www.pulsar.pl POE044816 GREEN POWER CCTV PoE
2. Installation.
2.1. Requirements.
The buffer PSU should be mounted by a qualified installer, holding relevant permits and licenses
(applicable and required for a given country) for 230V/AC and low-voltage installations. The unit should be
mounted in confined spaces, in accordance with the 2nd environmental class, with normal relative humidity
(RH=90% maximum, no condensation) and temperature range from -10°C up to +40°C. The power supply should
operate in a vertical position in order to provide free and convectional air flow through ventilating holes of the
enclosure.
During normal operation, the total current drawn by the device should not exceed
I = 4x0,4A.
The power supply is designed for a continuous operation and is not equipped with a power-
switch. Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the
user should be informed how to disconnect the power supply unit from the mains supply (usually by assigning an
appropriate fuse in the fuse box). The electrical system shall be made in accordance with applicable standards
and regulations.
The PSU is designed for 10Mbit/s and 100Mbit/s Ethernet network (so-called Fast Ethernet). However, it
can not be used for a 1000 Mbit/s network (so-called Gigabit Ethernet). Connections between the power
supply and the camera can be done using UTP-3 cable (networks with data-rates up to 10 Mbit/s) or UTP-5 cable.
Due to the lower resistance wiring, it is recommended (especially at large distances between the power supply and
receivers) to use UTP-5 cable also for networks with data-rates up to 10 Mbit/s.
2.2. Installation procedure.
1. Before installation, cut off the voltage in the 230V power-supply circuit.
2. Mount the PSU in a selected location and lead the connecting cables.
3. If required, mount the switch network (Ethernet Switch / Hub) on the mounting plate (element 6, Figure 3) using cable
ties supplied with the PSU. An example of mounting the Ethernet switch is shown in Figure 4:
Fig.4. An example of mounting the Ethernet switch.
4. Connect the power cables (230V AC) to L-N terminals of the PSU. Connect the ground wire to the terminal marked
with grounding symbol: . Use a three-core cable (with a yellow and green PE protection wire) to make the connection.
The power cables should be connected to the appropriate terminals on the connection board through the bushing.
The shock protection circuit shall be done with a particular care: the yellow and green wire coat
of the power cable should be connected to the terminal marked with the symbol in the
PSU enclosure. Operation of the PSU without the properly made and fully operational shock
protection circuit is UNACCEPTABLE! It can cause damage to the equipment or an electric shock.
5. Connect the network cables (Ethernet) to the PoE module: supply voltage is present only at the AUX sockets and the
cameras should be connected to them. Pin assignment of the AUX and IN sockets is shown in the Figure 5: