York Vertical, Reduced-Footprint Blower-Coil Units User guide

Type
User guide

York Vertical, Reduced-Footprint Blower-Coil Units are highly adaptable units for various HVAC systems. Their compact design, with vertical orientation and minimized footprint, makes them ideal for areas with space constraints. The units boast galvanized steel construction for durability and longevity, and they are thoroughly inspected and tested prior to shipment to ensure optimal performance upon installation.

These Blower-Coil Units offer exceptional flexibility with a wide range of options, allowing you to customize them to your specific requirements. You can choose from various fan discharge configurations, electric heat with or without single-point power connection, mixing boxes with low-leak dampers, and more.

York Vertical, Reduced-Footprint Blower-Coil Units are highly adaptable units for various HVAC systems. Their compact design, with vertical orientation and minimized footprint, makes them ideal for areas with space constraints. The units boast galvanized steel construction for durability and longevity, and they are thoroughly inspected and tested prior to shipment to ensure optimal performance upon installation.

These Blower-Coil Units offer exceptional flexibility with a wide range of options, allowing you to customize them to your specific requirements. You can choose from various fan discharge configurations, electric heat with or without single-point power connection, mixing boxes with low-leak dampers, and more.

engineering guide
ACB/ACR Blower-Coil Units
Reduced-Footprint, Vertical
2 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
TABLE OF CONTENTS
Features and Benefits ........................................................................................................................................... 3
Construction Features ........................................................................................................................................... 4
Features and Options ............................................................................................................................................ 5
Applications ........................................................................................................................................................... 6
Coil and Filter Data ............................................................................................................................................... 7
Coil Data ................................................................................................................................................................ 8
Electric Data ........................................................................................................................................................ 10
Electric Heat .......................................................................................................................................................... 9
Typical Installations ............................................................................................................................................. 11
Unit Discharge Options ....................................................................................................................................... 12
Fan Performance Curves .................................................................................................................................... 13
Dimensional Data ................................................................................................................................................ 16
Guide Specifications ............................................................................................................................................ 22
NOTES:
• JohnsonControlsoffersWeb-Select
®
,theindustry’sfirstweb-basedratingandselectionprogramforcom-
plete unit, coil and sound selection.
• Seeyourrepresentativeorvisitourwebsiteatwww.JohnsonControls.comformoreinformation.
• Somedrawingsarenotshowninthiscatalog.Drawingsarenotforinstallationpurposes.
• ETLReportNumber510580.
• MEANumberMEA55-98-EappliestoallunitswithanycombinationofchilledwaterorR-22directexpan-
sion coils and either hot water coils, steam coils, or electric heat.
• Alldatahereinissubjecttochangewithoutnotice.
Johnson Controls 3
Reduced-Footprint, Vertical Blower-Coil Units Form: 115.26-EG4 (815)
DESIGN FLEXIBILITY
The Johnson Controls ACB/ACR Belt Drive Blower
Coilsgivemaximumflexibilityforselectionandinstalla-
tionwhereextremespacerestrictionsexist.Theunits
are designed with a slant coil and all front access to
minimize the space used for installation.
Theunitsaredesignedtoexceedthestringentquality
standards of the institutional market, while remaining
cost competitive in the light commercial segment of
the market.
Johnson Controls Belt Drive Blower Coils set the new
standardsforquality,flexibility,andcompetitivepricing.
OPTIONAL COMPONENTS
Theextensivevarietyofstandardoptionsavailableon
theACB/ACR unitsarewhereyou findtheversatility
to fit any HVAC system designer’s needs.
Optionsinclude:Mixingboxeswithstandardlow-leak
dampers,blowthruelectricheatwithorwithoutsingle
point power connection. All electric heat units are listed
withETLasanassemblyandcarrythecETLlabel.
High efficiency motors, starters, disconnects and fusing
mean easier coordination between mechanical and
electrical trades.
Coil options allow for 4 or 6 row cooling coils.
LOWER INSTALLATION COSTS
AllACB/ACRmodelblowercoilsareshippedcomplete-
lyassembled,reducingfieldinstallationtimeandlabor.
All units are thoroughly inspected and tested prior to
shipment, eliminating potential problems at startup.
Motorwiringisbroughttoajunctionboxandterminat-
ed.Thejunctionboxislocatedontheoutsideofthe
unitcasing,reducingelectricalhook-uptime.
A wide variety of fan discharge configurations allow
for increased flexibility and easier installation on the
jobsite, resulting in cost reductions by eliminating
expensiveelbows,etc.
QUALITY PRODUCT
ACB/ACR model blower coils are constructed from
18 gauge galvanized steel. This metal surpasses the
ASTM125hoursaltspraytestforcorrosionandrust.
Insulationis1inchthick,1.6poundpercubicfootscrim
reinforced foil faced insulation, which is glued, pinned
andtapedformaximumpositiveadhesion.Insulation
complieswithUL181,ASTM-C1071,NFPA90Aand
90Bandmeets bacteriological standardASTM-C665
and C1136 for mold, mildew and humidity resistance.
Allunits,withorwithoutElectricHeat,arecETLlisted
and labeled. All wiring is in compliance with NEC,
assuringsafetyandqualityfortheowner.
FEATURES AND BENEFITS
4 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
CONSTRUCTION FEATURES
MODEL ACB, ACR
(ACRshown)
ModelsACBandACRblowercoilshavemanystandardandoptionalfeatureswhichareuniquetotheindustry
(seepage5foracompletelisting).
Full size front access panel
reducesspacerequired
for installation
ACB filter access from front
(notshown)reducesspace
requiredforinstallation
Coilstuboutsextendthrough
unit casing front, reducing space
requiredforinstallation
Productlabelincluding
tagging, airflow and
electrical information
ETLlabel
(notshown)
Forward
curved fan
NEMA1controlenclosure
houses optional starter,
disconnect, fusing, relays,
and other electrical options
Multi-bendconstructionforopti-
mum strength and rigidity
1”ductcollarallowsforquick
field connection of duct work
Heating and cooling coil
stuboutsonoppositesides
Optional stainless steel
drain pan
ACRfilteraccessfromtop
(notshown)reducesspace
requiredforinstallation
Motorwiringin
optional conduit
Scrim reinforced foil faced
insulation, glued and
pinned in place
18 gauge galvanized steel casing
withstanding 125 hour salt spray test
perASTMB-117
Johnson Controls 5
Reduced-Footprint, Vertical Blower-Coil Units Form: 115.26-EG4 (815)
FEATURES AND OPTIONS
STANDARD FEATURES
Construction
• Galvanizedsteelcabinetconstruction,minimum18
gauge
• 1”thick1.6lb/ft
3
scrim reinforced foil faced insula-
tion, glued, taped and pinned in place
• 1”supplyductcollars
• Gasketed,removableaccesspanelsizedforeasy
handling
• IAQgalvanizedsteeldrainpanwith11/8”ODM
copper pipe outlet
• Leftandrighthandarrangement
Fan Assembly
• Forwardcurved(doublewidth,doubleinlet)fans
• Staticallyanddynamicallybalanced
• Solidsteelshafting
• Ballbearingswithaminimumdesignaveragelife(L50)
of 100,000 hours
Fan Motor and Drive
• NEMAdesignODPmotors
• 1750RPMsinglespeed,60Hertz
• Singlephasemotorswithinherentthermalprotection
• Threephasemotors
• Rigidmountadjustablemotorbase
• Standardcrosssection“V-belt”drivewith1.2service
factor
• Adjustablepitchmotorpulley and fixed pitch blower
pulley
Coils
• AHRI410certifiedandlabeled
• 1/2”O.D.seamlesscoppertubes
• Collaredandcorrugatedaluminumfins
• Manualairventplugonallwatercoils
• 300PSIGworkingpressureat200°F
• Steamcoilsratedat15PSIGmaximum
• CopperODMsweatconnections
• 0.016”tubewallonwaterandevaporatorcoils
• 0.025”tubewallonsteamcoils
• High efficiency aluminum fin surface for optimizing
heat transfer, pressure drop and carryover
Filters and Filter Rack
• Topaccessflatfilterrack(ACRonly)
• Frontaccessfilterrack(ACBonly)
• Standardsize2”nominalthrowawayfilters
Electrical
• FanmotorwiredandterminatedtoJ-box
• All units ETL listed in compliance with UL/ANSI
Standard 1995
OPTIONAL FEATURES
Construction
• IAQstainlesssteeldrainpanwith1”MPTgalvanized
pipe outlet
• Externalrubber-in-shearorspringtypevibrationiso-
lators, floor mount
• Fandischargearrangements
• Dischargeplenumw/dbl.deflectiondischargegrille
• Accesspanelwithliftandturnfasteners
• Doublewallaccesspanelw/liftandturnfasteners
• Returnplenumwithremovablepanels(ACBonly)
• Base rails with rigging slots factory assembled and
installed
Fan Motor and Drive
• TEFCmotors •Highefficiencymotors
Coils
• 4and6rowchilledwaterorR22DXcoils
• 1and2rowhotwatercoils
• 1and2rowhotwaterorstandardsteamcoilsindis-
charge coil section only
• Hotwatercoilinpreheatorreheatposition
• Stainlesssteelcoilcasings
• 0.025”tubewallonwaterandevaporatorcoils
• Autoairventsonwatercoils
Filters and Filter Rack
• Sideaccessfilterrack(ACRonly)
• 2”pleatedfilter
• Sparethrowawayorpleatedfilters
Inlet Damper Section (ACR rear return unit)
• Factoryassembledandinstalled
• Heavygaugegalvanizedsteelformedbladedampers
• Low-leakdamperswithextrudedvinylbladesealsand
flexiblemetaljambseals
• Parallelbladeoperation
• Interconnectingdamperlinkage
Electrical
• Motorwiringinconduit
• Motorstarter(contactorwithoverloadforthreephase;
contactorforsinglephase),factoryinstalled(mounted
andwired)
• Doorinterlockingdisconnectswitch(non-fused)(with
mainfusing)
• Handoffautoswitch(HOA)
• Mainfusing
Electric Heat Section
Factory mounted electric heater with single
point powerconnection, ETL listed as anassembly
(seepage9)
6 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
APPLICATIONS
APPLICATION CONSIDERATIONS
ModelACB/ACRBeltDriveBlowerCoilsofferawide
rangeofapplicationflexibility,whilemaintainingasim-
ple, easy to install unit design. These units are intended
to provide comfort cooling and heating within a small
footprint.Theymaybeappliedinmanytypesofbuilding
structuresincludingschools,officebuildings,hospitals,
condominiums, assisted living facilities, apartments or
stores.Applicationscanbeconstantorvariablevolume.
TherearemanyapplicationstheACB/ACRproductcan
beutilized.Someexamplesarelistedbelow.
Constant volume applications:
• Two-pipehydronicsystemforcoolingand/orheating
• Two-pipehydroniccoolingsystemwithelectricheat
• Four-pipesystemwithdedicatedheatingandcooling
coils
• Direct Expansion (DX) split systems with hydronic
heat
• DirectExpansion(DX)splitsystemswithelectricheat
Variable volume applications:
• Two-pipehydronicsystemforcoolingand/orheating.
• Two-pipehydroniccoolingsystemwithelectricheat.
• Four-pipesystemwithdedicatedheatingandcooling
coils.
ACOUSTICS
Controlofnoisewithinbothoccupiedandunoccupied
spaceshasbecomeincreasinglyimportanttodesigners
andbuilding owners/occupants.Properconsideration
mustbegiventoplacementofindoorairconditioning
units, particularly in the occupied space. Inherent
flexibilityofthefanandcoilcombinationinthevertical
configuration allows application in sound-sensitive
areas. In such instances, a fan running at a low speed
with a high capacity coil normally yields satisfactory
results.Italsomaybedesirabletoselectalargernom-
inal capacity unit and operate it at a less than nominal
airflowforfurtheracousticbenefit.
Threephasemotorsarerecommendedforsound-sen-
sitive applications to avoid potential single phase motor
hum. Unit operation in the stall region of the fan curve
is not recommended since it may cause unsatisfactory
noiselevelsandexcessiveunitvibration.
INSTALLATION
Thesefloormountedunitscanbeinstalledwithexternal
vibrationisolationonabaserail(ACR)oronareturn
plenum(ACB)atthecornerpoints.Thisrequiresflex
connectionsatthecornerbrackets,ductwork,electrical
connections and piping connections. One of the most
importantandbasicIAQissuesiscondensatemanage-
ment.Thefirststeptoensuretrouble-freeoperationis
properinstallation.Itisveryimportantthattheunitbe
mounted high enough so that the condensate drain
from the unit may be properly trapped. Please refer
to the ACB/ACR IOM Manual for specifics on this
issue. As with all HVAC systems, these units should
beinstalledaccordingtoallapplicableASHRAEstan-
dards,SMACNAandlocalcoderequirements.
OPERATING LIMITATIONS
Unitsmustnotbeoperatedabovemaximumfanspeed
or unit airflow as listed in the Fan Performance section
ofthiscatalog.Unitoperationatgreaterthanmaximum
fan speed could drastically reduce bearing life and
may result in a catastrophic wheel failure. Operating
atgreater thanthemaximumallowable airflowinthe
cooling mode may result in unsatisfactory operation
due to moisture carry over from the coil. In addition, it
isoftennoteconomicaltooperateaunitatitsmaximum
fanspeedduetothegreatermotorpowerrequirements.
Units with electric heat should not be operated with
leaving air temperature greater than 104°F (40°C),
to prevent excessive leaving air temperatures and
electricheatlimittrips.Ahydronic(orsteam)coiland
electricheatshouldnotbeoperatedsimultaneouslyto
prevent excessive leaving air temperatures and limit
trips.Electricheatunitsareequippedwithahighlimit
lockout switch that disables the electricheater if the
temperatureofthehydronic(orsteam)coilisgreater
than104°F(40°C).
Watercoilsmustnotbeoperatedaboveafluidvelocity
of8ft./sec.toreducethepossibilityofvelocityinduced
erosion and flow noise. Water coils must not be
operatedbelowafluidvelocityof1ft./sec.toprevent
degraded coil performance caused by laminar flow.
Thesehighorlowfluidflowratesmaynotbeincluded
intheAHRIcoilcertification.
Johnson Controls 7
Reduced-Footprint, Vertical Blower-Coil Units Form: 115.26-EG4 (815)
COIL AND FILTER DATA
COIL FACE AREA AND FILTER DATA
NOMINAL COIL CONNECTION SIZES
08
2.1 [0.20] 2.1 [0.20] (1) 16" x 20" x 2" [406 x 508 x 51]2.2 [0.20]
12
2.8 [0.26] 2.1 [0.20] (1) 20" x 20" x 2" [508 x 508 x 51]2.8 [0.26]
16
3.6 [0.33] 3.2 [0.30] (1) 24" x 24" x 2" [610 x 610 x 51]4.0 [0.37]
20
4.8 [0.45] 3.2 [0.30] (1) 24" x 24" x 2" [610 x 610 x 51]4.0 [0.37]
25
5.7 [0.53] 4.6 [0.43]
(1) 24" x 24" x 2"
(1) 12" x 24" x 2"
[610 x 610 x 51]
[305 x 610 x 51]
6.0 [0.56]
30
6.8 [0.63] 5.7 [0.53]
(1) 24" x 24" x 2"
(1) 12" x 24" x 2"
[610 x 610 x 51]
[305 x 610 x 51]
6.0 [0.56]
FILTER
FACE AREA
UNIT
SIZE
INTERNAL COOLING
AND HEATING COILS
DISCHARGE SECTION
HEATING COILS
2" FILTERS
(Quantity) and Size
LIQUIDSUCTION LIQUIDSUCTION
08
5/8" [16] 5/8" [16] 7/8" [22] 7/8" [22] 5/8" [16] 5/8" [16] 5/8" [16] 5/8" [16]
12
5/8" [16] 5/8" [16] 7/8" [22] 7/8" [22] 5/8" [16] 7/8" [22] 5/8" [16] 7/8" [22]
16
5/8" [16] 7/8" [22] 7/8" [22] 1 1/8" [29] 5/8" [16] 7/8" [22] 5/8" [16] 7/8" [22]
20
5/8" [16] 7/8" [22] 1 1/8" [29] 1 1/8" [29] 5/8" [16] 7/8" [22] 5/8" [16] 7/8" [22]
30
7/8" [22] 1 1/8" [29] 1 1/8" [29] 1 3/8" [35] 5/8" [16] 1 1/8" [29] 5/8" [16] 1 1/8" [29]
40
1 1/8" [29] 1 3/8" [35] 1 3/8" [35] 1 5/8" [41] 5/8" [16] 1 1/8" [29] 7/8" [22] 1 3/8" [35]
UNIT
SIZE
WATER
COIL TYPE
REFRIGERANT
6 ROW
1 ROW
4 ROW
2 ROW 4 ROW 6 ROW
NOTES:
1.WatercoilsarebasedonStandardGPMCircuiting.Consultfactoryforapplicationsrequiringspecialcircuiting.
2.Forotherselections,refertoWeb-Select
®
.
3.Refrigerantcoilconnectionsizesforsinglecircuitcoilsandmayvarywithapplication.Contactfactoryfordoublecircuitcoils.
4.Alldimensionaldataisoutsidediameter(O.D.),measuredininches[millimeters].
5. See page 8 for a list of standard and optional features of Johnson Controls coils.
NOTES:
1.Standardfiltersare2”throwaway;optionalfiltersare2”pleated.
2.Filtersizesarenominalandstandardsize,measuredininches[millimeters].
3.Coilandfilterfaceareasaremeasuredinsquarefeet[squaremeters].
8 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
COILS DATA
COILS
COMPONENT STATIC PRESSURE LOSS – INCHES W.G.
1 ROW2 ROW4 ROW6 ROW1 ROW2 ROW
08
800 0.09 0.25 0.05 0.10 0.31 0.46 0.05 0.10 0.04 0.05
12
12000.090.250.060.120.370.550.100.190.0
60
.05
16
16000.100.250.060.120.380.580.080.150.0
90
.05
20
20000.110.250.060.110.350.520.110.220.0
50
.05
25
25000.120.250.060.120.380.570.090.170.0
60
.05
30
30000.140.250.060.120.380.570.080.160.080.05
INLET
DAMPER
SECTION
ELECTRIC
HEAT
SECTION
UNIT
SIZE
NOMINAL
CFM
CABINET
FILTER
(2" T/A)
INTERNAL
EXTERNAL
COIL
NOTES:
1.AllstaticpressuresareatnominalCFM.
2.Coilstaticpressureforstandardcoil,10FPIat80/67EATand45°EWTwith10°rise.
3.For12FPI,refertoWeb-Select
®
.
4.Filterstaticpressurebasedon50%loadedfilter.
5. If pleated filters are used in lieu of throwaway, the filter static pressure loss is 0.35.
STANDARD FEATURES
• Coilsdesigned,manufacturedandtestedby
Johnson Controls
• AHRI410certifiedandlabeled
• 1/2”O.D.seamlesscoppertubes
• High efficiency aluminum fin surface for optimizing
heat transfer, pressure drop and carryover
• Mechanicallyexpandedcoppertubesleaktestedtoa
minimum 450 PSIG air pressure under water
• Manualairventplugonallwatercoils
• CopperODMsweatconnections
• 300PSIGworkingpressureat200°F
• Evaporatorcoilsarefactorysealedandchargedwith
a minimum of 5 PSIG nitrogen or refrigerated dry air
• Steamcoilsratedat15PSIGmaximumoperating
pressureatabove35°F
• 0.016”tubewallthickness(0.025”onsteam)
OPTIONAL FEATURES
• Stainlesssteelcoilcasings
• Automaticairventsonwatercoils
• Elevatedworkingpressureratings
• Heatpumpcompatiblecoolingcoils
• DoublecircuitDXcoils(intertwinedwith50-50split)
• 0.025”tubewallthickness
JohnsonControlsofferstheindustry’sfirstweb-basedratingandselectionprogramforcompleteunit,coiland
fan selection. See your representative for more information.
Johnson Controls 9
Reduced-Footprint, Vertical Blower-Coil Units Form: 115.26-EG4 (815)
ELECTRIC HEAT
NOTES:
1.Electricheatsectionsmaybeshippedseparateforfieldinstallationtounit.
2.Factorycertifiedsubmittalsavailableuponrequest.
3.StandardheaterkWlimitsaremaximumperunitsizeandvoltage.
4.Heatershouldbesizedforamaximumleavingairtemperatureof104°F.
STANDARD FEATURES
• Galvanizedsteelcasing
• Flangedconstructionfordirectunit
mounting,inblowthruconfiguration
• Listedforzeroclearanceinstallation
• MeetsNationalElectricalCoderequirements
• Ni-Chromewireinceramicinsulators
• Stainlesssteelelementterminalsandhardware
• Elementsupportbracketsonmaximum31/2”centers
• Solidcoverwithcontinuousfullheighthinge
• Overtemperatureprotection
• Allinternalwiringratedfor105°Cminimum
• Airflowswitch
• Incominglinepowerdistributionblock
• ETLListedincompliancewithUL/ANSI
Standard 1995
• Singlepointpowerconnection
• HeaterfactorymountedtounitwithETLlistingasan
assembly
OPTIONAL FEATURES
• Doorinterlockingdisconnectswitch
• Fusing(main)(perstage)
• Magneticcontactorswiredfordisconnecting
operation
• Fancontrolpackagewithheaterinterlockcontacts
(requiredforsinglepointpowerconnection)
16
Single Phase
08
12
208
230
277
115
40
ELECTRIC HEAT KW LIMITS
Unit Size
UNIT VOLTAGE AND
PHASE
Three Phase
208
230
460
575
20
30
ELECTRICAL CALCULATIONS INFORMATION
1.RefertoMCA/MOPCalculatoratwww.JohnsonControls.comforMCAand/orMOPcalculations.
2.Non-FusedDoorInterlockDisconnectSwitchshallbesizedaccordingtoMCA.
3.FusedDoorInterlockDisconnectSwitchandMainFusingshallbesizedaccordingtoMOP.
VOLTAGE
115/1
208/1
230/1
277/1
208/3
230/3
460/3
575/3
4.81
4.35
3.61
HEATER AMP CALC.
AMPs per kW
8.70
1.00
2.78
2.51
1.26
10 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
ELECTRIC DATA
MOTOR ELECTRICAL DATA
UNIT WEIGHT DATA
MOTOR/DRIVE WEIGHT DATA
NOTES:
1.ActualmotornameplateAMPsmayvary,butwillnotexceedvaluesshown.
2.Consultfactoryforapplicationsrequiringspecialmotors.
NOTES:
1.Includesmotor,pulleys,belts,andmotorbase.
2.Motor/driveweightdataisshippingweightinpounds[kilograms].
08 12 16 20 25 30
125 [57] 131 [60] 160 [73] 167 [76] 231 [105] 236 [107]
42 [19] 53 [24] 59 [27] 73 [33] 91 [41] 91 [41]
42 [19] 42 [19] 42 [19] 50 [23] 55 [25] 55 [25]
35 [16] 37 [17] 49 [22] 53 [24] 76 [35] 80 [36]
22 [10] 26 [12] 35 [16] 38 [17] 76 [35] 76 [35]
29 [13] 30 [14] 33 [15] 35 [16] 44 [20] 44 [20]
1 ROW - DRY 12 [5] 14 [6] 17 [8] 21 [10] 23 [10] 27 [12]
1 ROW - WET 14 [6] 17 [8] 21 [10] 26 [12] 28 [13] 34 [15]
2 ROW - DRY 17 [8] 21 [10] 26 [12] 32 [15] 37 [17] 43 [20]
2 ROW - WET 21 [10] 27 [12] 33 [15] 42 [19] 48 [22] 56 [25]
4 ROW - DRY 29 [13] 36 [16] 45 [20] 57 [26] 65 [30] 76 [35]
4 ROW - WET 37 [17] 47 [21] 58 [26] 75 [34] 86 [39] 101 [46]
6 ROW - DRY 40 [18] 51 [23] 64 [29] 81 [37] 93 [42] 109 [50]
6 ROW - WET 52 [24] 66 [30] 84 [38] 109 [50] 124 [56] 146 [66]
COIL ROWS
COMPONENT
UNIT SIZE
BASIC UNIT
DAMPER SECTION
BLOW THRU ELECTRIC HEATER
DISCHARGE COIL SECTION
SUPPLY PLENUM
RETURN PLENUM (VB)
NOTES:
1.Unitweightdataisshippingweightinpounds[kilograms].
2. Discharge section includes a 2 row coil.
1/31/2 3/411 1/22 3
SINGLE PHASE
37 [17] 37 [17] 45 [20] 47 [21] -- -- --
THREE PHASE
34 [15] 34 [15] 40 [18] 43 [20] 46 [21] 53 [24] 81 [37]
MOTOR HP
TYPE
115/1 208/1 230/1 277/1208/3 230/3460/3 575/3
1/36.3 3.53.2 2.61.7 1.50.8 -
1/27.8 4.33.9 3.62.2 2.11.1 0.9
3/4 10.65.4 5.35.0 3.23.0 1.
51
.2
1 15.08.3 7.55.5 4.03.6 1.
81
.4
1 1/2 ----5.3 5.02.5 1.9
2 ----7.0 6.43.2 2.5
3 ----9.1 9.04.5 3.2
MAXIMUM MOTOR AMPERAGE
HORSEPOWER
VOLTAGE
Johnson Controls 11
Reduced-Footprint, Vertical Blower-Coil Units Form: 115.26-EG4 (815)
TYPICAL INSTALLATIONS
MODEL ACB, BOTTOM RETURN WITH
RETURN PLENUM CLOSET OR
CONFINED SPACE LAYOUT
MODEL ACR, REAR RETURN WITH MIXING
BOX - MECHANICAL ROOM LAYOUT
MODEL ACR WITH ELECTRIC HEAT
MECHANICAL ROOM LAYOUT
MODEL ACR, REAR RETURN
UNIT HANDLING LOAD IN ADJACENT ROOM
12 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
UNIT DISCHARGE OPTIONS
STANDARD ROTATION
ARRANGEMENT 2
REVERSE ROTATION
ARRANGEMENT 1
HORIZONTAL REAR DISCHARGE
ARRANGEMENT 7
REVERSE ROTATION
ARRANGEMENT 1
HORIZONTAL REAR DISCHARGE
ARRANGEMENT 7
NOTES:
1.RefertoDimensionalDataforunitdimensions.
2.Fanarrangementsarealsoavailablewithinletdampersection(ModelACR)andreturnplenumsection(ModelACB).
3.Sideaccessfilterrackstandardonarrangement7(ModelACR).
4.Dischargeheatingcoilsectionandsupplyplenumarenotavailablewitharrangement7.
5.Alldrawingssubjecttochangewithoutpriornotice.
STANDARD ROTATION
ARRANGEMENT 2
MODEL ACR
MODEL ACB
Johnson Controls 13
Reduced-Footprint, Vertical Blower-Coil Units Form: 115.26-EG4 (815)
FAN PERFORMANCE CURVES
UNIT SIZE 08 (FAN 0904R)
UNIT SIZE 12 (FAN 0906R)
SE= CFMxSP
6362xBHP
SE= CFMxSP
6362xBHP
14 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
FAN PERFORMANCE CURVES
UNIT SIZE 16 (FAN 1008R)
UNIT SIZE 20 (FAN 1010R)
SE= CFMxSP
6362xBHP
SE= CFMxSP
6362xBHP
Johnson Controls 15
Reduced-Footprint, Vertical Blower-Coil Units Form: 115.26-EG4 (815)
FAN PERFORMANCE CURVES
UNIT SIZE 25 (FAN 1509R)
UNIT SIZE 30 (FAN 1511R)
SE= CFMxSP
6362xBHP
SE= CFMxSP
6362xBHP
16 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
DIMENSIONAL DATA
MODEL ACB (BOTTOM RETURN)
Drawings are not to scale and are not for installation purposes.
Johnson Controls 17
Reduced-Footprint, Vertical Blower-Coil Units Form: 115.26-EG4 (815)
DIMENSIONAL DATA
MODEL ACR (REAR RETURN)
Drawings are not to scale and are not for installation purposes.
18 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
DIMENSIONAL DATA
MODEL ACR WITH INLET DAMPER SECTION
Drawings are not to scale and are not for installation purposes.
Johnson Controls 19
Reduced-Footprint, Vertical Blower-Coil Units Form: 115.26-EG4 (815)
DIMENSIONAL DATA
MODEL ACB WITH BLOW THRU ELECTRIC HEAT
Drawings are not to scale and are not for installation purposes.
20 Johnson Controls
Form: 115.26-EG4 (815) Reduced-Footprint, Vertical Blower-Coil Units
DIMENSIONAL DATA
DISCHARGE PLENUM WITH DOUBLE DEFLECTION GRILLE (ACB AND ACR)
Drawings are not to scale and are not for installation purposes.
RETURN PLENUM (MODEL ACB)
Drawings are not to scale and are not for installation purposes.
Front View
Side View
DIMENSIONAL DATA
NOTES:
1.Alldimensionsareinches[millimeters]+/-1/4”[6mm].Metricvalues
are soft conversions.
2.Alldrawingssubjecttochangewithoutpriornotice.
3. Discharge plenum shipped attached to unit.
4.Discharge plenum includes double deflection discharge grille;
location is front as shown.
5.Discharge plenum may not be combined with blow through
electric heat.
Front View
Side View
DIMENSIONAL DATA
NOTES:
1.Alldimensionsareinches[millimeters]+/-1/4”[6mm].
Metricvaluesaresoftconversions.
2.Alldrawingssubjecttochangewithoutpriornotice.
3.Bottomandbackpanelsarefixed.Bothsidepanelsare
removableandcanbeusedtocoverthefrontopening.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

York Vertical, Reduced-Footprint Blower-Coil Units User guide

Type
User guide

York Vertical, Reduced-Footprint Blower-Coil Units are highly adaptable units for various HVAC systems. Their compact design, with vertical orientation and minimized footprint, makes them ideal for areas with space constraints. The units boast galvanized steel construction for durability and longevity, and they are thoroughly inspected and tested prior to shipment to ensure optimal performance upon installation.

These Blower-Coil Units offer exceptional flexibility with a wide range of options, allowing you to customize them to your specific requirements. You can choose from various fan discharge configurations, electric heat with or without single-point power connection, mixing boxes with low-leak dampers, and more.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI