X4 AC Drive User’s Manual Summary of X4 Parameters
1428D-0607 - iv - © 2007 TB Wood’s All Rights Reserved
404 Accel Time 2 0.1-3200.0 sec 3.0 sec 56
405 Decel Time 2 0.1-3200.0 sec 3.0 sec 57
406 DC Inject Config text string DC at Stop 57
407 DC Inject Time 0.0-5.0 sec 0.2 sec 57
408 DC Inject Level 0.0% to 100.0% 50.0% 57
409 DC Inj Freq 0.0 to 20.0 Hz 0.0 Hz 57
410 DB Config text string Internal 58
414 S Ramp Rounding 1 - 100% 25% 58
490 App Macro text string Factory 40
491 Seq Appl text string Disabled 40
492 SIO Visible text string No 40
501 V/Hz Select text string Linear Fixed 59
502 Voltage Boost 0.0-50% 1.0% 59
503 V/Hz Knee Freq 25.0-400.0 Hz 60.0 Hz 59
504 Skip Freq Band 0.2-20.0 Hz 0.2 Hz 60
505 Skip Freq 1 Min Freq-Max Freq 0.0 Hz 60
506 Skip Freq 2 Min Freq-Max Freq 0.0 Hz 60
507 Skip Freq 3 Min Freq-Max Freq 0.0 Hz 60
508 Skip Freq 4 Min Freq-Max Freq 0.0 Hz 60
509 Rated Mtr Volt 100V-690V Model Dependent 60
510 Rated Mtr FLA 50% - 200% of ND Rating ND Rating 60
511 Rated Mtr RPM 0-24000 rpm 1750 rpm 60
512 Midpoint Freq 0.0 Hz-V/Hz Knee Freq 60.0 Hz 60
513 Midpoint Volt 0.0-100.0% 100.0% 60
514 Motor RS 0.0-655.35 Ohms Model Dependent 60
515 Power Factor 0.50-1.00 0.80 60
516 Slip Comp Enable text string No 61
517 Single Phase text string No 61
519 Find Mtr Data Not active / Motor RS Not active 61
520 Filter FStator 1 - 100 ms 8 ms 61
521 Start Field En Yes / No No 61
522 Filter Time Slip 10 - 1000 ms 100 ms 61
523 Id Percent 0 - 200% Read-only 62
524 Iq Percent 0 - 200% Read-only 62
525 Power Fail Config text string CTS No Msg 62
526 UV Ride-Thru En text string w/ LVT 62
600 Current Lim Sel 0-6 Fixed Lvls 63
601 Cur Lim Mtr Fwd 5%-150% 120% 63
602 Cur Lim Mtr Rev 5%-150% 120% 63
603 Cur Lim Reg Fwd 5%-150% 80% 63
604 Cur Lim Reg Rev 5%-150% 80% 63
605 Cur Lim Freq Min Freq-Max Freq 3.0 Hz 63
606 Ramp Time CL 0.1-3200.0 sec 1.0 sec 63
607 Cur Limit Minimum 0 - 50% 10% 63
608 Restart Number text string 0 64
609 Restart Delay 0-60 sec 60 sec 64
610 Timed OL Select text string Std Ind 60s 64
613 Max Regen Ramp 100 - 1000% 300% 64
700 Vmet Config text string Freq Out 65
701 Vmet Span 0.0-200.0% 100.0% 65
702 Imet Config text string Drive Load 65
703 Imet Span 0.0-200.0% 100.0% 65
704 Imet Offset 0.0-90.0-% 0.0% 65
No. Parameter Name Options Default User Setting See Page