Abies TAS400 Series Operating instructions

Category
Thermostats
Type
Operating instructions
Revised Date: 2012/12/20
1
TAS400 Series
Digital Fan-coil Thermostats
OPERATION MANUAL
Front view Back view
# Item Description
1
LCD Display temperature and operation data.
2
MODE button Access to user and engineer menu and for setting confirmation
3
UP button Increase setting or next item
4
DOWN button Decrease setting or previous item
5
Power On/Off button Turn on/off thermostat
6
FAN speed button Toggle to change Fan speed over Auto/Low/Med/Hi
7
Fan icon Indicate Fan continuous on Auto enabled
8
Hot spring icon or Flake icon Hot spring icon for Heating mode; Flake icon for Cooling mode
9
Flow icon Flow icon for Ventilating mode
10-1
Moon Sign Indicate unoccupied status
10-2
Sun Sign Indicate control output ON
11
Auto Automatic fan On-Off with outputs
12-1
Outdoor icon Indicate door/ window open
12-2
Clock 24-hour timer-Off set
13
Sleep Sleep mode enabled
14
Cover screw Screw to tighten back cover with front cover
15
Back plate Plate for mounting on electric box
16
Wiring terminal blocks Terminals for wiring
17
Mounting holes Holes for mounting on electric box
Installation
Mounting on electric box
1. Separate back plate from the controller by loosing the cover screw;
2. Align the mounting holes on the screw holes of the electric box(applicable to 65x65 or US standard box);
3. Fix the back plate on the electric box by tightening the back plate screws. Suggest to use Philips wider “truss head” or
“washer head” #6-32x 3/4”(20mm).
4. DO NOT let the bolt head rise above the wall of mounting holes of back plate. It might cause the short circuit of the
controller.
Revised Date: 2012/12/20
2
Mounting front cover
1. Lock front cover on the back plate by tightening the cover screw underneath with screw driver of Philip electronic
instrument type or similar.
Wiring Example
1. All wires come from electric box must be inserted above the retainers of respective terminal block before
tightening the captive screws;
Fig.1-1 3-wire valve, 2 Pipe Control, 120/230Vac Fig.1-2 3-wire valve, 2 Pipe Control, 24Vac
Fig.1-3 2-wire valve, 2 Pipe Control, 120/230Vac Fig.1-4 2-wire valve, 4 Pipe Control, 120/230Vac
Fig.1-5 2-wire valve, 2 Pipe Control, 24Vac Fig.1-6 2-wire valve, 4 Pipe Control, 24Vac
Revised Date: 2012/12/20
3
Room/
Set-point
Temperature
Temperature
Setting
Mode
Select
Mode
Fan Auto/
Co
s
10
_
+
*
*
_
+
*
FAN
* Back to when no
button was pressed for 10s
Mode
/
/ /
/
Select
Or press
Mode button
F
or 3s
*
+/-0.5
o
C
_
+
FAN
Operation
User Mode Operation
The first tier of operation includes the following settings as Figure 2. To operate:
1. Power switch “ON” or “OFF” to start/ stop the control;
2. At switch “ON”, press any button to start the User Mode operation. Press “MODE” button to switch over
different working modes. Press UP/ DOWN button to increase/ decrease or rotate the values of setting. Press
“FAN” button to toggle over different fan speeds. (Note: If press “MODE” button for more than 3 seconds, the
unit of temperature will toggle to change to ℉ (or ℃).)
3. It will return to current room temperature display with the latest setting if there’s no button pressed for 10
seconds.
# Item Description Remarks
1
Room / Set-point
Temperature
Display current room/ set-point
temperature
Setting “-SP-“ parameter in
Engineer table to choose Current
room or Set-point temperature.
2
Temperature Setting Set the required temperature
3
Mode Select
Select the working mode: Cooling (
)
,
Heating (
)
, or Ventilating (
)
.
If press “MODE” button for more
than 3 seconds, the unit of
temperature will toggle to change to
℉ (or ℃).
4
Fan Auto/ Continuous Fan run with the controlled outputs --
Fan
Auto or run continuously (Fan
Continuous Low/Med/Hi speed.)
Only applied to models with fan auto
control.
Fig. 2 User Mode operation sequence
Revised Date: 2012/12/20
4
Control Action
General:
When cooling/heating control output, a “Sun (
)
” icon will be shown on the LCD and the unit will be
active. I.E., Either Heating or cooling valve is open.
Stage On
Current
Temperature
Cooling
Stage
Differential
SP
Cooling Control for Example
OFF
Stage On
Current
Temperature
Cooling
Stage
Differential
Dead Band
Heating
Stage
Differential
SP
Cooling and Heating Control, Auto Changeover, for Example
OFF
Revised Date: 2012/12/20
5
Special:
1. ESI (Energy Saving Input) Contact status -- When the contact is activated (Room unoccupied), a “Moon
(
)
” icon will be shown on the LCD and the thermostat will change the set-point temperatures of Cooling &
Heating to be ESIC & ESIH (refer to Engineer table for details.). When the contact is deactivated (Room
back to be occupied), the unit will set the set-point values back as normal.
2. If disable local ESI contact detection, the room will become occupied status as default.
3. Door/Window status -- When the status is open, an “Outdoor (
)
” icon will be shown on the LCD and the
unit will be stopped. i.e., Both Heating/cooling valves are closed and Fan is stopped.
4. If disable Door/Window contact detection, the Door/Window will become “close” status as default.
5. There is a 2-minute delay to fan off after stop heating if the lowest fan speed (“LFAn” parameter in Eng.
table) is set as “0(stop)”.
Revised Date: 2012/12/20
6
Engineer Mode Operation
This mode is highly suggested to be operated by trained engineers because it is related to system parameters that
will affect the control results. To operate:
1. Press “Up” and “Down” buttons for over 5 seconds to enter into engineer mode;
2. Press UP or DOWN button to rotate the menu item and press MODE button to enter into the item;
3. Press UP or DOWN button to change the setting and press MODE button to confirm the setting and return to
menu item selection. For no button pressed for 10 seconds, it will go back to menu item selection. The setting
won’t be changed then.
4. To leave Engineer Mode, rotate till “End” and press MODE button or leave the button intact for 10 seconds.
5. Engineer mode operation flow chart:
Fig. 3 Engineer Mode operation sequence
E01
E02
+
End
MODE
E01 Setting
_
+
MODE
_
User Mode
+
_
+
MODE
E02 Setting
MODE
MODE
_
Previous
No button pressed
for 10s under menu
item selection
+
_
+
Press Up/down
for over 5s
Revised Date: 2012/12/20
7
6. Engineer mode menu item descriptions:
°C Type °F Type
Item
Mnemonic
Description
Default
Range Default
Range
Step
1 db Deadband 4.0 0~10.0 7.0 0~18.0 0.5 (°C/°F)
2 ESIC
Unoccupied(ESI) cooling set
point
28.0 25.0~30.0
82.0 77.0~86.0
1.0 (°C/°F)
3 ESIH
Unoccupied(ESI) heating set
point
15.0 10.0~22.0
59.0 50.0~72.0
1.0 (°C/°F)
4 I-t
Integral Time and Output Cycle
Time
90 10~500 90 10-500 10 (Sec.)
5 OP-L Not used
6 SPAn Not used
7 SP-L
Low limit for temperature set
point
10.0 0~50.0 50.0 32.0~122.0
1.0 (°C/°F)
8 SP-H
High limit for temperature set
point
30.0 0~50.0 86.0 32.0~122.0
1.0 (°C/°F)
9 OFSt Current temperature offset 0.0 -10.0~10.0
0.0 -18.0~18.0
0.1 (°C/°F)
10 Pb Proportional band or stage width
2.0 0~10.0 4.0 0~18.0 0.1 (°C/°F)
11 diFF Stage differential 0.5 0.1~1.0 0.9 0.1~1.8 0.1 (°C/°F)
12 LOC
Bit Definition ---
bit 0: MODE button
1: Down buttons
2: Up button
3: FAN SPEED button
4: Power On/Off button
5: Local ESI contact
detection
6: Door/Window detection
7: Not Used
*Bit Value
0: Unlock / enable
1: Lock / disable
Examples:
0- Unlock/enable all
1- Lock MODE
Button
2- Lock Down Button
3- Lock MODE & Down Buttons
4-Lock Up Button
5- Lock MODE & Up Button
8-Lock Fan SPEED Button
15-Lock MODE & Down & Up &
Fan SPEED Buttons
16-Lock Power Button
32-Disable local ESI contact
detection
64-Disable Door/Window
contact detection
127- Lock/disable all
0 0-127 0 0-127 1
To be continued…
Revised Date: 2012/12/20
8
13 ESI ESI contact definition 0 0~1 0 0~1
0: N.O.
1: N.C.
14 rE-C Not used
15 rE-H Not used
16 rS **
Present Temperature is getting
from built-in temperature
Sensor, remote temperature
sensor, or assigned through
Modbus
0 0~2 0 0~2
0: built-in
1: remote
2: assigned
through
Modbus
17 -SP-
Display present value of
temperature or set-point for
Normal Displaying
0 0-1 0 0-1
0: display PV
1: display SP
18 door
Door or Windows contact
definition
0 0~1 0 0~1
0: Close
1: Open
19 LFAn Lowest Fan speed 1 0~3 1 0~3
0: stop
1: low
2: Med.
3: Hi
20 baud Not used
21 Prty Not used
22 id Not used
23 Str Not used
24 tESt Self-Diagnostic
25 rSt
Reset all parameters as factory
defaults
26 End Exit Engineer Mode
Note: “**” When the “rs” parameter is set as 2(present temperature is assigned by Modbus),
if Modbus communication disconnects for more than 3 minutes, the present temperature will
be changed to get from built-in temperature sensor automatically. I.e. The “rs” parameter will
be automatically changed to 0 (present temperature is getting from built-in temperature
sensor).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Abies TAS400 Series Operating instructions

Category
Thermostats
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI