  • Hello! I am an AI chatbot trained to assist you with the Tripp Lite SU32ACORD User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Tripp Lite follows a policy of continuous improvement. Product specifications are subject to change without notice.
1111 W. 35th Street, Chicago, IL 60609 USA
www.tripplite.com/support
Copyright 2010 Tripp Lite. All rights reserved.
Connection: SU30A/SU32A to an SU6000RT4UHVG
(SUPDMB6KIEC):
- Green/Yellow or Green conductor/wire
N - White conductor/wire
L - Black conductor/wire
Connection: SU30A/SU32A to an SU6000RT3U
(SU6000XFMRRT3U):
L1 (AC INPUT) -
Black conductor/wire
G (AC INPUT) -
Green/Yellow or
Green conductor/wire
L2 (AC INPUT) -
White conductor/wire
Connection: SU30A/SU32A to an SU6000RT3UHV:
L2(N) - White conductor/wire
L1 - Black conductor/wire
- Green/Yellow or Green conductor/wire
Connection: SU32A to an SMX5000XLRT3U:
- Green/Yellow or Green conductor/wire
L2(N) - White conductor/wire
L1 - Black conductor/wire
Owner’s Manual Addendum
Wiring Instructions
Models: SU30ACORD/SU32ACORD
Warranty
Registration
Register online today for a
chance to win a FREE Tripp Lite
product! www.tripplite.com/warranty
General Warnings
• Beforeconnection,makesurethatyourUPSsystemisturnedOFF,bothinputandoutputbreakersareswitchedOFFandthatthesystemis
disconnectedfromACpower.(SeeUPSOwner’sManual.)
• Beforeconnection,youmustsetyourSU6000XFMRRT3U’sDIPswitchestoreceivetheappropriatevoltage(208Vor240V).Your
SU6000XFMRRT3UwillnotconvertACinputtothecorrectvoltage.(SeeUPSOwner’sManual.)
• For Hardwire Models: Please refer to the requirements of the National Electric Code and local ordinances for installation guidelines. Installation
must be handled by qualified service personnel only!
• Properlysizedinputprotectionmustbeprovidedbytheenduser.
Installation
•ThreadtheexposedendofthepowercordthroughtheknockoutontheUPSortransformer’sterminalblock.
•ConnectthecoloredwirestotheUPS,PDUorTransformer’sterminalblockaccordingtothediagramsbelow.
•Tightenthepowercord’sstrainreliefandafxittotheknockout.
•FortheSU6000RT4UHVGandSMX5000XLRT3UusethecableclampalreadyinstalledonthePDUorUPS.
•FortheSU6000RT3UandSU6000RT3UHVusethecableclampincludedwiththepowercord.
201008072•933044-EN
/