Danfoss NovoCon® S Digital & Hybrid - High Accuracy Actuator Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss NovoCon® S Digital & Hybrid - High Accuracy Actuator Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
NovoCon® S Digital & Hybrid - High Accuracy Actuator
VI.HU.H2.02 | 1© Danfoss | 2016.06
Operating Guide
IP40
IP54
IP54
IP54
*VIHUH202*
Calibration:
Press button until two
LED’s are turned on
DIP switch:
Manual override:
Adjust wheel
Serial number can be removed
from the NovoCon® S and added
to installation drawing.
Device Object
Instance Number
H200 V01
281624
0030471
H200 V01
281624
0030471
H200 V01
281624
0030471
MADE IN SLOVENIA
NovoCon
S Digital & Hybrid
003Z8502
Actuator for AB-QM DN10-32
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA
®
6430 Nordborg, Denmark
Power: 24VAC/DC, 50/60 HZ
Force: 90N. Stroke: 7 mm. Speed: 3-24s/mm
Consumption: 3.9VA running. Standby 0.9W
IP54/40, -10T55
III
Danf
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order pro
vided that such alterations can be made without subsequential changes being necessary eady agreed.
All trademarks in this material are property of the respec
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
73694010 / VI.HU.H2.022 | © Danfoss | DHS-SRMT/SI | 2016.06
NovoCon® S Digital & Hybrid - High Accuracy Actuator
NovoCon® S
BV:0 / 32784
Digital control (default)
or
Analog control
MSV:3 / 32802
Select Valve Type
(defau lt AB-QM DN 15)
AV:0 / 32768
Design Flow Rate
Red
Black
Green
White/
green
Common ground for power and bus signal wire
´+´ non-inverting signal wire
´−´ inverting signal wire
Red
Black
Grey
Blue
Power
Power ground
Analog input
Analog input ground
Digital port
Analog port or
voltage booster
Digital port
BACnet object / Modbus register
DIP Switch
DIP Switches 1 to 7 are used to assign the MAC address manually. Default
setting is Auto MAC addressing for BACnet MS/TP and DIP Switches for
Modbus RTU.
For termination of last unit on the field bus, turn DIP Switch 8 ON.
Dip switch 9 is not used.
Dip switch 10 is used to select between BACnet MS/TP (OFF=Default)
and Modbus RTU (ON).
When the protocol is changed on DIP Switch 10, a power cycle is required.
Power
NovoCon® digital cable
NovoCon® analog cable
Presettings
1 2 3 4 5 6 7 8 9 10
ON
OFF
Safety Note
To avoid injury and damage to persons and devices, it is
absolutely necessary these instructions are carefully read
and observed prior to assembly and commissioning.
Necessary assembly, start-up, and maintenance work
must be performed only by qualified, trained and authorised personnel.
Switch off the power line before wiring the actuator.
Disposal instruction
Always follow the local disposal regulations.
Common ground shall be
used for all devices on the
same network.
Safety Note
Connect via safety isolating transformer.
Galvanic separations shall be provided for segments
crossing buildings.
/