DVM S
AM✴✴✴MXVAFC Series
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
2
Contents
Safety precautions ....................................................................................................... 3
Preparing for installation ................................................................................................. 6
Selecting installation location ........................................................................................... 16
Space requirement for installation ...................................................................................... 17
Accessories ............................................................................................................. 19
Base construction and installation of the outdoor unit ................................................................... 20
Installing the wind/snow prevention duct ............................................................................... 25
Refrigerant pipe installation ............................................................................................. 27
Electrical wiring work ................................................................................................... 50
Air tightness test and vacuum drying ................................................................................... 60
Pipe insulation .......................................................................................................... 62
Charging additional refrigerant ......................................................................................... 66
Basic segment display .................................................................................................. 68
Setting outdoor unit option switch and key function .................................................................... 68
Things to check after completing the installation ........................................................................ 78
Inspection and test operation ........................................................................................... 80
Automatic refrigerant amount detection function ....................................................................... 84
3
ENGLISH
Safety precautions
Please follow the following safety information for safety of the installer and the user.
DVM S air conditioner uses R-410A refrigerant.
t When using R-410A, moisture or foreign substances may aect the performance and reliability of the product.
Safety precautions must be obeyed when installing the refrigerant pipe.
t The designed maximum pressure of the system is 4.1MPa(594.6 psi) and therefore select appropriate material and
thickness according to the regulations.
t R-410A is a quasi-azeotrope of two refrigerants and it has to be charged in liquid phase when lling the refrigerant.
(If you charge vapor refrigerant, it may change the blend of the refrigerant and cause product malfunction.)
You must connect the indoor units for R-410A refrigerant. Refer to product catalog to nd out the models names
for connectable indoor units. (If you connect the indoor units that are not designed for R-410A, it cannot operated
normally.)
After completing the installation and trial operation, explain to the user how to use and maintain the product. Also, hand
over this installation manual so that it can be stored by the user.
Manufacturer is not responsible for the incidents occurred by improper installation. Installer is responsible for any
installation related claims from the user occurred by neglecting warnings and cautions stated in this manual. (Installer
will be responsible for any service charges that may occur)
Generally, system air conditioners should not be relocated after installation. But when it has to be relocated for inevitable
reasons, please contact Samsungs qualied dealers for system air conditioners.
WARNING
t Hazards or unsafe practices that may result in severe personal injury or death.
CAUTION
t Hazards or unsafe practices that may result in minor personal injury (to installer/user) or
property damage.
SEVERE WARNING SIGNS
Consult qualied installer or dealer for installation.
f When installation is done by unqualied person, problems such as water leakage, electric shock or re may occur.
Installation work must be done properly according to this installation manual.
f When installation is not done properly, it may cause water leakage, electric shock or re.
When installing the unit in a small room, take measure to keep the refrigerant concentration from exceeding allowable
safety limits in case of refrigerant leakage. Consult the dealer for precautionary measure before the installation.
f When refrigerant leaks and exceed dangerous concentration level, it may cause suocation accidents.
If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problem may occur and it
may cause injury.
Use the supplied accessories, specied components and tools for the installation.
f Do not use the pipe and the installation product used for the R-22 refrigerant.
f Failure to use the specied components can cause product fall down, water leakage, electrical shock, and re. (The pipe
and are components used for R-22 refrigerant must not be used)
Install the outdoor unit on a hard and even place that can support its weight.
f If the place cannot support its weight, the outdoor unit may fall down and it may cause injury.
4
Safety precautions
Check the following before installation and service work.
f Before welding, remove dangerous and inammable things that may cause an explosion and re around the work.
f Before welding, remove the refrigerant from inside the pipe or the product.
- If you perform welding while refrigerant is in the pipe, it may increase the pressure of the refrigerant and cause the pipe
to burst. If the pipe bursts or explodes, it may cause severe injury to the installer.
f When welding, use the nitrogen gas to eliminate oxidation inside the pipe.
Do not modify the product on your own.
f Potential risk of electric shock, re, product failure or injury.
Fix the outdoor unit securely on foundation to resist strong wind or earthquake.
f If the outdoor unit is not properly xed, it turns over and accidents may occur.
Electric work must be done by qualied persons, complying the national wiring regulations and installed according to
the instruction stated in the installation manual with leased circuit.
f Capacity shortage on the leased circuit and improper installation may cause electric shock or re.
Make sure to perform grounding work.
f Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone grounding. Improper grounding
could cause electric shock.
Wiring must be connected with the designated wires and it must be xed securely so that it does not apply any external
force to the connection part of the terminals.
f If connection for xation is not properly done, it may cause heat generation or re.
Neatly arrange the wires in the electrical parts to make sure that electrical cover is closed securely without any gaps.
f If the cover is not properly closed, heat may generate on the electrical terminal and cause electric shock or re.
Exclusive circuit breaker (MCCB, ELB) must be installed to the power supply.
f When overcurrent or current leakage occurs with no circuit breaker installed, power will not be cut-o and it may cause
electric shock or re.
f Do not use damaged parts. It may cause re or electric shock.
You must cut-o the power before you work on, or adjust any power supply part for product installation, maintenance,
repair or any other services.
f There is risk of electric shock.
f Even when the power is o, it is dangerous when you come in contact with inverter PCB, fan PCB since high pressure DC
voltage is charged to those parts.
f When replacing/repairing the PCB, cut-o the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
If the refrigerant gas leaks during the installation, you should ventilate the room.
f When the refrigerant gas gets in contact with ammable substance, it may generate toxic gas.
Gas leakage must be checked after installation is completed.
f When the refrigerant gas gets in contact with ammable substance, it may generate toxic gas.
You can get a frostbite if you get in contact with the leaked refrigerant gas.
Supply power to the product during winter time since the product will operate in protection mode itself when the
temperature decrease below 0°C(32°F).
f If you cut-o the power, compressor protection mode cannot be operated and may cause damage to the product.
5
ENGLISH
CAUTION SIGNS
Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so that water
drains out smoothly. If not, pipe may freeze or bursts during winter time and cause damage to the product or water
leakage.
f When the draining work is not done properly, water leak may occur and cause property damage.
Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m(4.92ft) away from the
electric appliances and install it at least 2m(6.56ft) away from the lightning conductor.
f Noise may be generated from the electronic devices, depending on the status of the electric wave.
Install the outdoor unit within the angle stated in the table, according to the height of the building.
f Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
f You must use the appropriate pipes according to the standard since the pressure of the refrigerant is very high.
f Make sure that the pipes does not get any weaker by welding it too much.
f Make sure to install the product away from childrens’ reach. (Sharp parts of the heat exchanger is may cause personal
injury and when parts of the product gets damage, it may decrease product’s performance.)
Lighting rod
Protective angle: 25˚~55˚
Height of the building Protection control
20m(65.6 ft) or less 55˚
40m(131.2 ft) or less 35˚
60m(196.9 ft) or less 25˚
Install the indoor unit away from lighting apparatus that uses ballast stabilizer.
f If you use the wireless remote control, it may not operate normally due to ballast stabilizer.
Do not install the product in following places.
f Place where outdoor unit’s noise and warm air may disturb neighbors. (It may cause property loss.)
f Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.)
f The place where there is mineral oil or arsenic acid.
- Those parts may get damaged due to burned resin and cause water leakage or product may fall.
- The eciency of the heat exchanger may reduce or product may break.
f The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
- The copper pipe or connection pipe may corrode and refrigerant may leak.
f The place where there is a machine that generates electromagnetic waves.
- The air conditioner may not operate normally due to problems in control system.
f The place where there is a danger of combustible gas leakage or place where thinner or gasoline is handled.
- (There is risk of re or explosion.)
f The place with carbon ber or ammable dust.
f The place near seashore or hot spring where there is risk of outdoor unit corrosion.
6
Safety precautions
Changes in DVM S (inverter) compare to conventional models that has to noted when installing
f For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor units. (To not use
T-joint)
f You cannot operate normally if you do not complete the trial operation through outdoor unit key mode. You must use
KEY MODE to run trial operation.
f DVM S air conditioner uses R-410A refrigerant.
f Check the compatibility of other products such as indoor unit, EEV kits etc. which will be connected to DVM S.
f Make sure to note that outdoor unit combination is dierent from DVM PLUS III and IV.
f The length of maximum piping, level dierence, the quantity of connectable indoor units, the installation at the outdoor
joints and the outdoor unit combinations are dierent from the conventional models.
f If the pipe length is over 2m(6.56ft) between outdoor units, make traps to prevent oil stagnation. Oil stagnation may
occur when outdoor unit at the end of module stops while other outdoor units are still in operation.
Preparing for installation
Outdoor unit classication
Classication Small type Large type
Appearance
Models AM080/100/120MXVAFC AM140/160/180/200MXVAFC
Packaging material disposition
t Safely store or dispose the packaging materials.
- Sharp metals such as nails or wooden material packaging that may break into pieces become a cause for
personal injury.
- Make sure to store or dispose the vinyl type packaging material to keep it out of reach of children. Children
may put them over their face, which is very dangerous since it may lead them to suocation.
CAUTION
7
ENGLISH
Outdoor unit combination
f Make sure to use an indoor unit that is compatible with DVM S.
f Indoor units can be connected within the range indicated in following table.
f If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling capacity of the
indoor unit may decrease.
f Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM✴✴✴✴NQDCH) can be connected.
t Installation combination must be complied when composing outdoor unit combination.
CAUTION
Standard type (AM✴✴✴MXVAFC Series) (Cooling only)
Model name for combination AM080MXVAFC AM100MXVAFC AM120MXVAFC AM140MXVAFC AM160MXVAFC
Number of individual outdoor units 11111
Combined outdoor unit
AM080MXVAFC 1
AM100MXVAFC 1
AM120MXVAFC 1
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC
AM200MXVAFC
Nominal capacity
Cooling (kW) 22.4 28.0 33.6 40.0 45.0
Cooling (Btu/h) 76 400 95 500 114 600 136 500 153 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 11.2 14.0 16.8 20.0 22.5
Minimum (Btu/h) 38 200 47 800 57 300 68 200 76 800
Maximum (kW) 29.1 36.4 43.7 52.0 58.5
Maximum (Btu/h) 99 400 124 200 149 000 177 400 199 600
Maximum number of connectable indoor
units
14 18 21 26 29
8
Preparing for installation
Model name for combination AM180MXVAFC AM200MXVAFC AM220MXVAFC AM240MXVAFC AM260MXVAFC
Number of individual outdoor units 11222
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 121
AM140MXVAFC 1
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 1
Nominal capacity
Cooling (kW) 50.4 56.0 61.6 67.2 73.6
Cooling (Btu/h) 172 000 191 100 210 100 229 200 251 100
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 25.2 28.0 30.8 33.6 36.8
Minimum (Btu/h) 86 000 95 500 105 100 114 600 125 500
Maximum (kW) 65.5 72.8 80.1 87.4 95.7
Maximum (Btu/h) 223 600 248 400 273 200 298 000 326 400
Maximum number of connectable indoor
units
32 36 40 43 47
Model name for combination AM280MXVAFC AM300MXVAFC AM320MXVAFC AM340MXVAFC AM360MXVAFC
Number of individual outdoor units 22222
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 111
AM140MXVAFC 1
AM160MXVAFC 11
AM180MXVAFC 1
AM200MXVAFC 111
Nominal capacity
Cooling (kW) 78.6 84.0 89.6 96.0 101.0
Cooling (Btu/h) 268 100 286 600 305 700 327 600 344 600
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 39.3 42.0 44.8 48.0 50.5
Minimum (Btu/h) 134 100 143 300 152 800 163 700 172 300
Maximum (kW) 102.2 109.2 116.5 124.8 131.3
Maximum (Btu/h) 348 600 372 600 397 400 422 300 448 000
Maximum number of connectable indoor
units
51 54 58 61 64
9
ENGLISH
Model name for combination AM380MXVAFC AM400MXVAFC AM420MXVAFC AM440MXVAFC AM460MXVAFC
Number of individual outdoor units 22333
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 121
AM140MXVAFC 1
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 12111
Nominal capacity
Cooling (kW) 106.4 112.0 117.6 123.2 129.6
Cooling (Btu/h) 363 100 382 200 401 200 420 300 442 200
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 53.2 56.0 58.8 61.6 64.8
Minimum (Btu/h) 181 500 191 000 200 600 210 100 221 000
Maximum (kW) 138.3 145.6 152.9 160.2 168.5
Maximum (Btu/h) 472 000 496 800 521 600 546 400 574 800
Maximum number of connectable indoor
units
64 64 64 64 64
Model name for combination
AM480MXVAFC AM500MXVAFC AM520MXVAFC AM540MXVAFC AM560MXVAFC
Number of individual outdoor units 33333
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 111
AM140MXVAFC 1
AM160MXVAFC 11
AM180MXVAFC 1
AM200MXVAFC 11222
Nominal capacity
Cooling (kW) 134.6 140.0 145.6 152.0 157.0
Cooling (Btu/h) 459 200 477 700 496 800 518 700 535 700
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 67.3 70.0 72.8 76.0 78.5
Minimum (Btu/h) 229 600 238 800 248 300 259 200 267 800
Maximum (kW) 175.0 182.0 189.3 197.6 204.1
Maximum (Btu/h) 597 000 621 000 645 800 674 200 696 400
Maximum number of connectable indoor
units
64 64 64 64 64
10
Preparing for installation
Model name for combination
AM580MXVAFC AM600MXVAFC AM620MXVAFC AM640MXVAFC AM660MXVAFC
Number of individual outdoor units 33444
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 121
AM140MXVAFC 1
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 23222
Nominal capacity
Cooling (kW) 162.4 168.0 173.6 179.2 185.6
Cooling (Btu/h) 554 200 573 300 592 300 611 400 633 300
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 81.2 84.0 86.8 89.6 92.8
Minimum (Btu/h) 277 000 286 500 666 500 305 600 316 500
Maximum (kW) 211.1 218.4 225.7 233.0 241.3
Maximum (Btu/h) 720 400 745 200 770 000 794 800 823 200
Maximum number of connectable indoor
units
64 64 64 64 64
Model name for combination AM680MXVAFC AM700MXVAFC AM720MXVAFC AM740MXVAFC AM760MXVAFC
Number of individual outdoor units 44444
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 111
AM140MXVAFC 1
AM160MXVAFC 11
AM180MXVAFC 1
AM200MXVAFC 22333
Nominal capacity
Cooling (kW) 190.6 196.0 201.6 208.0 213.0
Cooling (Btu/h) 650 300 668 800 687 900 709 800 726 800
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 95.3 98.0 100.8 104.0 106.5
Minimum (Btu/h) 325 100 334 300 343 800 354 700 363 300
Maximum (kW) 247.8 254.8 262.1 270.4 276.9
Maximum (Btu/h) 845 400 869 400 894 200 922 600 944 800
Maximum number of connectable indoor
units
64 64 64 64 64
11
ENGLISH
Model name for combination
AM780MXVAFC AM800MXVAFC
Number of individual outdoor units 44
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC
AM140MXVAFC
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 34
Nominal capacity
Cooling (kW) 218.4 224.0
Cooling (Btu/h) 745 300 764 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 109.2 112.0
Minimum (Btu/h) 372 500 382 000
Maximum (kW) 283.9 291.2
Maximum (Btu/h) 968 800 993 600
Maximum number of connectable indoor units 64 64
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79 E201 error will occur.
t Installation combination must be complied when composing outdoor unit combination.
CAUTION
12
Preparing for installation
Moving the outdoor unit
f Select the moving path in advance.
f Be sure that moving path can support weight of the outdoor unit.
f Do not slant the product more than 30˚ when carrying it. (Do not lay the product down in sideways.)
f Surface of the heat exchanger is sharp. Be careful not to get injured while moving the product.
t You must use certain part of the product when moving the product.
CAUTION
When moving with a crane
f Fasten the wire rope as shown in the gure.
f To protect damage or scratches, insert a piece of cloth between the
outdoor unit and the wire rope.
Wire rope
Holes for wire rope to go
through
When moving with a forklift
f Carefully insert the forklift forks into the forklift holes at the bottom of
the outdoor unit.
f Be careful with the forklift from damaging the product.
Forklift
Forklift holes
Holes for forklift forks
to go through
When moving the product without wooden pallet and the crane is not available for use
f Connect a wire rope to the outdoor unit as you would move it with a
crane.
f Hang the wire rope to the forklift fork to move the outdoor unit.
Wire rope
Forklift
13
ENGLISH
Installation Guide for Corrosion Resistance Model (AM✴✴✴MXVAFCAAZ)
The Corrosion Resistance model enhances the material and coating processing, but it is not 100% perfect for corrosion. Therefore, it
is necessary to increase the corrosion prevention eect through the following installation planning and maintenance.
1. Do not install the product in a place where it is directly exposed to sea water and sea breeze.
- Make sure to install the product behind a structure (such as building) that can block see breeze.
- Even when it is inevitable to install the product in seashore, make sure that product is not directly exposed to sea
breeze by installing a wind board.
- Pay attention to installation direction. (The degree of corrosion when installed parallel to the shoreline diers from that
when installed at right angles.)
2. Consider that the salinity particles clinging to the external panels should be suciently washed out in rainwater.
3. Because the residual water at the bottom of the outdoor unit signicantly promotes corrosion, make sure that the slope
does not disturb drainage.
- Keep the oor level so that rain does not accumulate.
- Be careful not to block the drain hole due to foreign substance
4. When product is installed in seashore, periodically clean it with water to remove attached salinity.
5. Make sure to install the product in a place that provides smooth water drainage. Especially, ensure that the base part has
good drainage.
6. If the product is damaged during installation or maintenance, make sure to repair it.
7. Check the condition of the product regularly.
- Apply anti-corrosive coating, such as grease or wax, for preventing water absorption at the time of installation and refer
to ‘Maintenance of R-Pro according to installation condition (For Anti-corrosion (Corrosion Resistance) Model)’.
- When the product is to be shut down for a long period of time, such as o-peak hours, take appropriate measures like
covering the product.
14
Preparing for installation
Installation Guide for Special anti-corrosion treatment
f Special anti-corrosion treatment is required when installed in following conditions. SAMSUNG ELECTRONICS CO., LTD.
recommends to use R-Pro for anti-corrosion spray.
f Maintenance of R-Pro according to installation condition (For Anti-corrosion (Corrosion Resistance) Model)
Environment
Installation conditions
Anti-Corrosion Eect from
Installation
Anti corrosion Eect by
Maintenance
Seashore
Seashore within 500m
Direct exposure
With Anti-corrosion coating
: 1 year from installation
* Check 6 months later from installation
t After Corrosion Protection period
(1 year)
Cleaning & Spray R-Pro
: 1 year extended
Seashore within 500m
Building / Protection Wall
With Anti-corrosion coating
: 4 years from installation
Without Anti-corrosion coating
: 2 years from installation
* Check 6 months later from installation
t After Corrosion Protection period
Cleaning & Spray R-Pro (With
initial coating)
: 4 years extended
Cleaning & Spray R-Pro
(without initial coating)
: 2 years extended
Seashore within 500m~2km
With Anti-corrosion coating
: 4 years from installation
Without Anti-corrosion coating
: 2 years from installation
* Check 6 months later from installation
t After Corrosion Protection period
Cleaning & Spray R-Pro (With
initial coating)
: 4 years extended
Cleaning & Spray R-Pro
(Without initial coating)
: 2 years extended
Seashore
+
corrosive gas area
Seashore within 500m
Corrosive gas area
With Anti-corrosion coating
: 1 year from installation
* Check 6 months later from installation
t After Corrosion Protection period
(1 year)
Cleaning & Spray R-Pro
: 1 year extended
Seashore within 500m~2km
Corrosive gas area
corrosive gas area
The place where corrosive
gas generates
The installation site marked dotted line box absolutely need anti-corrosion coating to prevent corrosion of equipment.
All installation site need inspection every year after initial installation complete.
15
ENGLISH
f Maintenance of R-Pro according to installation condition (For general model)
Environment Installation conditions
Anti-Corrosion Eect from
Installation
Anti corrosion Eect by
Maintenance
Seashore
Seashore within 500m
Building / Protection Wall
With Anti-corrosion coating
: 4 years from installation
Without Anti-corrosion coating
: 2 years from installation
* Check 6 months later from installation
t After Corrosion Protection period
Cleaning & Spray R-Pro (With
initial coating)
: 4 years extended
Cleaning & Spray R-Pro
(without initial coating)
: 2 years extended
Seashore within 500m~2km
With Anti-corrosion coating
: 4 years from installation
Without Anti-corrosion coating
: 2 years from installation
* Check 6 months later from installation
t After Corrosion Protection period
Cleaning & Spray R-Pro (With
initial coating)
: 4 years extended
Cleaning & Spray R-Pro
(Without initial coating)
: 2 years extended
Seashore
+
corrosive gas area
Seashore within 500m
Corrosive gas area
With Anti-corrosion coating
: 1 year from installation
* Check 6 months later from installation
t After Corrosion Protection period
(1 year)
Cleaning & Spray R-Pro
: 1 year extended
Seashore within 500m~2km
Corrosive gas area
corrosive gas area
The place where corrosive
gas generates
The installation site marked dotted line box absolutely need anti-corrosion coating to prevent corrosion of equipment.
All installation site need inspection every year after initial installation complete.
16
Selecting installation location
Decide the installation location, with the consideration of the following conditions, under user’s approval.
f Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in residential areas,
keep the operation hours in mind.)
f Place where structure can bear the weight and vibration of the outdoor unit.
f Place with at surface where rainwater does not settle or leak.
f Place where it is not exposed to strong wind.
f Well ventilated place with sucient service place for repairs and maintenance. (Discharge duct can be purchased separately)
f Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable distance.
f Place where there is no risk of inammable gas leakage.
f Place where there is no direct inuence of snow or rain.
f Do not install the product in a place where it will be directly exposed to sea breeze.
- Consult an installation expert (or company) since you will need to take extra anti-corrosion measures if you need to
install the product in a place where it can be exposed to direct sea breeze. (You have to remove dusts and salinity on
the heat exchanger and apply designated rust inhibitor more than once a year.)
Sea
Sea breeze
Outdoor
unit
Outdoor
unit
Caution when installing the product in seashore
- When installing the product in seashore, make sure to install it behind a structure (such as building) that can block the
sea breeze or install protection wall around the outdoor unit.
- Make sure to install the product in a place where it allows smooth drainage.
Protection wall should be constructed with a solid material that
can block the sea breeze and the height and width of the wall
should be 1.5 times larger than the size of the outdoor unit. (You
must secure more than 700mm(28inch) of space between the
protection wall and the outdoor unit for air circulation.)
Corrosion registance model (AM✴✴✴MXVAFCAAZ) can be
installed in front of a structure, without a protection wall.
However, it must be installed where the water containing salt
does not contact the outdoor unit directly.
As we cannot guarantee that the corrosion resistance model can
prevent corrosion completely, we recommend that you install
a protection wall, or install the outdoor unit behind a structure
(such as building) that can block see breeze.
Sea
Sea breeze
Outdoor
unit
Protection wall
Outdoor unit
Sea
Sea breeze
Outdoor
unit
17
ENGLISH
t System air conditioner may cause static noise when listening to AM stations. Therefore, select an installation
location for indoor unit where electrical wiring can be done while keeping certain distance from a radio,
computer and stereo equipment.
- Especially, keep the unit at least 3m(9.84inch) away from the electrical equipment in an area with weak electromagnetic
waves and put the main power cable and communication cables in a separately installed protection tube.
- Make sure that there is no equipment that generates electromagnetic waves. If not electromagnetic waves may
cause problem to the control systems which may lead to air conditioner malfunction. (Example: Remote control
sensor of the indoor unit may not receive the signal very well, due to ballast stabilizer of the lighting equipment.)
t In regions with heavy snowfall, make sure to install the outdoor unit where there is no concerns of direct
snowfall on the outdoor unit. Also, build higher base support so that accumulated snow does not block the air
inlet or the heat exchanger.
t R-410A refrigerant is a safe, nontoxic and nonammable refrigerant. However, if the place holds any concerns for
exceeding dangerous level of refrigerant concentration in case of refrigerant leakage, extra ventilation system is required.
t When you install the outdoor unit in a high places such as roof, install fence or guardrail around it. When there is
no fence or guardrail, service person could fall.
t Do not install the product in places where corrosive gases such as sulfur oxides, ammonia, and sulfurous gas are
produced. (e.g. Toilet outlet, ventilation opening, sewage works, dyeing complex, cattle shed, sulfuric hot spring,
nuclear power plant, ship etc.) When installing the product in those places, contact an installation specialty store as
the copper pipe and brazing part will need additional corrosion proof or anti-rust additive to prevent corrosion.
t Make sure to keep any inammable materials (such as wooden materials, oil etc.) around the outdoor unit. When
there's re, those inammable material will easily catch the re and may pass it on to the product.
t Depending on the condition of power supply, unstable power or voltage any cause malfunction of the parts or
control system. (At the ship or places using power supply from electric generator...etc)
CAUTION
Space requirement for installation
f Space requirement was decided based on following conditions; Cooling mode, outdoor temperature of 35°C (95°F).
Larger space is required if the outdoor temperature is higher than 35°C (95°F) or if the place is heated easily by quantity of
solar radiation.
f When you secure installation space, consider path for people and the direction of the wind.
f Secure installation space as shown in the below illustration, considering ventilation and the service space.
f If the installation space is narrow, installer or other worker may get injured during work and may also cause problem to
the product.
f If you install multiple number of outdoor units in one space, make sure to secure enough ventilation space if theres any walls
around the product that may disturb the air ow. If enough ventilation space is not secured, product may malfunction.
f You may install the outdoor units with 20mm (0.78 inch) of space between the product, but product’s performance may
decrease depending on the installation environment.
Single installation
Unit: mm (inch)
Height of the wall is
unlimited
Over 100 (4)
[S2]
Over 500 (20)
[S1]
Over 100 (4) Over 100 (4)
Front
side
Over 100 (4)
Over 300 (12)
<Case 1> <Case 2>
Front side
18
Space requirement for installation
Module installation
<Case 3>
Over 500
(20)
Over 500
(20)
Over 600
(24)
Over 100 (4) Over 100 (4)
Over 100 (4)
Over 100 (4)
Over 100 (4) Over 100 (4) Over 100 (4)
Over 100 (4)
Front side
Front side
<Case 1> <Case 2>
Over 200 (8)
Over 100 (4)
Over 300 (12)
[S2]
Over 500
(S1)
Over 100 (4)
Over 100 (4)
Over 100 (4)
Over 300 (12)
Over 400
(16)
Over 400
(16)
Height of
the wall is
unlimited
Front
side
Front side
For <Case 1> or <Case 3>
t Height of the wall on the front side should not be higher than 1500mm (60 inch).
t Height of the wall on the air inlet side should not be higher than 500mm (20 inch).
t Height of the wall on the side is not limited.
t If the height of the wall exceeds by certain value (h1, h2), additional clearance [(h1)/2, (h2)/2 : Half of the exceeded
distance] should be added to the service space (S1, S2).
1500 (60) h1
500 (20) h2
Front side
Air inlet side
Unit: mm (inch)
S1+h1/2 S2+h2/2
19
ENGLISH
Accessories
Accessories
f You must keep following accessories until the installation is nished.
f Hand over the installation manual to the customer after nishing the installation.
Installation manual (1)
Optional accessories
f Following optional accessories are needed for connecting pipes between the indoor and outdoor units.
Classication Model Name
Specication
MBH KW
Y-Joint
MXJ-YA1509M 51 below 15.0 and below
MXJ-YA2512M Over 51~136 and below Over 15.0 ~40.0 and below
MXJ-YA2812M Over 136~154 and below Over 40.0 ~45.0 and below
MXJ-YA2815M Over 154~240 and below Over 45.0 ~70.3 and below
MXJ-YA3419M Over 240~336 and below Over 70.3 ~98.4 and below
MXJ-YA4119M Over 336~461 and below Over 98.4 ~135.2 and below
MXJ-YA4422M Over 461 Over 135.2
Distribution header
MXJ-HA2512M 154 and below (for 4 rooms) 45.0 and below (for 4 rooms)
MXJ-HA3115M
Over 240 ~ 461 and below
(for 8 rooms)
Over 70.3 ~ 135.2 and below
(for 8 rooms)
MXJ-HA3819M Over 240 (for 8 rooms) Over 70.3 (for 8 rooms)
Y-Joint
- Outdoor unit
MXJ-TA3819M 461 and below 135.2 and below
MXJ-TA4422M 478.4 and over 140.2 and over
If you use an indoor unit with no internal EEV(Electric Expansion Valve), you will need an EEV kit.
Only use the genuine accessories listed in above table and do not use imitated accessories.
20
Base construction and installation of the outdoor unit
t Make sure to remove the wooden pallet before installing the outdoor unit. If you do not remove the wooden
pallet, there is risk of re during welding the pipes. If the outdoor unit is installed with wooden pallet on, and
it was used for long period time, wooden palette may break and cause electrical hazard or high pressure may
damage the pipes.
WARNING
Fix an outdoor unit rmly on the base ground with anchor bolts.
Manufacturer is not responsible for the damage occurred by not following the installation standards.
1. Make sure that the height of the base ground is 200mm or higher to protect the outdoor unit from rain water or other
external conditions. Also, install a draining pit around the base ground and connect the drain pipe to the drainage.
2. Considering the vibration and weight of the outdoor unit, strength of the base ground must be strong to prevent noise
and the top surface of it should be at.
3. Base ground should be 1.5 times larger than the bottom of the outdoor unit.
4. Outdoor unit must be xed rmly so that it can withstand the wind speed of 30m/s. If you cannot x the outdoor unit on
the base ground, x it by side or use extra structure.
5. To prevent water from stagnating or freezing, construct a drainage with over 1/50 slope. (Ice may form on the oor in
winter time.)
6. It is necessary to add wire mesh or steel bar during concrete construction for the base ground to prevent damages or
cracks.
7. When installing multiple outdoor units at the same place, construct a H beam or an anti-vibration frame on the base
ground to install the outdoor unit.
8. After installing a H beam or an anti-vibration frame, apply corrosion protection and other necessary coating.
9. When concrete construction for outdoor unit installation is completed, install an anti-vibration pad (t=20mm/0.78 inch or
more) or an anti-vibration frame to prevent vibration of the outdoor unit from transferring to the base ground.
10. Place the outdoor unit on a H beam or an anti-vibration frame and x it with the bolt, nut and washer. (The bearing force
has to be over 3.5kN)
Base ground construction
<When installing on the ground>
Draining pit
Over 200mm (8inch)
<When installing on the roof>
Bottom surface of the base
ground must be horizontally
leveled
Over 200mm (8inch)
Over 200mm (8inch)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86

Samsung AM080MXVAFC/AZ User manual

Category
Power heat guns
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI