PowerTec 1000 User manual

Type
User manual
Repair Center for Powertec Drives and Motors
460 Milford Parkway
Milford, OH . 45150
www.motorsystems.com
513-576-1725
Model
1000
Brushless DC Motor Control
I
NSTALLATION AND
O
PERATION
I
NSTRUCTION
M
ANUAL
J
UNE
, 2001
Model
1000
Installation and Operation Manual
Page
1
OFFICIAL 6/1/2001
I
II
I
NTRODUCTION
NTRODUCTIONNTRODUCTION
NTRODUCTION
WHAT IS A GENESIS SERIES BRUSHLESS DC DRIVE ?
The GENESIS series of drives were developed to operate very large Brushless DC motors. Large BLDC
motors were first made by POWERTEC Industrial Corporation in 1987.
Small BLDC motors have been in use for many years. The GENESIS series were the first drives that
were produced to operate really large BLDC motors. They range from fractional Horsepower (HP) to 300 HP.
Brushless DC motors and drives offer three significant benefits to the user:
1. Absolute Speed Control
2. High Efficiency
3. Low Maintenance.
ABSOLUTE SPEED CONTROL
The AC induction motor must “slip” in order to develop torque. “Slip” means that the rotor slows down
when loaded. The amount of slip varies with the load on the motor. When the motor load changes from no
load to full load, speed may change as much as 50 RPM. You must use extraordinary means to employ AC
motors in speed sensitive applications.
Traditional brush-type DC motors have “IR Losses.” These cause the speed of the motor to vary as the
load changes. “IR Losses” account for speed changes of as much as 2% of base speed. You can limit speed
changes to about 0.5% with a very expensive tachometer. That is still 8 or 9 RPM from no load to full load.
You must use extraordinary means to employ brush-type DC motors in speed sensitive applications.
Brushless DC drives and motors do not change speed when the load changes. This is true with the
standard product, right out of the box! This is very good for speed sensitive applications.
HIGH EFFICIENCY
AC induction motors are fairly efficient when operated across the line on plant power. Using an AC
variable speed inverter to control the speed of the AC motor adds power losses as heat in the drive. It also
creates additional losses in the motor. Total losses in the AC system approach 10% at the 100HP level.
Brush-type DC motor systems at 100 HP are relatively efficient, but the losses total about 8%.
Losses average less than 6% in Brushless DC systems at the 100 HP level.
At 100 HP, each percentage of losses is 750 watts. That’s 18 Kilo-Watt-Hours (KWH) per day, or about
6,500 KWH per year. A 2% increase in efficiency results in over $1,000 a year in direct energy savings.
LOW MAINTENANCE
An AC motor running on a variable speed AC drive produces a lot of heat. The motor needs lubrication
more often. It needs extra bearing changes. Heat also shortens the life of the motor.
Brush-type DC motors require frequent brush replacement. They need commutator service and field and
armature rewinding. They also require frequent lubrication and bearing changes due to heat.
Brushless DC motors need greasing, but oversize bearings and low heat output allow long bearing life.
Maintenance on a Brushless DC motor is minimal.
POWERTEC offers the GENESIS series for general purpose industrial use.
POWERTEC also offers a complete line of servo-duty rated drives and motors covering the range from
1/10 to 300 HP.
QUICK START - Page 3 TABLE OF CONTENTS - Page 5
Page
2
Model
1000
Installation and Operation Manual
6/1/2001 © copyright 1997 by Powertec
P4
RUN
123456789101112131415161718
TB2
REMOVE
FOR
COAST
STOP
JP1
CURRENT
LIMIT
LED
ZERO
SPEED
RUN
LED
MIN SPD
MAX SPD
JOG SPD
DECEL
ACCEL
CLIM
STAB
GAIN
POWERTEC
JP2
SPEED CONTROLLER
BOARD
LED
POWER
GREEN
HS3
RED
HS2
RED
HS1
RED
TAC
RED/GREEN
BUS
RED/GREEN
ENABLE
YELLOW
CURRENT CONTROLLER
BOARD
STALL
RED
PL
RED
OV/UV
RED
IOC
RED
TB1
JP1
JP3
Model
1000
Installation and Operation Manual
Page
3
OFFICIAL 6/1/2001
Q
QQ
Q
UICK
UICK UICK
UICK
S
SS
S
TART
TARTTART
TART
Follow these steps to quickly set up and operate the Model 1000 Brushless DC drive. If you are not sure
of the procedure for any of the steps, consult the installation section (beginning on page 7).
CONNECTIONS
1.
Connect the proper three-phase AC power from a suitably rated switching device to the input terminals L1, L2,
and L3. Check the nameplate. The sequence of the phases is not important to the drive.
2.
Connect the power system ground to the GND terminal. Make sure the system ground is earth ground.
3.
Connect T1 of the motor to T1 of the drive. Connect T2 to T2, and T3 to T3. The order of connection is
important. The motor will not run with improper motor connections..
4.
Connect a ground wire from the motor’s ground lug to the GND terminal on the drive.
5.
Connect the encoder cable to the motor. Consult the drawing on page 2. The cable used should be a nine-
conductor shielded cable. The colors do not matter, but they aid in tracing wires. Connect the shield at both
ends of the cable (the shield continues inside the motor, but is not connected there).
6.
Connect a 10 Kilo-ohm Speed Potentiometer to TB2 terminals 9 (CW), 10 (Wiper), and 11 (CCW). Connect the
shield of the speed pot cable to TB2 terminal 12.
7.
Connect an Emergency Stop (ESTOP) button between TB2 terminals 6 and 7. Use a normally closed,
maintained open contact type pushbutton.
8.
Connect a normally closed, momentary type, STOP pushbutton between TB2 terminals 7 and 5.
9.
Connect a normally open, momentary type, RUN pushbutton between TB2 terminals 5 and 4.
10.
If desired, connect a normally open, momentary type, JOG pushbutton between TB2 terminals 5 and 13.
11.
If desired, connect a Forward-Reverse (FWD-REV) selector switch to TB2 terminals 17 and 14. Use a single-
pole, two-position switch. The switch should close a contact in the Reverse position.
START UP
1.
Before applying power, turn the speed pot fully counter-clockwise (CCW) and turn the CLIM pot fully counter-
clockwise. Do not connect the motor to a load for its initial run. Set FWD-REV to FWD.
2.
When you apply power, the PWR LED should light up GREEN immediately.
3.
When you apply power, the BUS LED should light up RED immediately.
4.
When power is on, the HS1, HS2, and HS3 LED’s may or may not be on RED, depending on the position of
the motor. Only one or two should light; never all three and never none.
5.
When power is on, the TAC LED may be OFF, RED, GREEN, or ORANGE.
6.
Within 30 seconds, the BUS LED should turn GREEN and the you should hear the charging contactor click as
it energizes. If this does not happen within 30 seconds, shut power off and consult the troubleshooting section.
7.
Press and release the START button. The RUN LED should light. The CURRENT LIMIT LED may come on at
this time because the CLIM pot is all the way counter-clockwise.
8.
Immediately after the RUN LED comes on, the ENABLE LED should light.
9.
Increase the speed pot reference to about 10% of its rotation from the CCW position.
10.
Turn the CLIM pot slowly clockwise. If the motor does not turn (HS1, HS2, HS3, and TAC will start blinking)
before CLIM is at 50%, turn the CLIM pot back down fully CCW. Consult the troubleshooting section.
11.
When the motor begins turning more than 10 RPM, the ZERO SPD LED should light up YELLOW.
12.
Leave the CLIM pot at 50 % and increase the speed pot to 50% of its rotation. Check the motor speed with a
hand-held tachometer. Adjust the MAX speed pot, if necessary to attain 50% speed.
13.
Turn the speed pot to 100% and measure the motor speed. Adjust MAX speed if necessary.
14.
Press the Normal Stop button and start again. Time the acceleration to full speed and set ACCEL time.
15.
Turn speed pot to 0% (CCW) and set MIN SPD potentiometer, if desired.
16.
Set STAB and GAIN to 50% of their rotation. Press the Normal Stop button. ENABLE should go OFF.
17.
Press the JOG button and set the JOG speed, if desired.
18.
Start the drive at any speed and switch the Forward-Reverse switch to check reversing.
19.
The motor is ready for service.
Page
4
Model
1000
Installation and Operation Manual
6/1/2001 © copyright 1997 by Powertec
REFERENCE PAGES
Model 1000 Dimensions Chart ...............................................................................................................8
Model 1000 AC
Input
Electrical Ratings Table ................................................................................... 10
Model 1000
Output
Electrical Ratings Table ...................................................................................... 12
Contactor Specifications .....................................................................................................................14
Dynamic Braking Resistors ................................................................................................................. 14
Model 1000 Control Connections Table ..............................................................................................16
Terminal Descriptions List ................................................................................................................... 18
PLC Interface Suggestions .................................................................................................................20
Digital Mode Notes .............................................................................................................................. 22
Analog Versus Digital Operation Comparison .....................................................................................24
Standard Basic Connection Diagram ................................................................................................... 26
Capacitor Board Location and Layout ..................................................................................................28
Current Controller Board Layout .......................................................................................................... 30
Speed Controller Board Layout ............................................................................................................30
Jumpers List ....................................................................................................................................... 30
LED Indicators .....................................................................................................................................32
Adjustments ......................................................................................................................................... 34
Simplified Power Schematic ................................................................................................................36
Semiconductor Diagrams......................................................................................................................36
Transistor Module Static Test ............................................................................................................... 38
Diode Bridge Test ................................................................................................................................ 40
Transistor Leakage Test .......................................................................................................................40
Encoder Waveforms and Connections .................................................................................................42
IOC Tests..............................................................................................................................................44
OV/UV Tests .........................................................................................................................................44
Block Diagram Speed and Current Controller boards .......................................................................... 46
Base Driver board- Layout and Connections ........................................................................................48
Model
1000
Installation and Operation Manual
Page
5
OFFICIAL 6/1/2001
TABLE OF CONTENTS
INTRODUCTION
..................................................................................................................................................... 1
QUICK START
......................................................................................................................................................... 3
REFERENCE PAGES
.......................................................................................................................................... 4
TABLE OF CONTENTS
...................................................................................................................................... 5
SPECIFICATIONS
................................................................................................................................................. 6
MOTOR PROTECTION
........................................................................................................................................ 7
WARRANTY
............................................................................................................................................................. 7
INSTALLATION
HOW DO I
Physically Install
the Model 1000 Drive ? ........................................................................................................... 9
Connect AC Power
to the 1000 Drive ? ........................................................................................................... 11
Connect the Motor
to the 1000 Drive ? ............................................................................................................ 13
Install an
Output Contactor
? ........................................................................................................................... 15
Install
Dynamic Braking
? ................................................................................................................................. 15
Connect
Standard Control Circuits
? .............................................................................................................. 17
Get
RUN
, Zero Speed,
FAULT
, and
ENABLE
Information ? ............................................................................ 19
Connect an
ANALOG Speed Reference
?........................................................................................................ 21
Connect a
DIGITAL Speed Reference
? ........................................................................................................... 23
Connect a
DIGIMAX
? ..................................................................................................................................... 25
Installation Checklist
...................................................................................................................................... 27
START UP
WHAT HAPPENS WHEN I
Apply Power
to the Model 1000 Drive ? ............................................................................................................ 29
Give the Start Command
to the Model 1000 Drive........................................................................................... 31
Give the Speed Command
to the Model 1000 Drive ........................................................................................ 33
Make an Adjustment
on the Model 1000 Drive................................................................................................. 35
TROUBLESHOOTING
Troubleshooting the Model 1000 Drive............................................................................................................... 37
Troubleshooting Chart - POWER LED ............................................................................................................... 39
Troubleshooting Chart - BUS LED...................................................................................................................... 41
Troubleshooting Chart - HS1, HS2, HS3, and TAC LED’s.................................................................................. 43
Troubleshooting Chart - RUN and ENBL LED’s ................................................................................................. 45
Troubleshooting Chart - TAC and ZERO SPEED LED’s .................................................................................... 47
Troubleshooting Chart - CURRENT LIMIT and PHAD LED’s ............................................................................. 49
Page
6
Model
1000
Installation and Operation Manual
6/1/2001 © copyright 1997 by Powertec
SPECIFICATIONS
ENVIRONMENTAL
ALTITUDE : Use above 3300 feet (1000 meters) requires de-rating.
De-rate at 3% of full rating for each additional 1100 feet (330 meters).
STORAGE TEMPERATURE : -40 °C to +65 °C (-40 °F to + 150 °F)
AMBIENT TEMPERATURE :
Chassis : Maximum air temperature of 55 °C (131 °F).
Nema1 : Maximum air temperature of 40 °C (104 °F).
RELATIVE HUMIDITY : Less than 95%, non-condensing.
POWER SOURCE :
Voltage : Nominal 230 VAC, 380 VAC, or 460 VAC per nameplate rating.
Voltage Tolerance : -10%, +10% of nominal rated voltage.
Phases : Three (Drive will not operate on single phase).
Frequency : 48 to 62 Hertz
KVA Required : KVA rating of source must be at least equal to Horsepower rating.
Max KVA Rating : 100 KVA (limited by input fuse AIC rating).
DIMENSIONS
Physical Dimensions : See page 8.
Approximate Weights :
1000 chassis : 30 pounds ( 66 kg ).
1000A chassis : 44 pounds ( 97 kg )
1000 Nema1 : 41 pounds ( 90 kg )
1000A Nema1 : 56 pounds ( 123 kg )
PERFORMANCE
Maximum Load : 150% for 1 minute out of 10 minutes.
Speed Regulation : 0.0% (on load change from no load to full load)
Speed Accuracy :
Analog Mode : +/- 1.0% typical with speed pot supplied by internal reference.
Linearity : +/- 0.5% typical with external reference source.
Digital Mode : 0.0 % typical ( +/- ¾ revolution of the motor shaft ).
Displacement power factor : 0.96 typical
ADJUSTMENTS
ACCELERATION TIME : 2 to 90 seconds with JP2 installed; 0.05 to 2 seconds with JP2 removed..
DECELERATION TIME : 2 to 90 seconds with JP2 installed; 0.05 to 2 seconds with JP2 removed..
Acceleration and deceleration times settable in analog mode only.
MAXIMUM SPEED : 600 to 5000 RPM ( motor dependent ), analog mode only.
MINIMUM SPEED : 0 to 15% of MAXIMUM SPEED with 5K speed potentiometer, analog mode only.
JOG SPEED : 0 to 30% of MAXIMUM SPEED, analog mode only.
CURRENT LIMIT : Adjustable from 0% to 150% of rated current, calibrated by Horsepower Resistor.
GAIN : 10 to 1 stiffness ratio
STABILITY : 20 to 1 dynamic response.
JUMPERS
SEE PAGE 30
LED INDICATORS
SEE PAGE 32
TERMINAL ASSIGNMENTS
SEE PAGE 18
Model
1000
Installation and Operation Manual
Page
7
OFFICIAL 6/1/2001
I
II
I
NSTALLATION
NSTALLATIONNSTALLATION
NSTALLATION
Underwriter’s Laboratories
®
requires this notice for UL
®
listed equipment.
This Notice applies to Brushless DC Drive Model Numbers 1000 and 1000A.
MOTOR PROTECTION CONSIDERATIONS
You are about to install a
GENESIS
Series Brushless DC (BLDC) drive. You need to consider how the motor will be
protected while it is in service. This is what the Model 1000 series drive provides :
1.
“F” Series
motors have an internal switch that opens at high winding temperatures. You must connect this
switch to the drive. Look up the method of connection in the drive manual. When the thermal switch opens, the drive
has to be shut down before high temperatures can cause damage.
2. The Model 1000 series drive provides motor current limiting. This protection is adjustable from 0% to 150% of
the drive’s rated output current.
3. The Model 1000 series drive provides an overcurrent trip. This shuts off the drive if peak currents greater than
300% of the RMS rating occur.
4. The Model 1000 drive provides fast clearing fuses in the AC input. It does not provide an input circuit breaker
unless you chose that option at the time of purchase. If you did not purchase an optional circuit breaker with the drive,
you must supply a switch for input power. You must do this in order to meet the requirements of the National Electrical
Code.
5.
GENESIS
series drives
do not provide running overload protection as described in Underwriters Laboratories
Industrial Control Equipment Specification 508. The user is responsible for complying with local codes and practices. If
you decide you need more protection, that protection must shut off the drive.
SUMMARY
OF WARRANTY AND DISCLAIMER
Powertec
manufactures Model 1000 Series Brushless DC (BLDC) motor controls. We warrant these units against
defects in materials and workmanship for a period of
two years
. This period begins on the date of original shipment
from the factory.
You must notify us in writing of a defect in materials or workmanship in a warranted unit. We
will, at our sole option,
repair or replace such defective parts as we deem necessary to restore the unit to service. We will make these repairs,
or replacement of parts, at the factory. Shipping charges to and from the factory and on-site service charges are the
responsibility of the user.
There is no other warranty. We do not warrant the fitness of purpose for the application intended. This warranty
does not cover accidental or intentional damage or accidental or intentional abuse. This warranty does not cover
results from defective or incorrect installation, interference with other equipment, or any other situation over which
Powertec
has no control.
This warranty does not cover any other claims, including, but not limited to, special, incidental, or consequential
damages.
Powertec
supplies this manual as a guide to the use of
our products. We have used our best efforts to compile this
information. If you find mistakes of fact in this manual, please notify your distributor or
Powertec
at once.
Do not use this device on a circuit capable of delivering more than
5000 RMS symmetrical Amperes at 500 VAC maximum voltage.
Page
8
Model
1000
Installation and Operation Manual
6/1/2001 © copyright 1997 by Powertec
M
ODEL
1000 D
IMENSIONS
CHASSIS UNITS
ENCLOSED UNITS
Model
1000
Installation and Operation Manual
Page
9
OFFICIAL 6/1/2001
H
OW
D
O
I …
PHYSICALLY INSTALL THE MODEL 1000 DRIVE?
WARNING:
DANGEROUS HIGH VOLTAGES ARE NORMAL IN THIS EQUIPMENT! WHEN THE AC INPUT POWER IS
REMOVED, THE CAPACITORS ARE NOT DISCHARGED AT ONCE! WAIT FIVE MINUTES AND THEN CHECK
TO BE SURE THAT THE CAPACITORS ARE DISCHARGED BEFORE WORKING ON THE DRIVE.
WARNING! :
IF YOU TESTED THE DRIVE BEFORE INSTALLATION, CHECK THE BUS VOLTAGE. YOU WANT TO MAKE
SURE THAT THE BUS CAPACITORS HAVE DISCHARGED.
Mount a Model 1000 series drive of the NEMA 1 style with the fuses at
the top. Do not block air flow around the unit. Free air must flow up through
the fins on the back of the drive.
The temperature of the air around the drive (the ambient) must not
exceed 40°C (104°F) with a relative humidity of 95% or less.
Leave at least 6 inches (150 mm) of open space on all sides of the
NEMA 1 box. Do not mount it directly above a heat source, such as another
drive. If you mount two drive units in line vertically, there must be at least 18
inches (450 mm) of open space between the units.
When you move the Model 1000 series drive chassis to an enclosure,
DO NOT handle the chassis by parts that may bend or come loose. This
applies to the front cover of the drive. Support the chassis by the outside
edges of the heatsink.
Mount the chassis style Model 1000 series drive in an upright position (fuses at
top) inside an enclosure. Mount the chassis this way to promote cooling air flow
through the heatsink fins.
The temperature of the air around the chassis (ambient) may not exceed 55 °C
(131 °F). Relative humidity should be 95% or less, non-condensing.
Avoid mounting one chassis directly above another. This will result in hot air from
the lower chassis flowing up into the upper chassis. Leave at least 12 inches (300
mm) of open space between them.
There must be a minimum free panel space of 3 inches (75 mm) above and
below the chassis. This allows proper air flow through the heatsink fins.
The total heat dissipation within the electrical enclosure, for chassis units,
determines the size. There is a list of the heat output of the Model 1000 series drives
in the table on page 10.
NEMA 1, NEMA 1A, and NEMA 12 ventilated boxes depend upon air flowing
through the enclosure for cooling. They must have an air flow of 1 CFM (cubic feet
per minute) per 10 watts of dissipation (1 cubic meter/minute per 350 watts).
The allowance for totally enclosed units is 1 square foot of enclosure surface per
7 watts of dissipation (75 watts per square meter). Surface area includes front, sides,
top and bottom surface areas. Enclosure surfaces not exposed to cooling air do not
count.
For further information, consult the publication THERMAL MANAGEMENT,
available from your distributor.
Use of the Model 1000 Series drive above 3300 ft (1000 meters) requires de-rating.
If the drive is to be stored, store it in its original packaging in a dry environment.
Storage temperature should be between -40°C and +65°C.
Mount with 1/4-20 bolts
and nuts in 4 places
Page
10
Model
1000
Installation and Operation Manual
6/1/2001 © copyright 1997 by Powertec
M
ODEL
1000 AC I
NPUT
E
LECTRICAL
R
ATINGS
NOMINAL
AC LINE
VOLTAGE
HORSE-
POWER
KILO-
WATTS
MAXIMUM
CONTINUOUS
AC LINE
CURRENT
INPUT
KVA
MAXIMUM
HEAT
OUTPUT IN
WATTS
230 ½ 0.37 1.4 0.550 35
230 ¾ 0.56 1.8 0.725 42
230 1 0.75 2.4 0.950 60
230 1.5 1.1 3.6 1.450 85
230 2 1.5 4.9 1.950 122
230 3 2.2 7.3 2.900 165
230 5 3.7 12.1 4.825 232
230 7.5 5.6 18.1 7.200 281
230 10 7.5 23.9 9.525 385
380 1 0.75 1.5 0.975 36
380 1.5 1.1 2.2 1.450 55
380 2 1.5 2.9 1.925 70
380 3 2.2 4.4 2.875 105
380 5 3.7 7.3 4.810 142
380 7.5 5.6 10.9 7.150 178
380 10 7.5 14.1 9.250 222
460 2 1.5 2.4 1.910 113
460 3 2.2 3.5 2.800 144
460 5 3.7 5.9 4.750 200
460 7.5 5.6 8.9 7.100 258
460 10 7.5 11.4 9.050 355
460 15 11 17.8 14.150 475
Indicates 1000A models.
N
OTES
The Model 1000 Series drives are designed to operate on power line frequencies from 48 to 62 hertz.
The
tolerance
of the input voltage is +10% to -10% of the nominal voltage listed on the nameplate. A service that
supplies AC motors, in addition to the drive, must be capable of supporting the starting current of the motors without dropping
more than 10%. If the drive is operating at a line voltage of less than 95% of the nominal line voltage, brief power line
disturbances may trip the drive.
Do not measure the input voltage while the drive is not running. This neglects the effects of load on the power source.
Measure the actual input line voltage while the control is operating the motor in a loaded condition.
Brief power line disturbances will not normally disturb the Model 1000 series drives. The Model 1000 series drives do not
generate significant noise back onto the power service. Events that distort the AC waveform may lower the bus voltage. These
may trigger an under-voltage or power loss condition.
One of the most frequent problems encountered with digital type equipment is electrical noise. Noise is a treacherous
problem that is capable of causing destructive results. It can also cause intermittent and annoying problems. The methods
used in the installation of the equipment plays a large part in prevention of electrical noise interference in operation. Any digital
type control requires that extra care be taken in installation. Pay attention to the grounding of the equipment, the shielding of
wires and cables, and the placement of wires in the conduit runs. Pay attention to the sections of this manual that address the
precautions against noise. This also applies to peripheral equipment.
When you use other manufacturer’s equipment in a system, follow their directions regarding noise suppression and
protection. Pay particular attention to power and grounding requirements.
Model
1000
Installation and Operation Manual
Page
11
OFFICIAL 6/1/2001
H
OW
D
O
I …
CONNECT AC POWER TO THE 1000 DRIVE?
Standard Model 1000 series Brushless DC drives will not operate on
single phase AC power.
Model 1000 series drives require a three-phase main power source with a
KVA rating
at least equal to the
HorsePower rating
of the drive.
However, the branch service rating (in KVA) supplying the drive must not
be more than 10 times the HP rating of the drive. If it is, you may need special
disconnecting means with a higher AC short-circuit current interrupting
capacity.
Model 1000 series drives do not include a disconnect for input power. The
user must supply a switch that meets applicable code requirements.
The maximum Interrupting Capacity (AIC) of the fuses is 5,000 amperes.
You will need a switch with a rating greater than 5,000 amperes if the short
circuit current on the service is greater.
You do not necessarily need an ISOLATION TRANSFORMER for
operation of the drive. You may want to use one, or you might need to meet
local code requirements. You may need to change the voltage level.
If you use a transformer, you will need one with a KVA rating at least as
large as the HP rating of the drive. If you use a transformer, we recommend a
delta/wye winding configuration. We also recommend that the transformer
have taps to raise or lower voltage.
The user protection supplied before the wires determines the sizes of the
power wires to the drive input. The table on the opposite page lists the full load
AC line currents of Model 1000 series drives.
The order of connection of the input phases is not important.
We size the main fuses to protect the semiconductor elements of the unit.
THEY MAY OR MAY NOT MEET THE REQUIREMENTS OF NATIONAL,
STATE AND/OR LOCAL ELECTRICAL CODES. The responsibility for meeting
the branch service protection and other code requirements and safety codes
belongs to the user.
NOTICE: THE AC LINE CURRENT OF THE BRUSHLESS DC DRIVE IS NOT
REPRESENTATIVE OF THE OUTPUT LOAD CURRENT TO THE
MOTOR!
The AC input current is directly proportional to the POWER output of the
motor. The only time the AC line current reaches its full value is when the
motor is operating at full speed with full load.
DO NOT ATTEMPT TO MEASURE MOTOR LOAD BY
MEASURING AC INPUT LINE CURRENT TO THE BLDC MOTOR
CONTROL.
TRANSFORMER
.
SEE FUSE
INPUT
BOARD
DRAWING
ON PAGE 8
L1
L2
L3
GND
MAIN
POWER
Page
12
Model
1000
Installation and Operation Manual
6/1/2001 © copyright 1997 by Powertec
MODEL 1000 FUSE BOARD
MODEL 1000 OUTPUT ELECTRICAL RATINGS
NOMINAL
AC LINE
VOLTAGE
HORSE-
POWER
KILO-
WATTS
MAXIMUM
CONTINUOUS
MOTOR
CURRENT
MAXIMUM
MOMENTARY
MOTOR
CURRENT
NOMINAL
HP
CALIBRATE
RESISTOR
230 ½ 0.37 2.2 3.3 68.1 K
230 ¾ 0.56 3.4 5.1 45.3 K
230 1 0.75 4.7 7.0 33.2 K
230 1.5 1.1 7.0 10.5 22.1 K
230 2 1.5 8.5 12.7 18.2 K
230 3 2.2 12.8 19.2 12.1 K
230 5 3.7 22.8 34.2 6.81 K
230 7.5 5.6 31.1 46.6 4.99 K
230 10 7.5 41.5 61.1 3.74 K
380 1 0.75 2.7 4.0 56.2 K
380 1.5 1.1 3.9 5.8 39.2 K
380 2 1.5 4.7 7.0 33.2 K
380 3 2.2 7.8 11.7 20.0 K
380 5 3.7 14.1 21.1 11.0 K
380 7.5 5.6 18.8 28.2 8.25 K
380 10 7.5 25.0 37.5 6.19 K
460 2 1.5 4.0 6.0 39.2 K
460 3 2.2 6.9 10.3 22.1 K
460 5 3.7 11.6 17.4 13.3 K
460 7.5 5.6 17.1 25.6 9.09 K
460 10 7.5 20.7 31.0 7.50 K
460 15 11 31.1 46.6 4.99 K
Indicates 1000A models.
Model
1000
Installation and Operation Manual
Page
13
OFFICIAL 6/1/2001
H
OW
D
O
I …
CONNECT THE MOTOR TO THE 1000 DRIVE?
We ship every drive from the factory with A STANDARD CONNECTIONS card.
Connect the motor lead marked T1 to the
T1 terminal on the drive. Connect the T2 lead
to T2 on the drive, and connect T3 to T3.
Other connections to T1, T2, and T3 at the
motor will vary with the motor. The motor will
not operate correctly if the power wires from
motor to drive are not in the proper order.
Full load motor current determines the
wire size to the motor. The table on the
opposite page lists these currents.
Any high voltage, high frequency
equipment generates EMI and RFI.
YOU
MUST USE METALLIC CONDUIT TO
ENCLOSE MOTOR WIRES
BETWEEN THE
MOTOR AND THE DRIVE.
This will minimize
interference.
You must install a ground wire between
the motor frame and the drive chassis. There
is a ground lug in most motors. If there is no
ground lug, make a connection at any bolt in
the motor junction box.
THIS GROUND WIRE MUST BE RUN IN
ADDITION TO GROUNDING THE MOTOR FRAME TO ITS MOUNTING, WHICH IS REQUIRED BY
CODE.
The purpose of this separate ground is to equalize the potential between the motor's frame and the drive
chassis. There may be enough impedance to broadcast EMI and RFI even with the motor grounded to its
mounting frame. A direct wire connection between the motor frame and the drive chassis minimizes
interference in other equipment.
The encoder feedback cable must be a shielded cable. Connect the shield to TB1 terminal 1 on the
control end. Standard installation requires a nine-conductor shielded cable (Belden
part #9539 or equivalent).
The colors of this cable correspond to the colors of the wires in the motor and on the connection diagram. You
may interchange the Purple and White wires without ill effect.
The shield must be continuous from the motor to the control. Do NOT ground the shield at intermediate
points. This applies to all junction boxes installed between motor and control.
DO NOT USE THE SHIELD OF THE ENCODER CABLE AS AN ACTIVE CONDUCTOR!
If you want to use the motor thermal protector in a 120 VAC circuit, run it in wiring separate from the
cable. Use seven-conductor shielded cable. In this case, if the cable wire colors are different from the
diagram, you need to check them carefully for proper connections.
BLDC
MOTOR
T1 T2 T3
GND
1 2 3 4 5 6 7 8 9 S
T1
T2
T3
GND
Blue
Brown
Black
Orange
Red
Green
Yellow
16
1 2 3 4 5 6 7 89
TB1
18
1 2 3 4 5 6 7 89
TB2
Purple
White
SEE FUSE
INPUT
BOARD
DRAWING
ON PAGE 8
SEE MOTOR
MANUAL FOR
CORRECT
MOTOR
CONNECTIONS
Page
14
Model
1000
Installation and Operation Manual
6/1/2001 © copyright 1997 by Powertec
CONTACTOR SPECIFICATIONS
If you want to operate an Output or Dynamic Braking Contactor
directly from the Model 1000 or 1000A, you must choose a coil that
draws less than 50 milliamps DC.
The Output Contactor drawing on page 15 shows the
connections for direct operation of the contactor (use the same
connections for Dynamic Braking). The coil must be 48VDC and
draw less than 50 ma DC (2.4 Watts). This is the most power
available from the Model 1000 series drive’s supplies.
To use a 115VAC or 230 VAC coil, you need a 156-012
Contactor Control board, as shown in the drawing on page 15. Use
the same drawing for the Output Contactor. Maximum current for the
Contactor Control board is 1 Amp at 230 VAC.
You need three normally open power poles and a normally open
auxiliary for an Output Contactor. The contactor does not make or
break with current in the power contacts. Choose the contact ratings
only on the basis of carrying the current.
For Dynamic Braking, you need three normally closed power
poles and a normally open auxiliary. The contacts make with current
present, but they do not break current in the dynamic braking
operation. Choose contacts accordingly.
The contactor outline sketched at left is from the SH-04 series by
AEG Industries. The model used for the Output Contactor is part
number SH-04.40 and the Dynamic Braking is SH-04.13. Contact
ratings are 16 Amps.
DYNAMIC BRAKING RESISTORS
We choose DB resistors for their ability to absorb high inrush currents and to accept large amounts of
power for short periods of time. Typical DB resistors can absorb ten times their power rating for up to five
seconds. The resistors must then cool down to ambient temperature before they can dissipate their full rating
again (usually a few minutes). It is possible to extend the ratings by about three times with power resistors by
forced-air cooling.
You can derive an approximate value of dynamic braking resistor from the bus voltage and the full load
current on the nameplate of the motor:
Bus Voltage X 0.47
Each Resistor Value ~ -----------------------------------
Motor FLA
Three resistors (or groups of resistors) are necessary. The power rating of each should be:
Power > 0.02 X (Buss Voltage)
2
/ (Resistor Value)
These formulas are very general, and results will vary from motor to motor. For dynamic braking tailored
to your application, consult
Powertec
Engineering.
1.77"
1.66"
13 21 31 41
A1
14 22 32 42 A2
TOP VIEW
BOTTOM VIEW
1.25"
0.19"
1.54"
Model
1000
Installation and Operation Manual
Page
15
OFFICIAL 6/1/2001
H
OW
D
O
I …
CONNECT AN OUTPUT CONTACTOR?
When you use an output contactor with the Model 1000, you
MUST interlock the output contactor with the Emergency Stop.
You WILL damage the drive if you do not interlock it.
Requirements for the Model 1000 series are:
1. The contactor must close its main power contacts
BEFORE it enables the drive;
2. The contactor may only open its contacts AFTER
disabling the drive.
It is important to note that the contactor does not make
or break current.
The figure at left shows the connections for a 48VDC output
contactor (such as AEG part number SH-04.40-ODC, which is
available from
POWERTEC
).
In this configuration, the contactor energizes on a run
command and de-energizes ONLY on an emergency stop. The
contactor stays energized during normal stops.
POWERTEC
makes an optional track mount PC board (Part
# 156-012) for sequencing of contactors with AC coils.
DO NOT BREAK THE GROUND CONNECTION OR THE CABLE
CONNECTIONS WITH THE OUTPUT CONTACTOR.
H
OW
D
O
I …
CONNECT DYNAMIC BRAKING?
You MUST interlock the contactor with the
Emergency Stop when using Dynamic Braking. You
will damage the drive and/or the resistor banks if
you do not properly interlock the contactor.
The requirements are:
1. The contactor must open the main power
contacts BEFORE the drive is enabled; AND
2. The contactor may only close its contacts
AFTER disabling the drive.
The AEG SH-04.13-ODC contactor is suitable
to the circuitry above. The figure on the left shows
the connections for using a POWERTEC 156-012
Contactor Control board to control a larger
contactor or a contactor with an AC coil.
In this configuration, the contactor energizes
when there is a run command and de-energizes
ONLY on an emergency stop. The contactor stays
energized during normal stops.
BLDC
MOTOR
T1
T2
T3
G
T1
T2
T3
M
181 2 3 4 5 6 7 814
TB2
MOTOR
THERMAL
M
M aux
RUN STOP
EMER
STOP
CONTACTOR
3 POLE N.O.
1 N.O. aux
48VDC COIL
@ 2.4 W
GND
9 10 11 12 13
JOG
6
CONTACTOR
3 POLE N.C.
1 N.O. AUX
COIL < 230VAC
Page
16
Model
1000
Installation and Operation Manual
6/1/2001 © copyright 1997 by Powertec
M
ODEL
1000 C
ONTROL
C
ONNECTIONS
MOTOR
THERMAL
STD:
CONNECT FROM
TB2-8
TO
TB2-6**
Normally closed bi-metallic thermal switch in the motor. THE
MOTOR THERMAL SWICH MUST BE USED TO PROPERLY
PROTECT THE MOTOR! When the motor thermal switch opens,
the drive must be shut off to prevent damage to the motor
from overheating.
EMERGENCY
STOP
+24VDC
ON
TB2-7
STD: N/C PB
FROM
TB2-7
TO
TB2-6**
Voltage must be present to RUN or JOG. When removed,
ENABLE REQUEST is blocked immediately (see page 31) and
all control functions are disabled. Do not connect voltage to
terminal with permanent jumper. In RAMP STOP mode, this is
the only way to stop the drive.
RAMP STOP
+24VDC
ON
TB2-5
S
TD
: N/C PB
FROM
TB2-7
TO TB
2-5
Voltage must be present to maintain RUN mode after a
momentary START is removed. When voltage is removed, the
drive decelerates to zero speed at the DECEL rate and shuts
off if RAMP STOP jumper JP2 is installed. Otherwise drive
shuts off immediately and the motor coasts to a stop.
START /
RUN
+24VDC
ON
TB2-4
STD: N/O PB
FROM
TB2-5
TO TB
2-4
Voltage must be applied to initiate RUN mode. When it is
removed, drive shuts off unless +24VDC is present at TB2-5.
RUN LED turns on when +24VDC is applied to TB2-4. RUN
LED turns off and RUN relay drops out when voltage is
removed from both TB2-4 and TB2-5.
RUN
CONTACT
TB2-1
AND
TB2-2
Normally open dry contact which closes when START is
energized and opens when RUN relay drops out (see above).
The RUN contact does not open on a FAULT unless the fault
removes the voltages from TB2-4 and TB2-5. The RUN contact
does not close on JOG and opens in RAMP STOP mode.
ZERO
SPEED
OUTPUT
: TB2-16
COMMON
: TB2-12
Open collector transistor output referenced to TB2-12. Rated
at 50 mADC @ 50 VDC max. This output operates only in RUN,
JOG, or RAMP STOP modes. The ZERO SPEED output turns
on at about 10 RPM and off at about 5 RPM. The ZERO
SPEED output shuts off if ENABLE LED shuts off.
JOG
+24VD
C ON
TB2-13
STD: N/O PB FROM
TB2-5
TO
TB2-13
Voltage must be applied to initiate JOG mode. JOG mode will
be maintained only as long as the voltage is present. When
the voltage is removed, the drive will go to RAMP STOP mode
if COAST TO STOP jumper JP2 is installed. Otherwise the
drive shuts off and the motor coasts to a stop.
REVERSE
+24VDC
ON
TB2-14
STD
: N/
O
PB
FROM
TB
2-17
TO TB
2-14
Voltage must be applied to make motor go in reverse direction
(forward direction is defined as clockwise rotation of shaft
looking at output shaft end). In analog mode, applying or
removing voltage causes drive to decelerate to zero speed
and accelerate to set speed in opposite direction. In digital
mode, input frequency must be reduced to zero until motor
stops, then re-applied to go in opposite direction.
FAULT
OUTPUT
OUTPUT
COLLECTOR
: TB1-12
E
MITTER
: TB1-13
Optically coupled transistor output (isolated). Rated at 50
mADC @ 50 VDC. Turns on when bus has achieved proper
level. Output is off when any trip occurs.
ANALOG/
DIGITAL
SWITCH
+24VDC
ON
TB1-10
REFERENCE TB
1-9
TB
1-9
IS NOT DRIVE
COMMON
Apply voltage to switch to DIGITAL mode. TB1-10 and TB1-9
are electrically isolated from the board power supplies. The
negative side of the +24VDC used for the input must be
connected to TB1-9. External frequency must be applied to
terminal 11. Terminal 9 is also common for this frequency.
** NOTE:
TB2-6 is a dead terminal. It is used as a tie point.
Model
1000
Installation and Operation Manual
Page
17
OFFICIAL 6/1/2001
H
OW
D
O
I …
CONNECT STANDARD CONTROL CIRCUITS?
If you are using an output contactor or dynamic
braking, see page 15
.
The table on the opposite page lists the functions,
connections and descriptions of the control circuits of the
Model 1000. Read the descriptions of the operations of
these circuits carefully, since there are some differences
between operation in analog and digital modes.
The control circuits of the POWERTEC Brushless DC
Drive Models 1000 and 1000A motor controls operate on
48 VDC. This results from using the positive and negative
24 VDC unregulated power supplies. Using 48VDC helps to
balance the load of relays and other devices on the
supplies.
The maximum current from each of the raw supplies is
50 milliamps. Due to this supply limitation, you must use an
external supply when you use several external relays.
THE POWER SUPPLIES OF THE MODELS 1000 AND
1000A SHOULD NOT BE USED FOR EXTERNAL
EQUIPMENT! We make an optional power supply (part #
127-101) available for additional 24 VDC power.
It is possible to operate the control circuits with a
variety of devices. Standard operator devices are O.K.. The
current flowing through these devices is very small. When
locating pushbuttons more than 30 feet away from the drive,
you should consider using 120 VAC control circuits.
There is a desire in some cases to place a jumper
across the Emergency Stop terminals, rather than to install ESTOP buttons. Because the drive has a
ramp to stop capability, this could set up an UNSAFE situation. IT IS STRONGLY RECOMMENDED
THAT AN EMERGENCY STOP BUTTON (or an ESTOP relay) BE CONNECTED TO THE DRIVE! This
should be of the MAINTAINED CONTACT TYPE.
T
HE MOTOR THERMAL MUST BE USED TO
PROPERLY
PROTECT THE MOTOR
!
You can use the "two-wire" control method by connecting a contact or switch between terminals 7
and 4 on TB2. Leave off the RAMP STOP and START buttons. This DOES NOT disable the RAMP STOP
function. The only way to disable the RAMP STOP function is removing the RAMP STOP jumper.
The RAMP STOP function in the analog mode shorts the analog reference input to zero. This causes
the motor to decelerate to zero speed before shut-down. In digital mode, you must reduce the external
frequency to zero, or the RAMP STOP circuitry will not function.
Note that the JOG function OVERRIDES the RUN function. If you activate the JOG input while the
RUN mode is in operation, it will change the motor speed to JOG speed.
RAMP
STOP
EMER
STOP
TO
MOTOR
THERMAL
TB2
16151413121110987654321 1817
START
JOG
FWD REV
Page
18
Model
1000
Installation and Operation Manual
6/1/2001 © copyright 1997 by Powertec
TERMINAL DESCRIPTIONS
- M
ODEL
1000
AND
1000A
TB1 CURRENT CONTROLLER BOARD (141-108)
1 Dedicated Shields and Ground connection
2 HS1 position encoder
3 HS3 position encoder
4 HS2 position encoder
5 HS4 speed encoder
6 HS5 speed encoder
7 Encoder Common for encoder ONLY
8 Encoder +5 VDC for encoder ONLY
9 Isolated Common for terminals 10 and 11
10 Auto/Manual Selection +24 VDC for Digital Mode
11 External Frequency Input +24 VDC Square Wave
12 Collector of FAULT transistor
13 Emitter of FAULT transistor
14 Drive Load output -2VDC = 150%
15 Auxiliary Supply output +15VDC for extra encoder
16 Power Supplies Common
TB2 SPEED CONTROLLER BOARD (141-107)
1 RUN contact closes on RUN
2 RUN contact 1 Amp 125 VAC
3 -24 VDC raw supply 50 ma max
4 RUN input +24VDC to RUN
5 RUN hold +24VDC to maintain RUN
6 SPARE tie point for motor thermal
7 Emergency STOP +24VDC to RUN
8 +24 VDC RUN Logic Supply 50 ma max
9 +10 VDC reference supply
10 Speed reference input 0 to +10VDC
11 Minimum speed connection for speed pot
12 Signal common
13 Jog input +24VDC to JOG
14 Forward/Reverse input +24VDC to reverse **
15 Frequency output open collector to common
16 Zero speed output open collector to common
17 +24VDC raw supply 50 ma max
18 Current reference (velocity error) 0 to +10VDC
TB3 CAPACITOR BOARD (141-106)
1 Horsepower calibration resistor
2 No connection
3 Horsepower calibration resistor
*+24 VDC source for forward/reverse input must be must be from TB2 terminal 17 ONLY.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

PowerTec 1000 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI