
LIGHT SWITCH
125-01-0307
L1 N
~120 VAC - 60 Hz.
BUNDLE
ORANGE
MCA= 2.69A
MOP= 15A
BLK#14
WHT#14
RED +
BLUE -
LED DRIVER
OPTIONAL LEDGE LIGHTS
6' LED LIGHT
6' LED LIGHT
6' LED LIGHT
6' LED LIGHT
5' LED LIGHT
HUSSMANN_GDF_1.1 SHEET SIZE D
THIRD
ANGL
E
PROJECTION
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES.
APPROVED BY - CRAIG BOOREY
TOLERANCES ARE:
DECIMALS .XX
u
.03, .XXX
u
.010 ANGLES
u
2
v
MATERIAL - N/A
DATE DRAWN - 11-13-18
DRAWN BY -CRAIG BOOREY
REVIEWED BY -CRAIG BOOREY
ECN-CAP-0014946
REF -
3080512
DIAGRAM-
TY4ECRC- 6X12I-R
10",12",14" SHELVES
REV
A
B
ECN
ECN-CAP-0014946
ECN-COD-0011343
DATE
2018/11/13
2020/08/14
REV BY
CB
CB
CHKD BY
CB
CB
APPR BY
CB
CB
REVISION HISTORY
REVISION DESCRIPTION
RELEASED TO PRODUCTION
REVISED TO ULTRA CANOPY LIGHTS
NOTES:
CASE MUST BE GROUNDED
WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
B
SHEET 1 OF 1
CIRCUIT
#1
LOADING
120V
6.5L1
LIGHT SWITCH
125-01-0307 BUNDLE
BROWN
L1 N
LN
~120 VAC - 60 Hz.
BUNDLE
ORANGE
MCA= 3.26A
MOP= 15A
LIGHT CIRCUIT= 2.61A 281.4W
M M
BLK#14
WHT#14
~120 VAC - 60 Hz.
MCA= 1.87A
MOP= 15A
BLK#14
WHT#14
EVAPORATOR FANS
PER COIL
12W 0.3A @ 120VAC (6)
0477655
M M M
RED +
BLUE -
LED DRIVER
BUNDLE
BROWN
LN
M M
~120 VAC - 60 Hz.
MCA= 1.87A
MOP= 15A
BLK#14
WHT#14
EVAPORATOR FANS
PER COIL
12W 0.3A @ 120VAC (6)
0477655
M M M
CIRCUI T#2
~120 VAC - 1Ø -60 Hz
NOTE: CASE MUST BE
GROUNDED
15.0L1
L2
L3
CIRCUIT #2
LOADING
120 V
GFCI DUPLEX
125-01-3178
WGBK
ANTI-SWEAT HEATER
50W .42A@ 120 VAC
(2) 0497590
L1 N
~120 VAC - 60 Hz.
MCA= 1.15A
MOP= 15A
RED +
BLUE -
LED DRIVER
1.5' LED LIGHT
1.5' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
6' LED LIGHT
6' LED LIGHT
6' LED LIGHT
6' LED LIGHT
6' LED LIGHT
6' LED LIGHT
1.5' LED LIGHT
1.5' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
1' LED LIGHT
RED +
BLUE -
LED DRIVER
RED +
BLUE -
LED DRIVER
CANOPY LIGHTS
T-STAT
(1) 225-01-0707
OPTIONAL
TAG
WHITE/BLACK
L1
N
~120 VAC - 60 Hz
BLK # 14
WHT # 14
SOLENOID VALVE
.14A @ 120VAC
RED +
BLUE -
LED DRIVER
RED +
BLUE -
LED DRIVER
6' LED LIGHT
6' LED LIGHT
5' LED LIGHT
OPTIONAL LEDGE LIGHTS
6' LED LIGHT
6' LED LIGHT
5' LED LIGHT
LIGHT SWITCH
125-01-0325
L1 N
~120 VAC - 60 Hz.
BUNDLE
ORANGE
MCA= 0.93A
MOP= 15A
BLK#14
WHT#14
BUNDLE
PURPLE
4' LED LIGHT ULTRA
4' LED LIGHT ULTRA
3' LED LIGHT ULTRA
4' LED LIGHT ULTRA
4' LED LIGHT ULTRA
3' LED LIGHT ULTRA
/