HELIOS KWL-Center 1200 Operation And Installation Instructions

Category
Cooker hoods
Type
Operation And Installation Instructions
Operation and installation instructions no. 90728
Central ventilation with heat recovery unit KWL-Center 1200
It is important for safety reasons, that you read and observe this instruction
fully before proceeding.
RECEIPT
Please check delivery immediately on receipt for accuracy and damage, please
notifiy carrier immediately. In case of delayed notification, any possible claim may
be void.
STORAGE
When storing for a prolonged time the following steps are to be taken to avoid da-
maging influences: protection by dry air and dustproof packing (plastic bags with
drying agent and moisture indicators). The storage area must be free of water,
vibration and temperature variations.
When storing for several years or non rotation of motor an inspection of the bea-
rings with possible relubrication and an installation inspection in accordance with
VDE 0530 are absolutely necessary before starting operation. Damages due to
improper storage, transportation or installation are not liable for warranty.
OPERATION / USE
The unit is designed for the central ventilation of residential and commercial used
rooms. The unit is equipped with a heat recovery battery. It must not be connec-
ted to kitchen hoods or laboratory extract fans. The standard equipment allows a
working temperature range from -20°C up to 40°C. For operation under difficult
conditions, e.g. high humidity, long periods of standstill, high air pollution or
through climatic (e.g. operating temperature over 40°C), technical or electronic in-
fluences other than standard operations may not be suitable. For this reason plea-
se enquire and obtain operation release. A release by a third party is not valid.
MODE OF ACTION
In the heat exchanger the cold outside air and the warm extracted air "crosses
over " without touching. Through this method approx. 70% of the energy of the
warm air is tranfered to the incoming air. Additionally a thermostat controlled hea-
ting element warms up the inlet air (in extreme cold weather conditions) to the re-
quired temperature. The intake air is directed to the primary rooms, where intake
air is required, through pipes and valves. The used air is extracted from the ba-
throoms, toilets and kitchens. It flows back to the fan via the ducting systems,
transfering heat before being released into the open air.
PERFORMANCE DATA
To achieve the given performance, the unit must be correctly installed. Varying
from the design and/or by bad construction and also by incorrect operation can
lead to a reduction in the discharge capacity. Noise figures are stated as sound
power levels LWA in dB(A) (conforms to DIN 44635 T.1). Sound pressure levels
LPA depend on room specific attitudes.
INSTALLATION-ASSEMBLY (pic. 2)
The KWLC 1200 is to install vertical. As an "undercover" we recommend plaster of
chipboard on a secure mineral wool board (approx. 70 x 190 cm). The board must
be even. The KWLC has differently high consoles so that an incline arises in direc-
tion of the condensate waterflow.
The mounting of the same should use the shortest possible pipework and should
be easy to connect up. Tight bends can lead to a high pressure loss and flow noi-
se. The ductwork must not be bent. A secure and tight connection of the duct-
work has to be assured. For maintenance and installation work, the unit must be
reachable.
Before installation, take out summer-heat exchanger and operating switch
from the unit. It must be checked that the installed unit has a drop in the di-
rection of the condensate water flow.
Condensation Run-Off
The condensation spout is to be connected to the water run off by means of a
flexible pipe of 15mm diameter. If the same is not in a room which is heated, it
must be isolated. A copper drain trap is to be provided. It must have a minimum
height of 100 mm, otherwise water could be sucked back through the fan.
To avoid an odor, fill in water into the drain trap before putting into operati-
on. The regulations of the water board and other legislation must be obser-
ved.
Air ducting, Ventilation circuit
When designing the ductwork, try to achieve the shortest possible runs. To avoid
the collecting of dirt, pressure loss and noise, use smooth pipes (plastic or rigid
ducting). For main pipes (outside air, extract air, inlet air, discharge collection) a
diameter 315 mm has to be used, for side pipes an appropriate reduction of the
diameter. To reduce condensation in the extract pipes, the ducting has to be isola-
ted where appropriate. Also if inlet and extract ductwork cross unheated rooms
isolation must be provided to reduce heat losses.
Fresh air should be taken into primary rooms, extraction takes place in secondary
rooms. To regulate the whole system use adjustable valves (HELIOS-valves). The
opening for the kitchen extract needs a filter. A kitchen hood must not be connec-
ted up (danger of grease build-up). There must be enough air flow facilities (e.g.
door grilles) within the building to guarantee air flow between intake rooms and
extract rooms.
Fire and building regulations must be observed.
Thermal humidistat
This thermal humidistat works all-electronic and has a sensor which is installed in
the heat exchanger to measure the degree of humidity. Is the degree of humidity
low, the thermal humidistat will switch off the function of the frost protection and
the unit continues its normal work. In addition, the thermal humidistat contains an
electronic thermostat, which controls the function of the frost protection, when
there is a higher degree of humidity. The sensor is installed in the “cold corner“
and thus measures the temperature correctly in a optimum position. The compo-
nents are provided with a voltage of 24 V.
Electrical connections (pic. 5)
Electrical connection may only be carried out by a qualified person. All work only
in disconnected state. An appliance is required for cut off from the mains with a
minimum of 3 mm contact opening of each pole.
All relevant safety and installation regulations (for example DIN VDE 0100) as well
as TAB of EVK's are to be adhered.
Electrical connections are to be made according to wiring diagram.
TECHNICAL DATA
voltage 3~, 400 V, 50 Hz
current 16 A
connecting cable 5 x 2,5 mm2
dimensions (LxWxH) 1700 x 634 x 1055 mm
condensate waterflow outside 15mm, spigot 315 mm
motor power 670 W
heater power 6 kW
OPERATION - ADJUSTMENT
The KWLC is controlled with an operator device with 2 switches. The 3 speed step
switch controls the fan speed.
Speed step 1 Basic air flow, for less intake air needs
Speed step 2 Normal air flow
Speed step 3 Full R.P.M., for maximum intake air needs
The switch control light operates when the heating coil is on. Speed step 2 (or air
flow volume) of the unit can be adjusted to the size of the rooms to be ventilated.
All servicing when electrically isolated. Therefore the electric connection room (10)
of the unit has to be opend.
Therefore open up the terminal box of the unit and change the marked speed step
2 wire at the transformer in the unit according the wiring diagram.
Attention: For good room conditions and to reduce condensation water dama-
ges, the unit should not be completely switched off, except when servicing / main-
tenance or by breakdown.
Regulating the electric heater battery
The electric heater battery is controlled by a thermostat (1) on the KWLC and by the
on/off switch (S2) on the operator device.
With the thermostat the desired temperature of the intake air is adjusted in intake air
spigot. The thermostat is factory set at 15° C.
1) On/Off switch at operator device 15 set to „Ein“:
If the temperature of the intake air drops in the intake air spigot under the adjusted
temperature at the thermostat the electric heater battery is switched in automatically.
2) On/Off switch at operator device is set to „Aus“:
The electric heater battery remains turned off even if the temperature of the intake
air drops under the adjusted temperature at the thermostat in the intake air spigot.
Attention: The temperature sensor is located in the intake spigot. When intake
ductwork are laid through cold areas, heat loss on the way to the valve must
be considered. A control light in the 3 step switch indicates use of the heater bat-
tery (7).
The heater is protected against overheating by a thermal overload thermostat. It
switches off automatically when the temperature of 55° C has been reached and
restarts after cooling. As an additional safety control, a second thermostat switches
off the whole unit, if a temperature of 80° C is exceeded. The thermostat can be
manually re-set by pressing the red push button, which is accessible by removing
the red push button, which is accessible has to be investigated and remedial action
is to be taken
Frost Protection of the Heat Exchanger Unit
A thermal humidistat avoids ice build up on the heat exchanger unit of the KWLC.
This sensor controls the intake air fan so that ice cannot build up. Warm air e.g.
from the bathroom contains high humidity and therefore it is very likely that con-
densation occurs. Therefore the temperature in the heat exchanger must not drop
too low that water freezes in it. The thermal hunidistat controls the hunidity of the
air. In addition he measures the temperature of the heat exchanger unit. In case of
frost danger and high humidity in the heat exchanger the speed of the intake air
fan is reduced and the bypass flap opens simultaneously to the protection of the
heat exchanger unit. The lower speed of the intake air fan as well as the open by-
pass flap remain unchanged until the heat exchander has warmed itself sufficient-
ly. In case of frost danger und dry air in the heat exchanger the KWLC keeps its
adjusted operating state ( no reduced output)
Summer Service (pic. 3)
During the warmer months (apart from the heating period) it is not necessary to re-
cover heat. If the temperature at the summer thermostat at the outside air spigot
increases above the adjusted temperature (e.g. 17°C) the bypass flap will open
and let the air flow through.
Attention: The thermostat of the additional heating (1) and a possible separate
room thermostat have to be set to "0" to avoid unnecessary waste of energy.
MAINTENANCE
All servicing when electrically isolated.
- Opening of doors (pic. 3)
Open all claims (14). Then remove the door completely (12/13). Set the door back
in reverse order.
Attention: The unit has a door on both sides so that entry can be made through
the side required.
- Filter
The unit comes with several filters:
Outside air/Extract air: fine filter F5 Ref.no. 0179
The outside and the extract pre filter are to be changed or cleaned at least every
three months. The fine filter should be replaced at least after 1 year of use for hy-
gienic reasons. When replacing the filter the correct air flow direction through the
filter has to be observed. When the outside air is very dirty an air filter box (LFBR
315) should be fitted in the ductwork and the filter should be cleaned or replaced
frequently.
- Filter control (pic. 3)
To control the filter automatically, two differential pressure switches are connected
to the KWLC. Is the filter dirty, the control lamp of the filter at the operator device
will light up.
- Fans
The fans are to be maintained and cleaned every 12 months at least. For cleaning
use a small brush and an oil free cleaning fluid. Make sure that no water gets into
the motor. Fan must be completely dry before re-mounting. To dismantle the fan,
unplug the electrical plug-socket facility (pic.3)
- Heat recovery battery
To be cleaned at least twice a year. Pull out the unit carefully. For cleaning put in
warm soapy water (do not use cleaning fluid containing Natriumcarbonate) and fi-
nally clean with warm water. When re-assembling ensure correct installation.
- Valves: To be cleaned at least annually.
- Outer grilles: Check yearly that grilles are free from leaves etc.
SOURES OF MALFUNCTIONING (pic. 3)
No air flow
Check electrical connection / fuses
The overheating thermostat (2) may have tripped. Remove white plastic cap
and press red button.
The unit can be dirty
Filters (5) could be dirty. Change or clean them (see maintenance)
Operation and installation instructions no. 90728
Central ventilation with heat recovery unit KWL-Center 1200
Inlet air is cold
Set heater thermostat (1) to a higher temperature
Ductwork in cold areas need extra isolation
Make sure that summer-insert was changed against the heater recovery battery.
Check if overheating thermostat of the heater has tripped. Press red reset but-
ton (2).
If any of the mentioned points do not help please contact HELIOS. Please state
serial number given on the rating plate which is near the thermostat of the heating
coil. Do not try to repair the unit yourself.
ACCESSORIES
The use of accessories not offered or recommended by HELIOS will make the gu-
arantee invalid. The use of an electronic speed or transformer speed controller is
not permitted.
WARRANTY
If the preceding instructions are not observed all warranty claims and accommodati-
on treatment are excluded. The Helios warranty is limited to the material and work-
manship of the product.
CERTIFICATES
When installed correctly and used for its intended purpose, the
product complies with applicable European standards and regulations at date of ma-
nufacture.
Ein
Aus
Filter
3-step
switch (S1)
control lamp
of fan
control lamp of
electric heater bat-
tery
control lamp of
filter control
on-/off-switch of
electric heater
battery (S2)
pic. 1
operator device
Operation and installation instructions no. 90728
Central ventilation with heat recovery unit KWL-Center 1200
pic. 2
pic. 3
1 thermostat for heater battery
2 overheating thermostat
3 thermal humidistat
4 condensation run-off
5 fine filter F7
6 summer thermostat
73x2000 W elecrical heater battery
8 intake air fan
9 extract air fan
10 electrical terminal box
11 heat exchanger
12 left door
13 right door
14 claim
15 DDS-switch for filter control
16 bypass-flap
17 fuse 2x
overview drawing
eexxttrraacctt aaiirr
iinnttaakkee aaiirr
oouuttssiiddee aaiirr
eexxttrraacctt aaiirr
schematic sketch
oouuttssiiddee aaiirr
iinnttaakkee aaiirreexxttrraacctt aaiirr
iissoollaatteedd
ddrroopp
iissoollaatteedd
eexxttrraacctt aaiirr
sswwiittcchh
ddrraaiinnppiippee
ddrraaiinn ttrraapp ttoo bbee llaayyeedd ffrroosstt-pprrooooff
mmiinniimmuumm 110000 mmmm
ccooppppeerr ppiippee 1155 mmmm oouuttssiiddee ddiiaammeetteerr
ttoo bbee llaayyeedd ffrroosstt-pprrooooff
ppllaasstteerr ooff ppaarriiss//cchhiippbbooaarrdd
ppllaasstteerr ooff mmiinneerraallwwooooll
mmiinniimmuumm 5500 mmmm
mmiinneerraall wwooooll
Operation and installation instructions no. 90728
Central ventilation with heat recovery unit KWL-Center 1200
Druckschrift-Nr. 90 728 / 06.03
Service und Information
DHELIOS Ventilatoren GmbH & Co · Lupfenstraße 8 · 78056 VS-Schwenningen FHELIOS Ventilateurs · Z.I. La Fosse à la Barbière · 2, rue Louis Saillant · 93605 Aulnay sous Bois Cedex
CH HELIOS Ventilatoren AG · Steinackerstraße 36 · 8902 Urdorf / Zürich GB HELIOS Ventilation Systems Ltd. · 5 Crown Gate · Wyncolls Road · Severalls Industrial Park ·
AHELIOS Ventilatoren · Postfach 854 · Siemensstraße 15 · 6023 Innsbruck Colchester · Essex · CO4 9HZ
5 x 2,5 mm²
400V 16A 50Hz
KWLC 1200 SEH ab/from/à partir Ver.6294
H1 H2 H3
L
S2 -
Heizung /
Heater / Chauffage
Ein - Aus
on - off
marche - arrêt
H1 - KWLC Ein / On / Marche
H2 - Filter-Wechsel /
Filter change / Changement de filtre
H3 - Heizung / Heater / Chauffage
Ein / On / Marche
S1 - KWLC
- Stufen-Schalter
- step switch
- commutateur à étages
Aus / Off / Arrêt
Ein-klein / On-slow /
Marche-petite vitesse
mittel a,b,c / medium a,b,c /
moyenne vitesse a,b,c
voll / full / pleine vitesse
P1
12L
P2
PE N 12
L2 10 14
L1 913
L3 118 15
SS-571
KWLC 1200 SEH
mit KWLC
-Stufen- und
Heizschalter
nur ab
Versions-Code
6294
pic. 4
pic. 5
Dimensional drawing
ccoonnddeennssaattiioonn rruunn-ooffff
iinnttaakkee aaiirr
eexxttrraacctt aaiirr
oouuttssiiddee aaiirr
eexxttrraacctt aaiirr
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

HELIOS KWL-Center 1200 Operation And Installation Instructions

Category
Cooker hoods
Type
Operation And Installation Instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI