M-system R8-SS4NJ User manual

  • Hello! I am an AI chatbot trained to assist you with the M-system R8-SS4NJ User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-9732 Rev.3 P. 1 / 4
INSTRUCTION MANUAL
DC CURRENT INPUT MODULE
(built-in excitation, 4 points, non-isolated)
MODEL
R8-SS4NJ
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
PACKAGE INCLUDES:
DC current input module ....................................................(1)
MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
CONFORMITY WITH EU DIRECTIVES
•The equipment must be mounted inside a panel.
•The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
GENERAL PRECAUTIONS
•Before you remove or mount the unit, turn off the power
supply and input signal for safety.
•Switches on the side of the module can be set for mainte-
nance only while the power supply is off. Do not access
them while the power is supplied.
• ENVIRONMENT
•Indoor use.
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to90% RH
in order to ensure adequate life span and operation.
WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
EXCITATION SUPPLY
•Power output (input terminal): Rated current 0.5 A DC
per channel (rated current 3 A for internal fuse (slow blow
fuse i
2
t (A
2
sec) max. 5.04) , Total 1 A DC
AND ....
•The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
HOW TO MOUNT THE MODULE ON DIN RAIL
A
B
• I/O Module
Confirm that the locking clamps of the I/O module are set.
Insert the module in parallel to the next one while aligning the grooves of
both modules (A & B in the above figure).
Maintain it perpendicularly to the rail.
More I/O modules can be added in the same manner.
R8-SS4NJ
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-9732 Rev.3 P. 2 / 4
• Protective Cover
The protective cover is to be attached over the connected I/O module
at the right end.
Align the hooks on the cover with the grooves of the module and slide it
straight until the hooks are latched.
When removing the cover, pull it out while squeezing the hooks inward.
Groove
Hook
HOW TO UNMOUNT THE MODULE FROM DIN RAIL
Release the locking clamps and pull out straight the module.
Caution !
1) Be careful not to hurt your hand by pointed edges of the internal
communication bus connector.
2) I/O modules cannot hold tightly on the DIN rail by themselves without
power/network module.
Secure them to the position if necessary by using DIN rail end plates.
• Removing an intermediate module
R8-SS4NJ
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-9732 Rev.3 P. 3 / 4
COMPONENT IDENTIFICATION
RUN
AI_I1
AI_I2
Module Address Setting
Rotary SW
Function Setting
DIP SW
Terminator DIP SW
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
SW1
x10
12345678
x1
SW2
SW4
SW3Term
On
On
Status Indicator LED
Input Indicator LED
Internal Bus Connector
Input Connectors
FRONT VIEW RIGHT SIDE VIEW
CARD ADD.
Short across grounds
JP1
SHORT OPEN
LEFT SIDE VIEW
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
INDICATOR LED
ID
OPERATION
FUNCTION
Status OFF Stopping
Green ON Valid host communication
Green Blinking
Reading/writing configuration
Red ON Setting error
Red Blinking Parameter error
Input
Status
OFF Input data in the range
Red Blinking Input data out of range
INPUT CONNECTOR ASSIGNMENT
PIN
ID FUNCTION
No.
1 24 V Excitation supply 24 V
2 AI Input (+)
3 AG Input (−)
4 0V Excitation supply 0 V
1
2
3
4
PC CONFIGURATOR
The following parameters can be set with using PC Configu-
rator Software (model: R8CFG):
•Input setting by channels (range, scaling, zero/gain ad-
justments)
•Common setting (loss of internal bus communication de-
tection time)
Turn SW4-8 ON to allow programming by the PC Configu-
rator via the Power/Network Module.
Refer to the users manual for the R8CFG for detailed opera-
tion of the software program.
SHORT ACROSS GROUNDS
Choose to open or short across grounds of excitation supply
and input.
In case of shorting across, insert short-plug in the center pin
of JP1 and SHORT side.
In case of opening, insert short-plug in the center pin of JP1
and OPEN side.
Factory default is on SHORT side.
MODULE ADDRESS
The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address.
Address is selected between 0 to 30.
(Factory setting: 0)
Module Address Setting (x10)
Module Address Setting (x1)
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
OPERATING MODE
(*) Factory setting
• Input Range
Same range for all channels. Use PC Configurator to set
independent ranges per channel.
INPUT RANGE SW4-1 SW4-2
0 − 20 mA DC OFF OFF
4 − 20 mA DC (*) ON OFF
• Conguration Mode
CONFIGURATION MODE SW4-8
DIP switch setting (*) OFF
PC Configurator and communication ON
• Terminator DIP SW
TERMINATOR SW SW3
Without (*) OFF
With ON
Note: Be sure to set unused SW4-3 through 4-7 to OFF.
R8-SS4NJ
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-9732 Rev.3 P. 4 / 4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
EXTERNAL DIMENSIONS unit: mm (inch)
115 (4.53)6 (.24)7 (.28) 6 (.24) 7 (.28)
DIN RAIL
(35 mm wide)
[3 (.12)]
[4 (.16)]
12 (.47)
59 (2.32)
55 (2.17)
CONNECTION DIAGRAM
1
2
4
3
INTERNAL POWER
INTERNAL BUS
EXC. SUPPLY
24V
I1
AG
0V
INPUT 1
INPUT CONNECTOR 1
1
2
4
3
24V
I2
AG
0V
INPUT CONNECTOR 2
1
2
4
3
24V
I3
AG
0V
INPUT CONNECTOR 3
1
2
4
3
24V
I4
AG
0V
INPUT CONNECTOR 4
INPUT 2
INPUT 3
INPUT 4
BUS CONNECTOR
INPUT CONNECTION
50Ω
+
NC
INPUT
NC
NC
NC
50Ω
3
4
1
2
3
4
1
2
When Used as Current Input
JP1 can be open or short.
When Used as DC Supply
Short the JP1.
+
+
2-WIRE
TRANSMITTER
WIRING INSTRUCTIONS
e-CON connector
Unit side connector: XN2D-1474-S002 (Omron)
Recommended cable side connector: XN2A-1470 (Omron)*
1
Applicable wire size: 0.08 – 0.5 mm
2
(AWG28 – AWG20)
Outer sheath diameter: max. 1.5 dia
*1. The cable side connector is not included in the package.
Refer to the specifications of the product.
/