Munters TEN-MCDI-B1602 Owner's manual

Type
Owner's manual
Originalinstructions
Usermanual
MC150
Digitalcontrol
Desiccantdehumidier
TEN-MCDI-B1602©MuntersEuropeAB2016
Importantuserinformation
Intendeduse
Muntersdehumidiersareintendedtobeusedforthe
dehumidicationofair.Anyotheruseoftheunit,or
usewhichiscontrarytotheinstructionsgiveninthis
manual,cancausepersonalinjuryanddamagetotheunit
andotherproperty.
Nomodicationoftheunitisallowedwithoutprior
approvalbyMunters.Attachmentorinstallation
ofadditionaldevicesisonlyallowedafterwritten
agreementbyMunters.
Warranty
Thewarrantyperiodisvalidfromthedatetheunit
leftourfactory,unlessotherwisestatedinwriting.
Thewarrantyislimitedtoafreeexchangeofpartsor
componentswhichhavefailedasaresultofdefectsin
materialsorworkmanship.
Allwarrantyclaimsmustincludeproofthatthefaulthas
occurredwithinthewarrantyperiodandthattheunit
hasbeenusedinaccordancewiththespecications.All
claimsmustspecifytheunittypeandserialnumber.This
informationisstampedontheidenticationlabel.
Itisaconditionofthewarrantythattheunitforthe
fullwarrantyperiodisservicedandmaintainedas
describedinsectionServiceandmaintenance.Theservice
andmaintenancemustbedocumentedforthewarranty
tobevalid.
Safety
Informationaboutdangersareinthismanualindicated
bythecommonhazardsymbol:
W W
W
ARNING! ARNING!
ARNING!
Indicatesapossibledangerthatcanleadtopersonalinjury.
CA CA
CA
UTION! UTION!
UTION!
Indicatesapossibledangerthatcanleadtodamagetothe
unitorotherproperty,orcauseenvironmentaldamage.
NOTE!Highlightssupplementaryinformationforoptimal
useoftheunit.
ConformitywithDirectives
Thedehumidierisinconformitywiththeessential
safetyrequirementsoftheMachineryDirective
2006/42/EC,theRoHSDirective2011/65/EUandthe
EMCDirective2004/108/EC.
Copyright
Thecontentsofthismanualcanbechangedwithout
priornotice.
NOTE!Thismanualcontainsinformationwhichis
protectedbycopyrightlaws.Itisnotallowedtoreproduceor
transmitanypartofthismanualwithoutwrittenconsentfrom
Munters.
Sendanycommentsregardingthismanualto:
MuntersEuropeAB
TechnicalDocumentation
P.O.Box1150
SE-16426KISTASweden
iiImportantuserinformationTEN-MCDI-B1602
Tableofcontents
Importantuserinformation...............ii
Intendeduse...........................
ii
Warranty...............................
ii
Safety..................................
ii
ConformitywithDirectives............
ii
Copyright..............................
ii
Tableofcontents...........................iii
1Introduction.................................1
1.1Aboutthismanual.....................
1
1.2Unintendeduse........................
1
1.3Safety..................................
1
2Functiondescription.......................4
3Transport,inspectionandstorage.......5
3.1Transport..............................
5
3.2Inspectionofdelivery..................
5
3.3Storingtheequipment................
5
4Installation...................................6
4.1Safety..................................
6
4.2Closedsystem.........................
6
4.3Opensystem..........................
7
4.4Siterequirements.....................
7
4.5Ductsandhoses.......................
8
4.5.1Ductworkforoutdoorairinlet..
8
4.5.2Ductworkforwetairoutlet.....
8
4.6Electricalconnections................
9
4.7Expandingthesystem................
9
4.8Accessories...........................
10
5Operation....................................11
5.1Safety..................................
11
5.2Menusandoperation..................
11
5.2.1Operatorpanel.................
11
5.2.2Defaultview....................
12
5.2.3Mainmenu.....................
14
5.2.4Controloptions.................
22
5.2.5Alarms..........................
23
5.3Network................................
24
5.3.1Networkfunctions.............
24
5.3.2Howtonetworkdehumidiers
24
6Serviceandmaintenance.................26
6.1General................................
26
6.2Maintenanceschedule................
26
6.3Filterreplacement.....................
26
7Faulttracing.................................27
8Technicalspecication....................28
8.1Dimensionsandservicespace.......
28
8.2Capacitydiagram.....................
29
8.3Fancurveprocessair.................
30
8.4Fancurvereactivationair.............
31
8.5Technicaldata.........................
32
9Scrapping....................................33
10ContactMunters............................34
TEN-MCDI-B1602Tableofcontentsiii
DehumidierMC150
1Introduction
1.1Aboutthismanual
Thismanualiswrittenfortheuserofthedehumidier.Itcontainsnecessaryinformationforhowtoinstall
andusethedehumidierinasafeandefcientway.Readthroughthemanualbeforethedehumidieris
installedandused.
ContactyournearestMuntersofceifyouhaveanyquestionsregardingtheinstallationortheuseofyour
dehumidier.
Thismanualmustbestoredinapermanentlocationclosetothedehumidier.
1.2Unintendeduse
Thedehumidierisnotintendedforoutdoorinstallation.
Thedehumidierisnotintendedforuseinclassiedareaswhereexplosionsafetycompliantequipment
isrequired.
Thedehumidiermustnotbeinstallednearanyheatgeneratingdevicesthatcancausedamagetothe
equipment.
NOTE!Whenadehumidierisplacedinabuildingwithradonitisnecessarytocontactanexperttosecurethe
bestoverallsolution.Allchangesaffectingtheventilationorthepressurebalanceinthebuildingcanresultina
changedconcentrationofradon.
CA CA
CA
UTION! UTION!
UTION!
Donotsit,stand,orplaceanyobjectsontheunit.
1.3Safety
Everymeasurehasbeentakeninthedesignandmanufactureofthedehumidiertoensurethatitmeetsthe
safetyrequirementsofthedirectivesandstandardslistedintheECDeclarationofConformity.
Theinformationinthismanualshallinnowaytakeprecedenceoverindividualresponsibilitiesorlocal
regulations.
Duringoperationandotherworkwithamachineitisalwaystheresponsibilityoftheindividualtoconsider:
Thesafetyofallpersonsconcerned.
Thesafetyoftheunitandotherproperty.
Theprotectionoftheenvironment.
ThetypesofdangersthatareindicatedinthismanualaredescribedinsectionImportantuserinformation.
Thisequipmentcanbeusedbychildrenagedeight(8)yearsoraboveandpeoplewithreducedphysical,
sensoryormentalcapabilitiesorwithlackofexperienceandknowledgeprovidedtheyhavebeengiven
instructionsandinformationonhowitissafelyusedandthattheyunderstandthehazardsinvolved.
1IntroductionTEN-MCDI-B1602
DehumidierMC150
W W
W
ARNING! ARNING!
ARNING!
-Theunitmustnotbeinstalledoutdoors.
-Theunitmustnotbesplashedwithorimmersedinwater.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Theunitmustbeconnectedtoanearthedelectricaloutlet.
-Donotconnecttheunittoothermainsvoltagethanspeciedontheidenticationplate.
Maxoutletfuse230VAC:16A.
-Donotoperatetheunitifthepowerplugorcordisdamaged,riskofelectricalshock.
-Donotpulltheplugwithwethands,riskofelectricalshock.
-Donotinsertngersoranyobjectsintotheairvents,rotatingfansareinside.
-Donotcovertheunitasthatcanblockairintakeoroutletandcauseare.
-Iftheunithasoverturned,cutthepowerimmediately.
-Thedehumidiermustnotbepowereduntiltheinstallationisnishedinaccordancewiththismanual.
-Aresidual-currentdevice/groundfaultcircuitinterruptershouldbeusedtominimizetheriskofelectricshocks.
-Nevercarryorpullthedehumidierbyitscable.
-Theunitmustnotbeusedinclassiedareaswhereexplosionsafetycompliantequipmentisrequiredorwhere
explosivegasescouldstillbepresent.
-Theunitwillrestartautomaticallyandwithoutwarningfollowingapowerfailure.
-Thedehumidiermustneverbeusedwithanyotheraccessoriesthanthoselistedinthismanual.
-Donotattempttorepair,dismantleormodifythisunit.
-Theunitmustnotbeopenedbyanyoneotherthantrainedandqualiedpersonnel,duetotheriskofelectrical
shock.
-AlwayscontactMuntersforserviceorrepair.
-Operatingfaultscanoccuriftheunitismaintainedinsufcientlyorincorrectly.
-Iftherotoristobecutinpieces,wearasuitableCEmarkedfacemaskselectedandttedinaccordancewiththe
applicablesafetystandardstoprotectfromthedust.
TEN-MCDI-B1602Introduction2
DehumidierMC150
CA CA
CA
UTION! UTION!
UTION!
-Thedehumidiermustnotbeinstallednearanyheatgeneratingdevicesthatcancausedamagetothe
equipment.
-Removethemainsplugfromthesocketbeforestartinganymaintenancework.
-Alwaysunplugtheunitfromthepowersupplywhennotinuse.
-Thedehumidiermustbeplacedsteadilyandmustnotbeusedtosit,standorplaceobjectson.
-Basesororganicmaterialwithhighboilingpointsuchasoil,grease,solvents,boracolorsimilarsubstancesmust
notbedrawnintothedehumidier.Theycandamagetherotor.
-Neverusethedehumidierwithoutthelterinstalledasthiscancausedamagetoit.Ensurethatthelterisclean.
Aclutteredltercancausethedehumidiertooverheat.
-Allchangesaffectingtheventilationorthepressurebalanceinthebuildingcanresultinachangedconcentration
ofradon.Iftheunitisplacedinabuildingwithradon,itisnecessarytocontactanexperttosecurethebestoverall
solution.
-Donotunplugthedehumidierwhileitiscoolingdown.Unpluggingitcanleadtopermanentunitdamage.
-Onlyquickstopthedehumidierincaseofemergency.Thefanstopsandtheheatercanbeveryhot,whichcan
resultindamagetotheheaterandothercomponentsclosetoit.
-Donotusetheairconnectionsforliftingtheunit.
3IntroductionTEN-MCDI-B1602
DehumidierMC150
2Functiondescription
Thedesiccantrotoristheadsorptiondehumidifyingcomponentintheunit.Therotorstructureis
comprisedofalargenumberofsmallairchannels.
Thedesiccantrotorismadeofacompositematerialthatishighlyeffectiveinattractingandretainingwater
vapour.Therotorisdividedintwozones.Theairowtobedehumidied,processair,passesthroughthe
largestzoneoftherotorandthenleavestherotorasdryair.Sincetherotorrotatesslowly,theincomingair
alwaysmeetsadryzoneontherotor,thuscreatingacontinuousdehumidicationprocess.
Theairowthatisusedtodrytherotor,reactivationair,isheated.Thereactivationairpassesthrough
therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair(warm,moistair).This
principleenablesthedehumidiertoworkeffectively,evenatfreezingtemperatures.
TypeYusesoneinletairowforprocessairandforreactivationoftherotor.
TypeXusesaseparateinletairowforreactivationoftherotor.
Figure2.1TypeY
1.Process/Reactivationair
2.Dryair
3.Wetair
Figure2.2TypeX
1.Processair
2.Dryair
3.Wetair
4.Reactivationair
TEN-MCDI-B1602Functiondescription4
DehumidierMC150
3Transport,inspectionandstorage
3.1Transport
Transportthedehumidierintheoriginalpackaging.Theunitmustalwaysbeplacedinanuprightposition
duringtransport.Failuretocomplywiththiscancausetheunittomalfunction.
CA CA
CA
UTION! UTION!
UTION!
Donotusetheairconnectionsforliftingtheunit.
3.2Inspectionofdelivery
Inspectthedeliveryandcomparewiththedeliverynote,orderconrmationorotherdelivery
documentation.Makesurethateverythingisincludedandnothingisdamaged.
ContactMuntersimmediatelyifthedeliveryisnotcompleteordamagedinordertoavoidinstallation
delays.
Removeallpackagingmaterialfromtheunit,andmakesurethatnodamagehasoccurredduring
transportation.
AnyvisibledamagemustbereportedinwritingtoMunterswithin3daysandpriortoinstallationof
theunit.
Disposeofthepackagingmaterialaccordingtolocalregulations.
3.3Storingtheequipment
CA CA
CA
UTION! UTION!
UTION!
Alwaysunplugtheunitfromthepowersupplywhennotinuse.
Followtheseinstructionsifthedehumidieristobestoredpriortoinstallation:
Placethedehumidierinanuprightpositiononahorizontalsurface.
Re-usethepackagingmaterialtoprovideprotectionfortheunit.
Protectthedehumidierfromphysicaldamage.
Storethedehumidierundercoverandprotectitfromdust,frost,rainandaggressivecontaminants.
5Transport,inspectionandstorageTEN-MCDI-B1602
DehumidierMC150
4Installation
4.1Safety
W W
W
ARNING! ARNING!
ARNING!
Donotconnecttheunittoothermainsvoltagethanspeciedontheidenticationplate.
Theunitmustbeconnectedtoanearthedelectricaloutlet.
Donotoperatetheunitifthepowerplugorcordisdamaged.
CA CA
CA
UTION! UTION!
UTION!
Donotsit,stand,orplaceanyobjectsontheunit.
NOTE!Whenadehumidierisplacedinabuildingwithradonitisnecessarytocontactanexperttosecurethe
bestoverallsolution.Allchangesaffectingtheventilationorthepressurebalanceinthebuildingcanresultina
changedconcentrationofradon.
4.2Closedsystem
Thedehumidierisplacedinthespacetobedehumidied.Thewetairistransportedoutdoorswithducting.
FortypeYtheprocessandreactivationairistakenfromthespacetobedehumidied.FortypeXthe
reactivationairistakenfromtheoutside,seeguresbelow.Toensurethatthedryairisdistributedevenlyin
thespacetobedehumidiedaductingcanbeconnectedtothedryairoutletofthedehumidier.
Aclosedsystemispreferablewhenthereisaneedfordehumidicationtoaverydryclimate.Itismore
economicaltoruncomparedtoanopensystem.
Figure4.1Closedsystemprinciple,typeYFigure4.2Closedsystemprinciple,typeX
1.Process/Reactivationair
2.Dryair
3.Wetair
1.Processair
2.Dryair
3.Wetair
4.Reactivationair
TEN-MCDI-B1602Installation6
DehumidierMC150
4.3Opensystem
Thedehumidierisplacedoutsidetheareatobedehumidied.Dryairistransportedwithductingtothe
spacetobedehumidiedandthewetairisdischargedinthevicinityoftheunitormovedoutdoors,see
guresbelow .Theinstallationisusedtosolvethefollowingproblems:
-Whenmoisturedamagedobjectsaretobedehumidied.
-Dustorcorrosioncausingparticlesarepresentinaspacewheredryairwillbesupplied.
-Topreventmoisturefromenteringthedehumidiedspace/object.
Figure4.3Opensystemprinciple,typeYFigure4.4Opensystemprinciple,typeX
1.Process/Reactivationair
2.Dryair
3.Wetair
1.Processair
2.Dryair
3.Wetair
4.Reactivationair
4.4Siterequirements
Thedehumidierisonlyintendedforindoorinstallation.Avoidinstallingthedehumidierinadamp
environmentwherethereisariskofwaterenteringtheunitorinaverydustyenvironment.Ifindoubt,
seekadvicefromMunters.Itisimportantthattheintendedinstallationsitemeetsthelocationandspace
requirementsfortheequipmentinordertoachievethebestpossibleperformanceandtrouble-free
operation.Forspacerequirements,seesection8.1,Dimensionsandservicespace.
Ifthedehumidierisintendedtobeplacedonabracketwerecommendourspeciallydesignedwallbracket.
Alwaysleaveminimum10cmspacebetweentheunitandthewall.
7InstallationTEN-MCDI-B1602
DehumidierMC150
4.5Ductsandhoses
Wheninstallingductworkbetweenthedehumidierandtheinletandoutletconnections,thefollowing
recommendationsshouldbeobserved:
Ductlengthmustbekeptasshortaspossibletominimisestaticpressureloss.
Allductandhoseconnectionsmustbeairtightandvapourtighttoensurefullperformance.
Theductingmustalwaysbeinsulatedwhenthereisariskoffreezing.
Thetotalresistanceintheductworkmustnotexceedtheperformanceratingofthefansttedinthe
dehumidier.
NOTE!Maximumlengthofdryairhoseis25metres.
NOTE!Maximumlengthofwetairhoseis6metres.
4.5.1Ductworkforoutdoorairinlet
Whenbringingoutsideambientairintothedehumidier,theopeningtotheinletductshouldbelocated
sufcientlyhighabovegroundleveltopreventthepickupofdustanddebris.Theductingshouldbe
designedtopreventrainandsnowfrombeingdrawnintothedehumidier.Theairinletmustbelocated
awayfrompossiblecontaminantssuchasengineexhaustgases,steamandharmfulvapours.
Fastenwirenettingwithameshwidthofapproximately10mmintheouterendoftheduct.
4.5.2Ductworkforwetairoutlet
Wetairductingmustbeincorrosion-resistantmaterialandmustbecapableofwithstandingtemperatures
upto80°C.
Thewetairductingmustalwaysbeinsulatedifthereisariskoffreezing.Thewetairleavingthedehumidier
willeasilycausecondensationontheinsideoftheductwallsduetothehighmoisturecontent.
NOTE!Horizontalductsmustbeinstalledwithaslightdecline(awayfromthedehumidier)todrainpossible
condensation.Thedeclinemustbeatleast2cm/metreofduct.Drainageholes(5mm)shouldbemadeatlow
pointsoftheducttopreventwateraccumulationwhichcandamagethemachine.
Fastenwirenettingwithameshwidthofapproximately10mmintheouterendoftheduct.
Wetairhosesareusuallyguidedoutdoors.Inlargepremiseswherethedehumidierisoutsideofthespace
tobedehumidied,thewetairmustbeductedawayfromtheunitwithahoseofminimumlength2metres.
Makesurethatthewetairisnotsuckedbackintotheunitandthatthewetairdoesnotblowagainstmoisture
sensitiveobjects.
TEN-MCDI-B1602Installation8
DehumidierMC150
4.6Electricalconnections
Thedehumidierisdeliveredwitha5metrepowercable,equippedwithanearthedplug.Themainelectrical
componentsareinstalledintheupperpartoftheunit.
CA CA
CA
UTION! UTION!
UTION!
Donotconnecttheunittoothermainsvoltagethanspeciedontheidenticationplate.
NOTE!Incaseofaxedinstallationwheretheplugisreplacedbyacircuitbreaker,checkthatthefuserating
inthecircuitbreakeriscorrect.
4.7Expandingthesystem
TheMC150YD/XDareequippedwithtwoM12connectors,placedatthebackbythepowersupplycable
inlet,allowingforexternalaccessoriestobeconnectedandusedwiththedehumidier.
9InstallationTEN-MCDI-B1602
DehumidierMC150
4.8Accessories
Thefollowingaccessoriesareavailableasoptionstothedehumidier.
WallBracket.Theunitcanbemountedonthewall.
Externalpanelmountallowingthecontrolpanelofthe
dehumidiertobemovedtoasuitablelocationfromwhere
thedehumidiercanbecomfortablycontrolled.
ExternalHumidistatRH15fordehumidicationcontrol.
MCDAdapterCableallowinguseofHumidistatwith4–pin
AmphenolconnectortobeconnectedtooneoftheM12
connectorsonthedehumidier.
ExternalRHTsensor,RelativeHumidityandTemperature
sensorformonitoringandcontrol.
DigitalGateway,toallowremotecontrolandmonitoringof
thedehumidicationthroughanalogueordigitalcontrol
systemssuchasModBusRTU,ModBusTCPandEthernet.
TEN-MCDI-B1602Installation10
DehumidierMC150
5Operation
5.1Safety
W W
W
ARNING! ARNING!
ARNING!
Donotoperatetheunitifthepowerplugorcordisdamaged.
Donotinsertngersoranyobjectsintotheairvents.
Theunitwillrestartautomaticallyandwithoutwarningfollowingapowerfailure.
CA CA
CA
UTION! UTION!
UTION!
Donotsit,stand,orplaceanyobjectsontheunit.
5.2Menusandoperation
5.2.1Operatorpanel
Whentheinstallationisnished,connectthedehumidiertomainspowerandsettheON/OFFswitch
toON.
TheMC150dehumidierserieshasaneasilyunderstooduserinterfacewithadisplayandvebuttons.
Therightandleftbuttonsontherespectivesidesofthedisplayareonlyusedtonavigatethemainmenu.
Nochangestothesetupcanbemadewiththesebuttons.
Thethreesmallerbuttonsbelowthedisplayareusedforselectionandediting.Theirrespective
functionsarealwayspresentedintextatthebottomofthescreen.Inthemainmenu,theleftofthese
buttonsisnamedHomeandpressingthisbuttonwillimmediatelyleadbacktothedefaultview .Inmany
oftheviewsthereisanInfobuttonwhichpresentsinformationthatcanbeofusetotheinexperienced
user.
Ifthebacklightofthedisplayhastimedout,pressinganybuttonservesonlytolightupthedisplay.
IfselectedunderSetupandMaintenance,thekeypadlockwillautomaticallyswitchon10minutesafterthe
lastpressofabutton.Thedehumidieristhenunlockedbysimultaneouslypressingthetwoupperbuttons
asispresentedingraphicsonthescreen.
11OperationTEN-MCDI-B1602
DehumidierMC150
5.2.2Defaultview
NOTE!Sidebuttons(left/right)areusedtonavigatethemenus.
Buttonsbelowthedisplayareusedforthefunctionsdisplayedintheblackhighlightedareaatthebottomofthe
screen.
1.DigitalGateway
VisiblewhenthemachineisconnectedtoDigitalGatewayforremotemonitoringandcontrol.
2.Networkstatus
“Master”or“Slaved”.Ifthedehumidierisconnectedtoalocalnetwork,thispositionindicates
whetherthedehumidieriscontrollingthenetwork,Master,orifitiscontrolledbyanother
dehumidierandthusSlaved.
3.Timer
VisiblewhenthedehumidierissettooperateonTimer.
4.Alarm
Thedehumidierhasdetectedanerror.
5.Dehumidicationindicator
Movingwhendehumidicationison-going.
6.Fanindicator
Movingwhenfanisrunning.
7.Controlmode
Indicateshowthedryingiscontrolled,ifitiscontinuous(MAN-manual)orifitoperatestodened
setpointRelativeHumidity,RH,mixingratio,MIXorDewpoint,DEW .Itcanalsobecontrolledby
externalhumidistat,HYG.IfexternalRelativeHumidityandtemperaturesensorisused,thisposition
readsE.RH,E.MIXorE.DEW .
8.Fanmode
Ifnothingisdisplayed,fanonlyoperateswhendryingisrequired.
CONT-continuousfan.
INT-intermittentfan.
TEN-MCDI-B1602Operation12
DehumidierMC150
9.Currentvaluesandsetpointvalue
Currentvaluesfollowedby,ifapplicable,thecontrolmodesetpointwhichishighlightedwithblack
background.Thevaluespresentedarefromthesensorthatiscurrentlyusedforcontrolofthe
dehumidier,theinternalRHTsensoror,fortheexternalcontrolmodes,theexternalRHTsensor.
10.Setpointadjustment
Indicatesthattheouterbuttonsbelowthedisplayareinthiscaseusedtoincreaseanddecreasethe
setpoint,highlightedwithblackbackground.
13OperationTEN-MCDI-B1602
DehumidierMC150
5.2.3Mainmenu
Fromthedefaultview,navigatethemainmenuusingtherightandleftarrows.
Startupview
Whenthedehumidierstartsup,thedisplaypresentsthe
userwithtwooptions:
Start:Startsthedehumidierwithdefaultsettings.
Resume:Thedehumidierresumesoperationwiththe
settingsithadlasttimeitwasused.
Iftheuserneverpressedstopbeforethepowerwascutthe
lasttimeitwasused,thedehumidierwillautomatically
resumeoperationwhenthecountdownhasreachedzero.
PressingthePausebuttonwillstopthecountdownandthe
dehumidierwillremaininstandbyuntilmanuallystarted.
Figure5.1Normalstart
Figure5.2Startafterpowerout,automaticresume
ofoperation
DefaultView
Whenthedehumidierisoperating,itcanalwaysbe
stopped,settostandby,bypressingthecenterbutton
belowthedisplay.
Pressingtherightorleftbuttonsnavigatesthroughthe
mainmenu.
Whenthedehumidierisrunningwithacontrolmode
otherthanMAN,manual,thesetpointvaluewhichis
highlightedwithblackbackgroundatthecenterofthe
screencanbeincreasedanddecreasedbyuseoftheminus
(-)andplus(+)buttonsrespectively.
Figure5.3Defaultscreenpictures
TEN-MCDI-B1602Operation14
DehumidierMC150
Controlmode
TheControlModedetermineswhetherthedryingshall
becontinuous(MANmanualmode)orifitshalloperate
onlywhenrequiredasdeterminedbytheambientclimate.
Theselectedcontrolmodeisdisplayedinthelowerleft
cornerofthedefaultview.
TheControlModeselectionscreenisreachedbypressing
theupperrightbutton.
Thefollowingbasiccontrolmodesareavailable:
MANManual,continuousdrying
RHDryingdowntoselectableRelativeHumidity,%
MIXDryingdowntoselectablemixingratio,g/kg
DEWDryingdowntoselectabledewpoint,°C
HYGDryingcontrolledbyexternalhumidistat
connectedtothedehumidier
Throughitsnetworkcapabilities,thedehumidiercanalso
connecttoexternalRHTsensorsandusetheirvaluesto
controltheoperationratherthanusingthebuilt-inRelative
HumidityandTemperaturesensor.Forthispurposethere
arealsothefollowingExternalsensormodes:
E.RHDryingdowntoselectableRelativehumidity,%
asgivenbyexternalRHTsensor(s)connectedto
thedehumidier.
E.MIXDryingdowntoselectablemixingratio,g/kg
asgivenbyexternalsensor(s)connectedtothe
dehumidier.
E.DEWDryingdowntoselectabledewpoint,°Cas
givenbyexternalRHTsensor(s)connectedto
thedehumidier.
TheExternalcontrolmodesrequirethedehumidierto
benetworkedandconnectedtoanexternalRHTsensor.
Ifthedehumidierisnotnetworkedalready,itwillaskifit
shallcreateanetwork.
Iftherearemultiplesensorsinthenetworkandalternative
<All>isselectedratherthanoneuniquesensor,e.g.
RHT61,thedehumidierapplies“worstcase”and
operatesaslongasanyoneofthesensorsreadahumidity
abovethesetpoint.
15OperationTEN-MCDI-B1602
DehumidierMC150
WhenselectingamodeotherthanMAN,thedehumidier
presentstheuserwiththepossibilityofselectingthe
setpoint.
Whenthesetpointlevelisreached,thedryingautomatically
stops.Ifthehumiditylateronrisesabovethesetpointlevel,
thedryingoperationisautomaticallyresumed.
Hysteresis
WhenselectingRH,DEWorMIXcontrolmodes,thereis
asymbolandahysteresisvaluepresentedtotherightinthe
display.
Thesymbolindicatesthepositionofthesetpointinthe
operationspanaspresentedbelow .
-center
-bottom
-top
Alarm
WhenselectingacontrolmodeotherthanMan(Manual),
theusercanchoosetodeneahumiditylevelthat,if
reached,shalltriggeranalarm.
Thealarmissetwithreferencetothehumiditylevelat
whichthedehumidierstartsdrying.Toassisttheuserthe
absolutelevelatwhichthealarmwilltriggerispresented
withinparenthesesatthebottomrightofthescreen.
Thisalarmisavailableformonitoringalsothroughthe
DigitalGateway.
FanMode
TheFanmodedetermineswhetherthefaninthe
dehumidiershalloperatecontinuouslyorifitshalloperate
onlywhendryingisrequiredandongoing.
Ifcontinuousfanisselected,thewordCONTispresented
inthelowerrightcornerofthedefaultscreen.
Ifpossible,foroptimaldryingeffect,usecontinuousfanto
keeptheairinconstantmotion.
ThereisalsoanIntermittent(Int)fanmode,wherethe
fanstartsonceeveryhourtoletthebuilt-insensormore
accuratelysensetheconditionoftheincomingprocessair.
TEN-MCDI-B1602Operation16
DehumidierMC150
Timer
Thedehumidierhasbuilt-intimerfunctionalityallowing
theusertodeterminewhenthedehumidiershalloperate.
WhentheTimerfunctionisused,thewordTimeris
presentedinthetoprightcornerofthedefaultviewascan
beseentotheright.
ToactivateTimer,presstherightarrowbuttonfourtimes
toentertheTimermenu.PressActivate.
Whenthetimerisactivated,thedehumidierasksthe
usertoverifythatitstimeanddatesettingsarecorrect.If
so,pressOK.Ifchangesarerequired,pressedittodothe
requiredchangesbeforecontinuing.
Inthenextstep,theuserisallowedtosetthetimeinterval
withinwhichthedehumidiershalloperate.
17OperationTEN-MCDI-B1602
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40