  • Hello! I am an AI chatbot trained to assist you with the Munters TEN-MCDI-B1602 Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Originalinstructions
Usermanual
MC150
Digitalcontrol
Desiccantdehumidier
TEN-MCDI-B1602©MuntersEuropeAB2016
Importantuserinformation
Intendeduse
Muntersdehumidiersareintendedtobeusedforthe
dehumidicationofair.Anyotheruseoftheunit,or
usewhichiscontrarytotheinstructionsgiveninthis
manual,cancausepersonalinjuryanddamagetotheunit
andotherproperty.
Nomodicationoftheunitisallowedwithoutprior
approvalbyMunters.Attachmentorinstallation
ofadditionaldevicesisonlyallowedafterwritten
agreementbyMunters.
Warranty
Thewarrantyperiodisvalidfromthedatetheunit
leftourfactory,unlessotherwisestatedinwriting.
Thewarrantyislimitedtoafreeexchangeofpartsor
componentswhichhavefailedasaresultofdefectsin
materialsorworkmanship.
Allwarrantyclaimsmustincludeproofthatthefaulthas
occurredwithinthewarrantyperiodandthattheunit
hasbeenusedinaccordancewiththespecications.All
claimsmustspecifytheunittypeandserialnumber.This
informationisstampedontheidenticationlabel.
Itisaconditionofthewarrantythattheunitforthe
fullwarrantyperiodisservicedandmaintainedas
describedinsectionServiceandmaintenance.Theservice
andmaintenancemustbedocumentedforthewarranty
tobevalid.
Safety
Informationaboutdangersareinthismanualindicated
bythecommonhazardsymbol:
W W
W
ARNING! ARNING!
ARNING!
Indicatesapossibledangerthatcanleadtopersonalinjury.
CA CA
CA
UTION! UTION!
UTION!
Indicatesapossibledangerthatcanleadtodamagetothe
unitorotherproperty,orcauseenvironmentaldamage.
NOTE!Highlightssupplementaryinformationforoptimal
useoftheunit.
ConformitywithDirectives
Thedehumidierisinconformitywiththeessential
safetyrequirementsoftheMachineryDirective
2006/42/EC,theRoHSDirective2011/65/EUandthe
EMCDirective2004/108/EC.
Copyright
Thecontentsofthismanualcanbechangedwithout
priornotice.
NOTE!Thismanualcontainsinformationwhichis
protectedbycopyrightlaws.Itisnotallowedtoreproduceor
transmitanypartofthismanualwithoutwrittenconsentfrom
Munters.
Sendanycommentsregardingthismanualto:
MuntersEuropeAB
TechnicalDocumentation
P.O.Box1150
SE-16426KISTASweden
iiImportantuserinformationTEN-MCDI-B1602
Tableofcontents
Importantuserinformation...............ii
Intendeduse...........................
ii
Warranty...............................
ii
Safety..................................
ii
ConformitywithDirectives............
ii
Copyright..............................
ii
Tableofcontents...........................iii
1Introduction.................................1
1.1Aboutthismanual.....................
1
1.2Unintendeduse........................
1
1.3Safety..................................
1
2Functiondescription.......................4
3Transport,inspectionandstorage.......5
3.1Transport..............................
5
3.2Inspectionofdelivery..................
5
3.3Storingtheequipment................
5
4Installation...................................6
4.1Safety..................................
6
4.2Closedsystem.........................
6
4.3Opensystem..........................
7
4.4Siterequirements.....................
7
4.5Ductsandhoses.......................
8
4.5.1Ductworkforoutdoorairinlet..
8
4.5.2Ductworkforwetairoutlet.....
8
4.6Electricalconnections................
9
4.7Expandingthesystem................
9
4.8Accessories...........................
10
5Operation....................................11
5.1Safety..................................
11
5.2Menusandoperation..................
11
5.2.1Operatorpanel.................
11
5.2.2Defaultview....................
12
5.2.3Mainmenu.....................
14
5.2.4Controloptions.................
22
5.2.5Alarms..........................
23
5.3Network................................
24
5.3.1Networkfunctions.............
24
5.3.2Howtonetworkdehumidiers
24
6Serviceandmaintenance.................26
6.1General................................
26
6.2Maintenanceschedule................
26
6.3Filterreplacement.....................
26
7Faulttracing.................................27
8Technicalspecication....................28
8.1Dimensionsandservicespace.......
28
8.2Capacitydiagram.....................
29
8.3Fancurveprocessair.................
30
8.4Fancurvereactivationair.............
31
8.5Technicaldata.........................
32
9Scrapping....................................33
10ContactMunters............................34
TEN-MCDI-B1602Tableofcontentsiii
DehumidierMC150
1Introduction
1.1Aboutthismanual
Thismanualiswrittenfortheuserofthedehumidier.Itcontainsnecessaryinformationforhowtoinstall
andusethedehumidierinasafeandefcientway.Readthroughthemanualbeforethedehumidieris
installedandused.
ContactyournearestMuntersofceifyouhaveanyquestionsregardingtheinstallationortheuseofyour
dehumidier.
Thismanualmustbestoredinapermanentlocationclosetothedehumidier.
1.2Unintendeduse
Thedehumidierisnotintendedforoutdoorinstallation.
Thedehumidierisnotintendedforuseinclassiedareaswhereexplosionsafetycompliantequipment
isrequired.
Thedehumidiermustnotbeinstallednearanyheatgeneratingdevicesthatcancausedamagetothe
equipment.
NOTE!Whenadehumidierisplacedinabuildingwithradonitisnecessarytocontactanexperttosecurethe
bestoverallsolution.Allchangesaffectingtheventilationorthepressurebalanceinthebuildingcanresultina
changedconcentrationofradon.
CA CA
CA
UTION! UTION!
UTION!
Donotsit,stand,orplaceanyobjectsontheunit.
1.3Safety
Everymeasurehasbeentakeninthedesignandmanufactureofthedehumidiertoensurethatitmeetsthe
safetyrequirementsofthedirectivesandstandardslistedintheECDeclarationofConformity.
Theinformationinthismanualshallinnowaytakeprecedenceoverindividualresponsibilitiesorlocal
regulations.
Duringoperationandotherworkwithamachineitisalwaystheresponsibilityoftheindividualtoconsider:
Thesafetyofallpersonsconcerned.
Thesafetyoftheunitandotherproperty.
Theprotectionoftheenvironment.
ThetypesofdangersthatareindicatedinthismanualaredescribedinsectionImportantuserinformation.
Thisequipmentcanbeusedbychildrenagedeight(8)yearsoraboveandpeoplewithreducedphysical,
sensoryormentalcapabilitiesorwithlackofexperienceandknowledgeprovidedtheyhavebeengiven
instructionsandinformationonhowitissafelyusedandthattheyunderstandthehazardsinvolved.
1IntroductionTEN-MCDI-B1602
DehumidierMC150
W W
W
ARNING! ARNING!
ARNING!
-Theunitmustnotbeinstalledoutdoors.
-Theunitmustnotbesplashedwithorimmersedinwater.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Theunitmustbeconnectedtoanearthedelectricaloutlet.
-Donotconnecttheunittoothermainsvoltagethanspeciedontheidenticationplate.
Maxoutletfuse230VAC:16A.
-Donotoperatetheunitifthepowerplugorcordisdamaged,riskofelectricalshock.
-Donotpulltheplugwithwethands,riskofelectricalshock.
-Donotinsertngersoranyobjectsintotheairvents,rotatingfansareinside.
-Donotcovertheunitasthatcanblockairintakeoroutletandcauseare.
-Iftheunithasoverturned,cutthepowerimmediately.
-Thedehumidiermustnotbepowereduntiltheinstallationisnishedinaccordancewiththismanual.
-Aresidual-currentdevice/groundfaultcircuitinterruptershouldbeusedtominimizetheriskofelectricshocks.
-Nevercarryorpullthedehumidierbyitscable.
-Theunitmustnotbeusedinclassiedareaswhereexplosionsafetycompliantequipmentisrequiredorwhere
explosivegasescouldstillbepresent.
-Theunitwillrestartautomaticallyandwithoutwarningfollowingapowerfailure.
-Thedehumidiermustneverbeusedwithanyotheraccessoriesthanthoselistedinthismanual.
-Donotattempttorepair,dismantleormodifythisunit.
-Theunitmustnotbeopenedbyanyoneotherthantrainedandqualiedpersonnel,duetotheriskofelectrical
shock.
-AlwayscontactMuntersforserviceorrepair.
-Operatingfaultscanoccuriftheunitismaintainedinsufcientlyorincorrectly.
-Iftherotoristobecutinpieces,wearasuitableCEmarkedfacemaskselectedandttedinaccordancewiththe
applicablesafetystandardstoprotectfromthedust.
TEN-MCDI-B1602Introduction2
DehumidierMC150
CA CA
CA
UTION! UTION!
UTION!
-Thedehumidiermustnotbeinstallednearanyheatgeneratingdevicesthatcancausedamagetothe
equipment.
-Removethemainsplugfromthesocketbeforestartinganymaintenancework.
-Alwaysunplugtheunitfromthepowersupplywhennotinuse.
-Thedehumidiermustbeplacedsteadilyandmustnotbeusedtosit,standorplaceobjectson.
-Basesororganicmaterialwithhighboilingpointsuchasoil,grease,solvents,boracolorsimilarsubstancesmust
notbedrawnintothedehumidier.Theycandamagetherotor.
-Neverusethedehumidierwithoutthelterinstalledasthiscancausedamagetoit.Ensurethatthelterisclean.
Aclutteredltercancausethedehumidiertooverheat.
-Allchangesaffectingtheventilationorthepressurebalanceinthebuildingcanresultinachangedconcentration
ofradon.Iftheunitisplacedinabuildingwithradon,itisnecessarytocontactanexperttosecurethebestoverall
solution.
-Donotunplugthedehumidierwhileitiscoolingdown.Unpluggingitcanleadtopermanentunitdamage.
-Onlyquickstopthedehumidierincaseofemergency.Thefanstopsandtheheatercanbeveryhot,whichcan
resultindamagetotheheaterandothercomponentsclosetoit.
-Donotusetheairconnectionsforliftingtheunit.
3IntroductionTEN-MCDI-B1602
DehumidierMC150
2Functiondescription
Thedesiccantrotoristheadsorptiondehumidifyingcomponentintheunit.Therotorstructureis
comprisedofalargenumberofsmallairchannels.
Thedesiccantrotorismadeofacompositematerialthatishighlyeffectiveinattractingandretainingwater
vapour.Therotorisdividedintwozones.Theairowtobedehumidied,processair,passesthroughthe
largestzoneoftherotorandthenleavestherotorasdryair.Sincetherotorrotatesslowly,theincomingair
alwaysmeetsadryzoneontherotor,thuscreatingacontinuousdehumidicationprocess.
Theairowthatisusedtodrytherotor,reactivationair,isheated.Thereactivationairpassesthrough
therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair(warm,moistair).This
principleenablesthedehumidiertoworkeffectively,evenatfreezingtemperatures.
TypeYusesoneinletairowforprocessairandforreactivationoftherotor.
TypeXusesaseparateinletairowforreactivationoftherotor.
Figure2.1TypeY
1.Process/Reactivationair
2.Dryair
3.Wetair
Figure2.2TypeX
1.Processair
2.Dryair
3.Wetair
4.Reactivationair
TEN-MCDI-B1602Functiondescription4
DehumidierMC150
3Transport,inspectionandstorage
3.1Transport
Transportthedehumidierintheoriginalpackaging.Theunitmustalwaysbeplacedinanuprightposition
duringtransport.Failuretocomplywiththiscancausetheunittomalfunction.
CA CA
CA
UTION! UTION!
UTION!
Donotusetheairconnectionsforliftingtheunit.
3.2Inspectionofdelivery
Inspectthedeliveryandcomparewiththedeliverynote,orderconrmationorotherdelivery
documentation.Makesurethateverythingisincludedandnothingisdamaged.
ContactMuntersimmediatelyifthedeliveryisnotcompleteordamagedinordertoavoidinstallation
delays.
Removeallpackagingmaterialfromtheunit,andmakesurethatnodamagehasoccurredduring
transportation.
AnyvisibledamagemustbereportedinwritingtoMunterswithin3daysandpriortoinstallationof
theunit.
Disposeofthepackagingmaterialaccordingtolocalregulations.
3.3Storingtheequipment
CA CA
CA
UTION! UTION!
UTION!
Alwaysunplugtheunitfromthepowersupplywhennotinuse.
Followtheseinstructionsifthedehumidieristobestoredpriortoinstallation:
Placethedehumidierinanuprightpositiononahorizontalsurface.
Re-usethepackagingmaterialtoprovideprotectionfortheunit.
Protectthedehumidierfromphysicaldamage.
Storethedehumidierundercoverandprotectitfromdust,frost,rainandaggressivecontaminants.
5Transport,inspectionandstorageTEN-MCDI-B1602
DehumidierMC150
4Installation
4.1Safety
W W
W
ARNING! ARNING!
ARNING!
Donotconnecttheunittoothermainsvoltagethanspeciedontheidenticationplate.
Theunitmustbeconnectedtoanearthedelectricaloutlet.
Donotoperatetheunitifthepowerplugorcordisdamaged.
CA CA
CA
UTION! UTION!
UTION!
Donotsit,stand,orplaceanyobjectsontheunit.
NOTE!Whenadehumidierisplacedinabuildingwithradonitisnecessarytocontactanexperttosecurethe
bestoverallsolution.Allchangesaffectingtheventilationorthepressurebalanceinthebuildingcanresultina
changedconcentrationofradon.
4.2Closedsystem
Thedehumidierisplacedinthespacetobedehumidied.Thewetairistransportedoutdoorswithducting.
FortypeYtheprocessandreactivationairistakenfromthespacetobedehumidied.FortypeXthe
reactivationairistakenfromtheoutside,seeguresbelow.Toensurethatthedryairisdistributedevenlyin
thespacetobedehumidiedaductingcanbeconnectedtothedryairoutletofthedehumidier.
Aclosedsystemispreferablewhenthereisaneedfordehumidicationtoaverydryclimate.Itismore
economicaltoruncomparedtoanopensystem.
Figure4.1Closedsystemprinciple,typeYFigure4.2Closedsystemprinciple,typeX
1.Process/Reactivationair
2.Dryair
3.Wetair
1.Processair
2.Dryair
3.Wetair
4.Reactivationair
TEN-MCDI-B1602Installation6
DehumidierMC150
4.3Opensystem
Thedehumidierisplacedoutsidetheareatobedehumidied.Dryairistransportedwithductingtothe
spacetobedehumidiedandthewetairisdischargedinthevicinityoftheunitormovedoutdoors,see
guresbelow .Theinstallationisusedtosolvethefollowingproblems:
-Whenmoisturedamagedobjectsaretobedehumidied.
-Dustorcorrosioncausingparticlesarepresentinaspacewheredryairwillbesupplied.
-Topreventmoisturefromenteringthedehumidiedspace/object.
Figure4.3Opensystemprinciple,typeYFigure4.4Opensystemprinciple,typeX
1.Process/Reactivationair
2.Dryair
3.Wetair
1.Processair
2.Dryair
3.Wetair
4.Reactivationair
4.4Siterequirements
Thedehumidierisonlyintendedforindoorinstallation.Avoidinstallingthedehumidierinadamp
environmentwherethereisariskofwaterenteringtheunitorinaverydustyenvironment.Ifindoubt,
seekadvicefromMunters.Itisimportantthattheintendedinstallationsitemeetsthelocationandspace
requirementsfortheequipmentinordertoachievethebestpossibleperformanceandtrouble-free
operation.Forspacerequirements,seesection8.1,Dimensionsandservicespace.
Ifthedehumidierisintendedtobeplacedonabracketwerecommendourspeciallydesignedwallbracket.
Alwaysleaveminimum10cmspacebetweentheunitandthewall.
7InstallationTEN-MCDI-B1602
DehumidierMC150
4.5Ductsandhoses
Wheninstallingductworkbetweenthedehumidierandtheinletandoutletconnections,thefollowing
recommendationsshouldbeobserved:
Ductlengthmustbekeptasshortaspossibletominimisestaticpressureloss.
Allductandhoseconnectionsmustbeairtightandvapourtighttoensurefullperformance.
Theductingmustalwaysbeinsulatedwhenthereisariskoffreezing.
Thetotalresistanceintheductworkmustnotexceedtheperformanceratingofthefansttedinthe
dehumidier.
NOTE!Maximumlengthofdryairhoseis25metres.
NOTE!Maximumlengthofwetairhoseis6metres.
4.5.1Ductworkforoutdoorairinlet
Whenbringingoutsideambientairintothedehumidier,theopeningtotheinletductshouldbelocated
sufcientlyhighabovegroundleveltopreventthepickupofdustanddebris.Theductingshouldbe
designedtopreventrainandsnowfrombeingdrawnintothedehumidier.Theairinletmustbelocated
awayfrompossiblecontaminantssuchasengineexhaustgases,steamandharmfulvapours.
Fastenwirenettingwithameshwidthofapproximately10mmintheouterendoftheduct.
4.5.2Ductworkforwetairoutlet
Wetairductingmustbeincorrosion-resistantmaterialandmustbecapableofwithstandingtemperatures
upto80°C.
Thewetairductingmustalwaysbeinsulatedifthereisariskoffreezing.Thewetairleavingthedehumidier
willeasilycausecondensationontheinsideoftheductwallsduetothehighmoisturecontent.
NOTE!Horizontalductsmustbeinstalledwithaslightdecline(awayfromthedehumidier)todrainpossible
condensation.Thedeclinemustbeatleast2cm/metreofduct.Drainageholes(5mm)shouldbemadeatlow
pointsoftheducttopreventwateraccumulationwhichcandamagethemachine.
Fastenwirenettingwithameshwidthofapproximately10mmintheouterendoftheduct.
Wetairhosesareusuallyguidedoutdoors.Inlargepremiseswherethedehumidierisoutsideofthespace
tobedehumidied,thewetairmustbeductedawayfromtheunitwithahoseofminimumlength2metres.
Makesurethatthewetairisnotsuckedbackintotheunitandthatthewetairdoesnotblowagainstmoisture
sensitiveobjects.
TEN-MCDI-B1602Installation8
DehumidierMC150
4.6Electricalconnections
Thedehumidierisdeliveredwitha5metrepowercable,equippedwithanearthedplug.Themainelectrical
componentsareinstalledintheupperpartoftheunit.
CA CA
CA
UTION! UTION!
UTION!
Donotconnecttheunittoothermainsvoltagethanspeciedontheidenticationplate.
NOTE!Incaseofaxedinstallationwheretheplugisreplacedbyacircuitbreaker,checkthatthefuserating
inthecircuitbreakeriscorrect.
4.7Expandingthesystem
TheMC150YD/XDareequippedwithtwoM12connectors,placedatthebackbythepowersupplycable
inlet,allowingforexternalaccessoriestobeconnectedandusedwiththedehumidier.
9InstallationTEN-MCDI-B1602
DehumidierMC150
4.8Accessories
Thefollowingaccessoriesareavailableasoptionstothedehumidier.
WallBracket.Theunitcanbemountedonthewall.
Externalpanelmountallowingthecontrolpanelofthe
dehumidiertobemovedtoasuitablelocationfromwhere
thedehumidiercanbecomfortablycontrolled.
ExternalHumidistatRH15fordehumidicationcontrol.
MCDAdapterCableallowinguseofHumidistatwith4–pin
AmphenolconnectortobeconnectedtooneoftheM12
connectorsonthedehumidier.
ExternalRHTsensor,RelativeHumidityandTemperature
sensorformonitoringandcontrol.
DigitalGateway,toallowremotecontrolandmonitoringof
thedehumidicationthroughanalogueordigitalcontrol
systemssuchasModBusRTU,ModBusTCPandEthernet.
TEN-MCDI-B1602Installation10
DehumidierMC150
5Operation
5.1Safety
W W
W
ARNING! ARNING!
ARNING!
Donotoperatetheunitifthepowerplugorcordisdamaged.
Donotinsertngersoranyobjectsintotheairvents.
Theunitwillrestartautomaticallyandwithoutwarningfollowingapowerfailure.
CA CA
CA
UTION! UTION!
UTION!
Donotsit,stand,orplaceanyobjectsontheunit.
5.2Menusandoperation
5.2.1Operatorpanel
Whentheinstallationisnished,connectthedehumidiertomainspowerandsettheON/OFFswitch
toON.
TheMC150dehumidierserieshasaneasilyunderstooduserinterfacewithadisplayandvebuttons.
Therightandleftbuttonsontherespectivesidesofthedisplayareonlyusedtonavigatethemainmenu.
Nochangestothesetupcanbemadewiththesebuttons.
Thethreesmallerbuttonsbelowthedisplayareusedforselectionandediting.Theirrespective
functionsarealwayspresentedintextatthebottomofthescreen.Inthemainmenu,theleftofthese
buttonsisnamedHomeandpressingthisbuttonwillimmediatelyleadbacktothedefaultview .Inmany
oftheviewsthereisanInfobuttonwhichpresentsinformationthatcanbeofusetotheinexperienced
user.
Ifthebacklightofthedisplayhastimedout,pressinganybuttonservesonlytolightupthedisplay.
IfselectedunderSetupandMaintenance,thekeypadlockwillautomaticallyswitchon10minutesafterthe
lastpressofabutton.Thedehumidieristhenunlockedbysimultaneouslypressingthetwoupperbuttons
asispresentedingraphicsonthescreen.
11OperationTEN-MCDI-B1602
DehumidierMC150
5.2.2Defaultview
NOTE!Sidebuttons(left/right)areusedtonavigatethemenus.
Buttonsbelowthedisplayareusedforthefunctionsdisplayedintheblackhighlightedareaatthebottomofthe
screen.
1.DigitalGateway
VisiblewhenthemachineisconnectedtoDigitalGatewayforremotemonitoringandcontrol.
2.Networkstatus
“Master”or“Slaved”.Ifthedehumidierisconnectedtoalocalnetwork,thispositionindicates
whetherthedehumidieriscontrollingthenetwork,Master,orifitiscontrolledbyanother
dehumidierandthusSlaved.
3.Timer
VisiblewhenthedehumidierissettooperateonTimer.
4.Alarm
Thedehumidierhasdetectedanerror.
5.Dehumidicationindicator
Movingwhendehumidicationison-going.
6.Fanindicator
Movingwhenfanisrunning.
7.Controlmode
Indicateshowthedryingiscontrolled,ifitiscontinuous(MAN-manual)orifitoperatestodened
setpointRelativeHumidity,RH,mixingratio,MIXorDewpoint,DEW .Itcanalsobecontrolledby
externalhumidistat,HYG.IfexternalRelativeHumidityandtemperaturesensorisused,thisposition
readsE.RH,E.MIXorE.DEW .
8.Fanmode
Ifnothingisdisplayed,fanonlyoperateswhendryingisrequired.
CONT-continuousfan.
INT-intermittentfan.
TEN-MCDI-B1602Operation12
DehumidierMC150
9.Currentvaluesandsetpointvalue
Currentvaluesfollowedby,ifapplicable,thecontrolmodesetpointwhichishighlightedwithblack
background.Thevaluespresentedarefromthesensorthatiscurrentlyusedforcontrolofthe
dehumidier,theinternalRHTsensoror,fortheexternalcontrolmodes,theexternalRHTsensor.
10.Setpointadjustment
Indicatesthattheouterbuttonsbelowthedisplayareinthiscaseusedtoincreaseanddecreasethe
setpoint,highlightedwithblackbackground.
13OperationTEN-MCDI-B1602
DehumidierMC150
5.2.3Mainmenu
Fromthedefaultview,navigatethemainmenuusingtherightandleftarrows.
Startupview
Whenthedehumidierstartsup,thedisplaypresentsthe
userwithtwooptions:
Start:Startsthedehumidierwithdefaultsettings.
Resume:Thedehumidierresumesoperationwiththe
settingsithadlasttimeitwasused.
Iftheuserneverpressedstopbeforethepowerwascutthe
lasttimeitwasused,thedehumidierwillautomatically
resumeoperationwhenthecountdownhasreachedzero.
PressingthePausebuttonwillstopthecountdownandthe
dehumidierwillremaininstandbyuntilmanuallystarted.
Figure5.1Normalstart
Figure5.2Startafterpowerout,automaticresume
ofoperation
DefaultView
Whenthedehumidierisoperating,itcanalwaysbe
stopped,settostandby,bypressingthecenterbutton
belowthedisplay.
Pressingtherightorleftbuttonsnavigatesthroughthe
mainmenu.
Whenthedehumidierisrunningwithacontrolmode
otherthanMAN,manual,thesetpointvaluewhichis
highlightedwithblackbackgroundatthecenterofthe
screencanbeincreasedanddecreasedbyuseoftheminus
(-)andplus(+)buttonsrespectively.
Figure5.3Defaultscreenpictures
TEN-MCDI-B1602Operation14
DehumidierMC150
Controlmode
TheControlModedetermineswhetherthedryingshall
becontinuous(MANmanualmode)orifitshalloperate
onlywhenrequiredasdeterminedbytheambientclimate.
Theselectedcontrolmodeisdisplayedinthelowerleft
cornerofthedefaultview.
TheControlModeselectionscreenisreachedbypressing
theupperrightbutton.
Thefollowingbasiccontrolmodesareavailable:
MANManual,continuousdrying
RHDryingdowntoselectableRelativeHumidity,%
MIXDryingdowntoselectablemixingratio,g/kg
DEWDryingdowntoselectabledewpoint,°C
HYGDryingcontrolledbyexternalhumidistat
connectedtothedehumidier
Throughitsnetworkcapabilities,thedehumidiercanalso
connecttoexternalRHTsensorsandusetheirvaluesto
controltheoperationratherthanusingthebuilt-inRelative
HumidityandTemperaturesensor.Forthispurposethere
arealsothefollowingExternalsensormodes:
E.RHDryingdowntoselectableRelativehumidity,%
asgivenbyexternalRHTsensor(s)connectedto
thedehumidier.
E.MIXDryingdowntoselectablemixingratio,g/kg
asgivenbyexternalsensor(s)connectedtothe
dehumidier.
E.DEWDryingdowntoselectabledewpoint,°Cas
givenbyexternalRHTsensor(s)connectedto
thedehumidier.
TheExternalcontrolmodesrequirethedehumidierto
benetworkedandconnectedtoanexternalRHTsensor.
Ifthedehumidierisnotnetworkedalready,itwillaskifit
shallcreateanetwork.
Iftherearemultiplesensorsinthenetworkandalternative
<All>isselectedratherthanoneuniquesensor,e.g.
RHT61,thedehumidierapplies“worstcase”and
operatesaslongasanyoneofthesensorsreadahumidity
abovethesetpoint.
15OperationTEN-MCDI-B1602
DehumidierMC150
WhenselectingamodeotherthanMAN,thedehumidier
presentstheuserwiththepossibilityofselectingthe
setpoint.
Whenthesetpointlevelisreached,thedryingautomatically
stops.Ifthehumiditylateronrisesabovethesetpointlevel,
thedryingoperationisautomaticallyresumed.
Hysteresis
WhenselectingRH,DEWorMIXcontrolmodes,thereis
asymbolandahysteresisvaluepresentedtotherightinthe
display.
Thesymbolindicatesthepositionofthesetpointinthe
operationspanaspresentedbelow .
-center
-bottom
-top
Alarm
WhenselectingacontrolmodeotherthanMan(Manual),
theusercanchoosetodeneahumiditylevelthat,if
reached,shalltriggeranalarm.
Thealarmissetwithreferencetothehumiditylevelat
whichthedehumidierstartsdrying.Toassisttheuserthe
absolutelevelatwhichthealarmwilltriggerispresented
withinparenthesesatthebottomrightofthescreen.
Thisalarmisavailableformonitoringalsothroughthe
DigitalGateway.
FanMode
TheFanmodedetermineswhetherthefaninthe
dehumidiershalloperatecontinuouslyorifitshalloperate
onlywhendryingisrequiredandongoing.
Ifcontinuousfanisselected,thewordCONTispresented
inthelowerrightcornerofthedefaultscreen.
Ifpossible,foroptimaldryingeffect,usecontinuousfanto
keeptheairinconstantmotion.
ThereisalsoanIntermittent(Int)fanmode,wherethe
fanstartsonceeveryhourtoletthebuilt-insensormore
accuratelysensetheconditionoftheincomingprocessair.
TEN-MCDI-B1602Operation16
DehumidierMC150
Timer
Thedehumidierhasbuilt-intimerfunctionalityallowing
theusertodeterminewhenthedehumidiershalloperate.
WhentheTimerfunctionisused,thewordTimeris
presentedinthetoprightcornerofthedefaultviewascan
beseentotheright.
ToactivateTimer,presstherightarrowbuttonfourtimes
toentertheTimermenu.PressActivate.
Whenthetimerisactivated,thedehumidierasksthe
usertoverifythatitstimeanddatesettingsarecorrect.If
so,pressOK.Ifchangesarerequired,pressedittodothe
requiredchangesbeforecontinuing.
Inthenextstep,theuserisallowedtosetthetimeinterval
withinwhichthedehumidiershalloperate.
17OperationTEN-MCDI-B1602
/