Vega Safety barrier type 9001 is a passive component that converts a non-intrinsically safe circuit into an intrinsically safe circuit. It limits energy flow, damps capacitance and inductance, and reduces stored energy. It takes over this function, ensuring that circuits are secured and cannot ignite explosive mixtures. It provides an intrinsically safe 0–20 mA current signal for indicating instruments in hazardous areas. With galvanic separation, it is suitable for use in Ex-areas and has approvals for zone 1, zone 2, and outside Ex-areas.

Vega Safety barrier type 9001 is a passive component that converts a non-intrinsically safe circuit into an intrinsically safe circuit. It limits energy flow, damps capacitance and inductance, and reduces stored energy. It takes over this function, ensuring that circuits are secured and cannot ignite explosive mixtures. It provides an intrinsically safe 0–20 mA current signal for indicating instruments in hazardous areas. With galvanic separation, it is suitable for use in Ex-areas and has approvals for zone 1, zone 2, and outside Ex-areas.

in
in
out
out
Operating Instructions
Safety barrier type 9001
3 4
1 2
9001/01-
086/150/10
160
2 Safety barrier type 9001
29181-EN-040115
1 Application and function
Safety barrier type 9001 is a passive compo-
nent. With galvanic separation, it converts a
non-intrinsically safe circuit into an intrinsically
safe circuit.
The term „intrinsically safe“ characterizes a
circuit in which the energy flow is limited and
stored capacitive and inductive energy is
secured in such a way that neither switching
operations nor nor short-circuits can ignite an
explosive mixture.
Safety barrier type 9001 takes over this func-
tion. It limits the energy flow, damps the ca-
pacitance C
a
and the inductance L
a
of the
output circuit and reduces the stored energy
reliably. Circuits secured in this way cannot
ignite explosive mixtures.
Operating Instructions
Example:
An indicating instrument is mounted in Ex-
areas and requires an intrinsically safe
0 … 20 mA current signal.
The existing 0 20 mA signal to the indicating
instrument however, is not intrinsically safe.
Safety barrier type 9001 is connected to the
signal cable to supply the indicating instru-
ment in Ex-area with an intrinsically safe 20 mA
signal. The safety barrier then provides on its
output an intrinsically safe 0 20 mA current
signal for the indicating instrument.
Note:
The capacitance C
a
and inductance L
a
of the
output circuit resulting from the indicating
instrument and the supply cable must not
exceed the stated limit values. The standard
wiring normally ensures these values.
2 Technical data
General
Installation position outside Ex-area on carrier rail
Operating temperature -20°C … +60°C
Storage and transport temperature -20°C +75°C
Housing material Polyamide 6 GF
Cross-section area of conductor 1.5 mm
2
(terminals)
Protection acc. to IEC 60529
- terminals IP 20
- housing IP 40
Weight 115 g
Approvals
- zone 1 Ex II C 1/2G [EEx ia/ib] IIC/IIB
Ex II 3G EEx ia II T4
- zone 2 [EEx ia] II C / [EEx ia] II B
Input circuit
Nominal voltage U
N
6 V DC
Zener voltage 8.6 V
Min. series resistance R
min
64 Ohm
Max. series resistance R
max
73 Ohm
Leakage current against earth at U
N
1 µA
Output circuit
Short-circuit current I
K
150 mA
Capacitance C
a
t EEx ia IIC 6.2 µF
Inductance L
a
at EEx ia IIC 1.3 mH
Capacitance C
a
at EEx ib IIB 55 µF
Inductance L
a
at EEx ib IIB 7 mH
Safety barrier type 9001 3
29181-EN-040115
Operating Instructions
4 Mounting
Mount the safety barrier onto a carrier rail
outside of the hazardous area
Connect the potential equalisation cable
from the Ex-area to the projecting PA-termi-
nal
Connect the intrinsically safe circuit (blue)
correctly to the blue-coloured side of the
safety barrier. Note the polarity.
Now connect the non-intrinsically safe circuit
correctly to the upper white-coloured side of
the safety barrier. Wrong polarity will de-
stroy the safety barrier.
Note:
Cables in Ex-areas must have a durable blue
marking along their entire length.
Non-Ex area
Ex area
3 Dimensions
5 Electrical connection
U
N
0 … 20 mA input
circuit (non-
intrinsically safe)
0 … 20 mA output
circuit (intrinsically
safe)
e.g. indicating instru-
ment
1
6
0
1
6
0
+
6
V
0
8
6
-
1
5
0
-
1
0
9
0
0
1
/0
1
-
4
3
2
1
7
0
-
1
1
2
,2
+
0
,2
104
-1
ISO 9001
All statements concerning scope of delivery, application, practical
use and operating conditions of the sensors and processing sys-
tems correspond to the information available at the time of printing.
Technical data subject to alterations
29181-EN-040115
Safety information
Please read this manual carefully, and also take
note of country-specific installation standards
(e.g. the VDE regulations in Germany) as well
as all prevailing safety regulations and accident
prevention rules.
For safety and warranty reasons, any internal
work on the instruments, apart from that involved
in normal installation and electrical connection,
must be carried out only by qualified VEGA per-
sonnel.
VEGA Grieshaber KG
Am Hohenstein 113
77761 Schiltach
Germany
Phone (07836) 50-0
Fax (07836) 50-201
www.vega.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Vega Safety barrier type 9001 Operating instructions

Type
Operating instructions

Vega Safety barrier type 9001 is a passive component that converts a non-intrinsically safe circuit into an intrinsically safe circuit. It limits energy flow, damps capacitance and inductance, and reduces stored energy. It takes over this function, ensuring that circuits are secured and cannot ignite explosive mixtures. It provides an intrinsically safe 0–20 mA current signal for indicating instruments in hazardous areas. With galvanic separation, it is suitable for use in Ex-areas and has approvals for zone 1, zone 2, and outside Ex-areas.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI