LHN248HV

LG LHN248HV Installation guide

  • Hello! I am an AI chatbot trained to assist you with the LG LHN248HV Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ENGLISH
FRANÇAIS
ESPAÑOL
INSTALLATION MANUAL
AIR
CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
Ceilling Concealed Duct
MFL67206507
Rev.06_111419
www.lghvac.com
www.lg.com
Copyright © 2013 - 2019 LG Electronics Inc. All Rights Reserved.
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air
conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
ENGLISH
TIPS FOR SAVING ENERGY
2
TIPS FOR SAVING ENERGY
3
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation of all field wiring and components MUST conform with local building codes or, in the
absence of local codes, with the National Electrical Code 70 and the National Building Construction
and Safety Code or Canadian Electrical code and National Building Code of Canada.
• The information contained in the manual is intended for use by a qualified service technician familiar
with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment
malfunction, property damage, personal injury and/or death.
Installation
• Always perform grounding. - Otherwise, it may cause electrical shock.
• For installation of the product, always contact the service center or a professional installation agency. -
Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached
securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board. - No installation may cause a fire and
electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner. - Otherwise, it may cause a
fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly. - It will cause a fire or electrical shock.
• Do not install the product at a place that there is concern of falling down. - Otherwise, it may result in
personal injury.
• Use caution when unpacking and installing. - Sharp edges may cause injury.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or
Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion. There is the risk of
death, injury, fire or explosion.
!
ENGLISH
SAFETY INSTRUCTIONS
WARNING
This indicates that the failure to follow the instructions can cause serious injury or death.
CAUTION
This indicates that the failure to follow the instructions can cause the minor injury or damage to
the product.
This symbol is displayed to indicate matters and operations that can cause risk.
Read the part with this symbol carefully and follow the instructions in order to avoid risk.
!
!
!
SAFETY INSTRUCTIONS
The following safety guidelines are intended to prevent unforeseen risks or damage from unsafe
or incorrect operation of the appliance.
The guidelines are separated into ‘WARNING’ and ‘CAUTION’ as described below.
• Consult your lacal dealer regarding what to do in case of refrigerant leakage.
When the air conditioner is to be installed in a small room, it is necessary to take proper measures so that
the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen depletion.
• Carry out the specified installation work after taking into account earthquakes.
Failure to do so during installation work may result in the unit falling and causing accidents.
• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried
out by qualified personnel according to local laws and regulations and this installation manual.
An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
• Be sure to switch off the unit before touching any electrical parts.
• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal
connections or wires.
• If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant gas comes into contact with fire.
• Make sure to be materials in a compartment handling air for circulation through a duct supplying only one
room.
Operation
• Unplug the unit if strange sounds, smell, or smoke comes from it. - Otherwise, it may cause electrical
shock or a fire.
• Keep the flames away. - Otherwise, it may cause a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands. -
Otherwise, it may cause a fire or electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation. - Otherwise, it may electrical
shock and failure.
• Do not allow water to run into electrical parts. - Otherwise, it may cause the failure of machine or electrical
shock.
• Never touch the metal parts of the unit when removing the filter. - They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it. - It may cause an injury through
dropping of the unit or falling down.
• When the product is submerged into water, always contact the service center. - Otherwise, it may cause a
fire or electrical shock.
• Take care so that children may not step on the outdoor unit. - Otherwise, children may be seriously injured
due to falling down.
CAUTION
Installation
• Install the drain hose to ensure that drain can be securely done. - Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the
neighbors. - Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product. - Otherwise, it may cause the failure
of product.
• Keep level parallel in installing the product. - Otherwise, it may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes. - Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent. - The appearance of the air
conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or
art articles. - Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet. - Otherwise, it may cause the failure of appliance or
an accident.
!
ENGLISH
SAFETY INSTRUCTIONS
4
ENGLISH
5
2 TIPS FOR SAVING ENERGY
3 SAFETY INSTRUCTIONS
6 INSTALLATION PARTS
7 INSTALLATION
8 Ceiling dimension and hanging bolt location
9 Indoor Unit Installation
11 Air Filter
12 Checking the Drainage
13 Indoor Unit Drain Piping
14 Combination indoor units
15 Flaring work
16 Connection of piping - Indoor, Outdoor, BD Unit
17 Plumbing materials and storage methods
19 Indoor Unit Drain Piping
19 Drain test
20 Heat insulation
20 Wiring Connection
20 Connection method of the connecting cable(Example)
24 REMOTE CONTROLLER INSTALLATION
26 Wired remote controller installation
27 HOW TO SET E.S.P?
27 Installer Setting - E.S.P.
29 SELF-DIAGNOSIS FUNCTION
29 DIP SWITCH SETTING
TABLE OF CONTENTS
TABLE OF CONTENTS
6
ENGLISH
INSTALLATION PARTS
INSTALLATION PARTS
* Screws for fixing panels are attached to decoration panel.
Air outlet vents
Air filters
Control box
Air intake vents
Air filters
Air intake vents
Air outlet vents
Remote Controller
Air inlet vents
Air outlet vents
(Accessory)
Name Drain hose Clamp metal
Washer for
hanging bracket
Clamp
(Tie Wrap)
Insulation for
fitting
Quantity 1 EA 2 EA 8 EA 4 EA 1 set
Shape
for gas pipe
for liquid pipe
ENGLISH
7
INSTALLATION
Install the air conditioner in the location that satisfies the following conditions.
- The place shall easily bear a load exceeding four times the indoor unit’s weight.
- The place shall be able to inspect the unit as the figure.
- The place where the unit shall be leveled.
- The place shall easily connect with the outdoor unit.
- The place where the unit is not affected by an electrical noise.
- The place where air circulation in the room will be good .
- There should not be any heat source or steam near the unit
Confirm the positional relationship between the unit and suspension bolts.
- Installation the ceiling opening to clean the filter or service under the product.
[Unit:mm(inch)]
A(Min)
Ceiling
Service Space
A
B
B(Min)
H=20 (25/32)
or more
• Suitable dimension "H" is necessary to
get a slope to drain as shown in the figure
Side view [Unit: mm(inch)]
Air outlet
Inspection hole
600 x 600
(23-5/8 x 23-5/8)
Control box
600
(23-5/8)
600
(23-5/8)
Top view [Unit: mm(inch)]
Air outlet
Indoor unit
Capacity (kBtu/h)
A B
9
800 (31-1/2) 800 (31-1/2)
12/18
800 (31-1/2) 1 000 (39-3/8)
INSTALLATION
20(25/32) or more
Top view
(unit: mm(inch))
Front view
Front
Inspection hole
600(23-5/8) X 600(23-5/8)
Control box
1 000
(39-3/8)
600(23-5/8) 600(23-5/8)
Make sure to be materials in a compartment handling air for circulation through a duct
supplying only one room.
WARNING
!
8
INSTALLATION
ENGLISH
Ceiling dimension and hanging bolt location
Installation of Unit
Install the unit above the ceiling correctly.
- Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
- Apply a filter Accessory at air return hole.
<TYPE A/D> <TYPE B/C>
[Unit:mm(inch)]
C
E
G
D
F
I
A
J
B
H
Drainage hole
9 k 12 k / 18 k 24 k / 36 k 24 k 36 k 24 k 36 k
Model
AMNW**GL*A*
(TYPE A)
AMNW**GBGA0
(TYPE B)
ABNH**GGLA2
(TYPE C)
AMNW**GM*A0
(TYPE D)
A
733 (28-17/20) 933 (36-37/50) 1 232 (48-1/2) 1 232 (48.5) 1 290(50.8) 933.4 (36-3/4)
1 283.4 (50-17/32)
B
772 (30-2/5) 972 (38-13/50) 1 182 (46-17/32) 1 182 (46.5) 1 230(48.4) 971.6 (38-1/4) 1 321.6 (52-1/32)
C
628 (24-18/25) 628 (24-18/25) 355 (13-31/32) 355 (14) 477(18.8) 619.2 (24-3/8) 619.2 (24-3/8)
D
700 (27-11/20) 700 (27-11/20) 45.5 (1-25/32) 45.5 (1.8) 56(2.2) 700 (27-9/16) 700 (27-9/16)
E
36 (1-2/5) 36 (1-2/5) 450 (17-23/32) 450 (17.7) 590(23.2) 30 (1-3/16) 30 (1-3/16)
F
190 (7-12/25) 190 (7-12/25) 30 (1-3/16) 30 (1.2) 30(1.2) 270 (10-5/8) 270 (10-5/8)
G
20 (25/32) 20 (25/32) 87 (3-7/16) 87 (3.4) 120(4.7) 15.2 (19/32) 15.2 (19/32)
H
660 (25-49/50) 860 (33-17/20) 830 (32-11/16) 830 (32.7) 1 006(39.6) 858 (33-25/32) 1 208 (47-9/16)
I
155 (6-1/10) 155 (6-1/10) 186 (7-5/16) 186 (7.3) 294(11.6) 201.4 (7-15/16) 201.4 (7-15/16)
J
700 (27-11/20) 900 (35-11/25) 298 (11-23/32) 298 (11.7) 380(15) 900 (35-7/16) 1 250 (49-7/32)
Capacity (kBtu/h)
Dimension
POSITION OF SUSPENSION BOLT
h Install the unit leaning to a drainage hole side as a figure for easy water drainage.
Drainage hole
A
B
CD
(G)
EF
Inspection
Port
Indoor Unit
Ceiling
Canvas
Duct
Air Intake
Port
Ceiling
Board
Ceiling Board
Air Discharge
Port
Discharge
Duct
Intake
Duct
body
filter
Joint canvas
Main duct
H
I
J
INSTALLATION
ENGLISH
9
Indoor Unit Installation
M10 Nut
M10 washer
X 4
X 4
M10 Nut
M10 washer
X 4
X 8
- A place where the unit will be leveled and
that can support the weight of the unit.
- A place where the unit can withstand its
vibration.
- A place where service can be easily
performed.
POSITION OF CONSOLE BOLT
- Insert the set anchor and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
- Mount the suspension bolts to the set
anchor firmly.
- Secure the installation plates onto the
suspension bolts (adjust level roughly) using
nuts, washers and spring washers.
- Select and mark the position for fixing bolts.
- Drill the hole for set anchor on the face of
ceiling.
• Local supply
Set anchor
Plate washer - M10
Spring washer - M10
Nut - W3/8 or M10
Suspension bolt - W3/8 or M10
CAUTION
Tighten the nut and bolt to prevent unit
falling.
!
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
<TYPE A/D>
<TYPE B/C>
10
INSTALLATION
ENGLISH
1 Install declination of the indoor unit is very important for the drain of the duct type air
conditioner.
2 Minimum thickness of the insulation for the connecting pipe shall be 5 mm(3/16 inch).
• Always lay the drain with downward
inclination (1/100 to 1/50).
Prevent any upward flow or reverse flow
in any part.
• 10 mm or thicker formed thermal
insulator
shall always be provided for the drain
pipe.
• Install the P-Trap (or U-Trap) to prevent
a water leakage caused by the blocking
of intake air filter.
• Upward routing not allowed
Lay the drain hose with a downward inclination so water will drain out.
• The unit must be declined to the drain hose connected when finished installation.
Front of view
CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING
Ceiling
1/100~1/50
Drainage hole
Drainage hole
CORRECT
INCORRECT
Drainage holeMake sure to be closed.
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
CORRECT
INCORRECT
Applied U-Trap Dimension
CAUTION
!
U-Trap
B
C
A 70 mm(2-3/4 inch)
B ≥ 2C
C ≥ 2 x SP
SP = External Pressure
(mmAq(inAq))
Ex) External Pressure
= 10 mmAq (0.39 inAq)
A 70 mm(2-3/4 inch)
40 mm(1-9/16 inch)
20 mm(25/32 inch)
B ≥
C ≥
A
INSTALLATION
ENGLISH
11
Air Filter
<TYPE A>
Cabinet case
Panel Rear
Air outlet
Air Filter
Panel Rear
Air Filter
Air outlet
Panel Rear
Low static duct type in case of suction from back side.
Low static duct type in case of suction from bottom side.
In case of suction from bottom size, bend the Panel rear and screw with cabinet case.
12
ENGLISH
INSTALLATION
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
THERMAL INSULATION
After all workings are finished, check the working and operation.
• Air distribution ............. Is the air circulation good?
• Drain ............................ Is the drainage smoothly and no sweating?
• Gas leakage ................ Is the piping connection correctly?
• Wiring ......................... Is the wiring connection correctly?
• Lock-bolt ...................... Is the lock-bolt of compressor loosened?
• Insulation ..................... Is the unit fully insulated?
• Ground......................... Is the unit safely grounded?
TEST AND CHECK
Make sure that there is no clearance here.
Overlap with thermal
insulator for piping.
Thermal insulator for refrigerant pipe
(Local supply)
Thermal insulator for
piping(Local supply)
Hose clip for thermal insulator(Local supply)
Refrigerant pipe and thermal
insulator(Local supply)
Thermal insulator for refrigerant pipe
(Local supply)
Hose clip for thermal insulator
(Local supply)
Felt
Insulation
No clearance
Cabinet
Union for liquid pipe
Union for gas pipe
Checking the Drainage
1 Remove the Air Filter.
2 Check the drainage.
- Spray one or two glasses of water upon the evaporator.
- Ensure that water flows drain hose of indoor unit without any leakage.
<TYPE A/D> <TYPE B/C>
<TYPE A/D> <TYPE B/C>
INSTALLATION
ENGLISH
13
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
Indoor Unit Drain Piping (TYPE A/D)
- Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
- During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
- The outside diameter of the drain connection
on the indoor unit is 32 mm(1-1/4 inch).
- Be sure to execute heat insulation on the
drain piping.
Piping material: Polyvinyl chloride pipe
VP-25 and pipe fittings
Heat insulation material: Polyethylene foam
with thickness more than 8 mm(5/16 inch).
Drain test
The air conditioner uses a drain pump to drain
water.
Use the following procedure to test the drain
pump operation:
- Connect the main drain pipe to the exterior
and leave it provisionally until the test comes
to an end.
- Feed water to the flexible drain hose and
check the piping for leakage.
- Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
- When the test is complete, connect the
flexible drain hose to the drain port on the
indoor unit.
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
The supplied flexible drain hose should not
be curved, neither screwed. The curved or
screwed hose may cause a leakage of
water.
• Install declination of the indoor unit is
very important for the drain of the duct
type air conditioner.
• Minimum thickness of the insulation for
the connecting pipe shall be 19 mm(3/4
inch).
The unit must be horizontal or declined to
the drain hose connected when finished
installation.
1/50~1/100 slope
Hanger
distance
Hanger Bracket
Max 700 mm
(27-11/20 inch)
Flexible drain hose
Insulation
Metal
clamp
Max 300 mm
(11-4/5 inch)
1~15 m
(3-7/25
~49-1/5 ft)
Front of view
Drain Pump use
Drainage
hole
Ceiling
HAND OVER
Teach the customer the operation and
maintenance procedures, using the operation
manual.
(air filter cleaning, temperature control, etc.)
CAUTION
!
CAUTION
!
14
INSTALLATION
ENGLISH
Indoor Unit
Outdoor Unit
(Btu/h class)
Type
Capacity
(Btu/h
class)
36 k 54 k
Vertical
AHU
24 k O O
36 k X O
Ceiling
Concealed
Duct
(High
Static)
24 k O O
36 k X O
BD unit (PMBD3641)
A8UW54GFA0
[LMU540HV]
Example)
Total rated capacity index :
4Way CST
AMNW18GTQA0
[LMCN185HV]
18
VAHU
AMNW36GNJA0
[LMVN360HV]
36 x 1.3
Outdoor Unit
(Btu/h class)
Total capacity of connectable
indoor units (Btu/h)
36 k 48 k
54 k 73 k
Combination indoor units
(AMNW**G**A0 / TYPE B / TYPE D)
The indoor units connectable to the outdoor
unit are shown below
NOTE
1. The total capacity(in Btu/h unit) of
connected indoor unit models
represents the total sum of the figures
expressed in the indoor model name.
2. Combinations in which the total capacity
of the connected indoor units exceeds
the capacity of the outdoor unit will
reduce the capacity of each indoor unit
below the rated capacity during
simultaneous operation. Therefore, if
circumstances allows, combine indoor
units within the capacity of the outdoor
unit.
3. VAHU, Ceiling Concealed Duct(High
Static) type indoor unit’s combination
calculation method as below.
Calculation method for total capacity of
connectable indoor unit to an outdoor
unit
= (Sum of all VAHU & Ceiling Concealed
Duct(High Static) type indoor units
capacity
x 1.3) + Sum of all other indoor unit’s
capacity
64.8 < 73
+
=
INSTALLATION
ENGLISH
15
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Flaring work
Main cause of gas leakage is defect in flaring
work. Carry out correct flaring work in the
following procedure.
1 Cut the pipes
- Use the accessory piping kit or the pipes
purchased locally.
- Measure the distance between the
indoor and the outdoor unit.
- Cut the pipes a little longer than
measured distance.
- Cut the cable 1.5 m(4.9 ft) longer than
the pipe length.
2 Burrs removal
- Completely remove all burrs from the cut
cross section of pipe/tube.
- Put the end of the copper tube/pipe to
downward direction as you remove burrs
in order to avoid to let burrs drop in the
tubing.
3 Putting nut on
- Remove flare nuts attached to indoor and
outdoor units, than put them on
pipe/tube having completed burr removal.
(Not possible to put them on after flaring
work)
4 Flaring work
- Carry out flaring work using flaring tool as
shown below.
5 Check
- Compare the flared work with figure.
- If flare is noted to be defective, cut off
the flared section and do flaring work
again.
Firmly hold copper tube in a bar(or die) as
indicated dimension in the table above.
Bar
Copper pipe
"A"
<Wing nut type>
<Clutch type>
Pipe diameter
Inch (mm)
A Inch (mm)
Thickness
Inch (mm)
Wing nut type
Clutch type
Ø 1/4 (Ø 6.35)
0.04~0.05 (1.1~1.3)
0~0.02
(0~0.5)
0.03 (0.7)
Ø 3/8 (Ø 9.52)
0.06~0.07 (1.5~1.7)
0.03 (0.8)
Ø 1/2 (Ø 12.7)
0.06~0.07 (1.6~1.8)
0.03 (0.8)
Ø 5/8 (Ø 15.88)
0.06~0.07 (1.6~1.8)
0.04 (1.0)
Ø 3/4 (Ø 19.05)
0.07~0.08 (1.9~2.1)
0.04 (1.0)
16
INSTALLATION
ENGLISH
Finally, tighten the flare nut with torque
wrench until the wrench clicks.
• When tightening the flare nut with torque
wrench ensure the direction for tightening
follows the arrow on the wrench.
Align the center of the piping and sufficiently
tighten the flare nut by hand.
ODU
Liquid
Gas
IDU
(only indoor units
36 kBtu/h class- connect “D ROOM”)
A ROOM
B ROOM
C ROOM
D ROOM
(only indoor units
24 kBtu/h class)
A ROOM
B ROOM
C ROOM
D ROOM
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
(Only Indoor Units
AMNW18GL2A1)
(Only Indoor Units
24 kBtu/h class )
(PMBD3620 / PMBD3630 /
PMBD3640)
(PMBD3641)
Outside diameter Torque
mm inch N
.
m kgf
.
m lbf
.
ft
Ø 6.35 1/4 14~18 1.4~1.8 10~13
Ø 9.52 3/8 34~42 3.5~4.3 25~31
Ø 12.7 1/2 49~61 5.0~6.2 36~45
Ø 15.88 5/8 69~82 7.0~8.4 51~60
Ø 19.05 3/4 100~120
10.0~12.2
73~88
BD Unit
Refrigerant Connections
Pipe Size (inch (mm))
Connectable
Indoor Unit
Capacity
(kBtu/h class)
Liquid Gas
PMBD3620
1/4 (Ø 6.35)
x 2 EA
3/8 (Ø 9.52)
x 2 EA
9/12/18/24 k
PMBD3630
1/4 (Ø 6.35)
x 3 EA
3/8 (Ø 9.52)
x 3 EA
9/12/18/24 k
PMBD3640
1/4 (Ø 6.35)
x 4 EA
3/8 (Ø 9.52)
x 4 EA
9/12/18/24 k
PMBD3641
1/4 (Ø 6.35)
x 4 EA
3/8 (Ø 9.52)
x 3 EA
9/12/18/24 k
(A/B/C ROOM)
1/2 (Ø 12.7)
x 1 EA
36 k
(D ROOM)
h AMNW18GL2A1 includes the sockets.
Ø 6.35 Ø 9.52 x 1 EA, Ø 12.7
Ø 15.88 x 1 EA, Ø 9.52 Ø 12.7 x 1 EA
ODU Model
Refrigerant
Connections
Pipe size
Liquid Gas
Single
Zone
AMNW18GL2A1
3/8
(Ø 9.52)
5/8
(Ø 15.88)
Connection of piping - Indoor, Outdoor, BD Unit
(AMNW**G**A0 / AMNW18GL2A1 / TYPE B / TYPE D)
h BD Unit(PMBD3641) includes the sockets.
(Ø 12.7 Ø 15.88 x 1 EA,
Ø 6.35 Ø 9.52 x 1 EA)
Capacity
Refrigerant Connections
Pipe size
(kBtu/h) Liquid Gas
24 1/4 (Ø 6.35) 1/2 (Ø 12.7)
36 3/8 (Ø 9.52) 5/8 (Ø 15.88)
INSTALLATION
ENGLISH
17
Drying Cleanliness Airtight
Should be no moisture
inside
No dust inside.
There is no refrigerant
leakage
Items
Moisture
Dust
Leakage
Cause
failure
- Significant hydrolysis of
refrigerant oil
- Degradation of refrigerant
oil
- Poor insulation of the
compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Degradation of refrigerant
oil
- Poor insulation of the
compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Gas shortages
- Degradation of refrigerant
oil
- Poor insulation of the
compressor
- Do not cold and warm
Countermeasure
- No moisture in the pipe
- Until the connection is
completed, the plumbing
pipe entrance should be
strictly controlled.
- Stop plumbing at rainy
day.
- Pipe entrance should be
taken side or bottom.
- When removal burr after
cutting pipe, pipe entrance
should be taken down.
- Pipe entrance should be
fitted cap when pass
through the walls.
- No dust in the pipe.
- Until the connection is
completed, the plumbing
pipe entrance should be
strictly controlled.
- Pipe entrance should be
taken side or bottom.
- When removal burr after
cutting pipe, pipe entrance
should be taken down.
- Pipe entrance should be
fitted cap when pass
through the walls.
- Airtightness test should
be.
- Brazing operations to
comply with standards.
- Flare to comply with
standards.
- Flange connections to
comply with standards.
Plumbing materials and storage methods
Pipe must be able to obtain the specified thickness and should be used with low impurities.
Also when handling storage, pipe must be careful to prevent a fracture, deformity and wound.
Should not be mixed with contaminations such as dust, moisture.
Refrigerant piping on three principles
18
INSTALLATION
ENGLISH
Nitrogen substitution method
Welding, as when heating without nitrogen substitution a large amount of the oxide film is
formed on the internal piping.
The oxide film is a caused by clogging EEV, Capillary, oil hole of accumulator and suction hole of
oil pump in compressor.
It prevents normal operation of the compressor.
In order to avoid this problem, Welding should be done after replacing air by nitrogen gas.
When welding plumbing pipe, the work is required.
How to work
Regulator
Nitrogen gas
Pressure 0.02 MPa less
Auxiliary valve
Taping
(Should not
contain air)
Welding Point
Note) should not block the outlet side.
When the internal pressure in pipe is above
the atmospheric pressure, pinhole is
occurred and it is a leakage cause.
Oxide scale
Nitrogen
1. Always use the nitrogen.(not use oxygen, carbon dioxide, and a Chevron gas):
Please use the following nitrogen pressure 0.02MPa
Oxygen --------- Promotes oxidative degradation of refrigerant oil.
Because it is flammable, it is strictly prohibited to use
Carbon dioxide --- Degrade the drying characteristics of gas
Chevron Gas ---- Toxic gas occurs when exposed to direct flame.
2. Always use a pressure reducing valve.
3. Please do not use commercially available antioxidant.
The residual material seems to be the oxide scale is observed.
In fact, due to the organic acids generated by oxidation of the alcohol contained in the
anti-oxidants, ants nest corrosion occurs. (causes of organic acid alcohol + copper +
water + temperature)
CAUTION
!
INSTALLATION
ENGLISH
19
- Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
- During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
- The outside diameter of the drain connection
on the indoor unit is 32 mm(1-1/4 inch).
- Be sure to execute heat insulation on the
drain piping.
- Install the drain raising pipes at a right
angle to the indoor unit and no more than
300 mm(11-13/16 inch) from the unit.
- Connect the main drain pipe to the exterior
and leave it provisionally until the test comes
to an end.
- Feed water to the flexible drain hose and
check the piping for leakage.
- When the test is complete, connect the
flexible drain hose to the drain port on the
indoor unit.
1 Remove the Air Filter.
2 Check the drainage.
- Spray one or two glasses of water upon
the evaporator.
- Ensure that water flows drain hose of
indoor unit without any leakage.
Drain test
(TYPE B / C )
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
Heat insulation material: Polyethylene foam
with thickness more than 8 mm(5/16 inch).
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Indoor Unit Drain Piping
(TYPE B / C )
20
INSTALLATION
ENGLISH
1 Use the heat insulation material for the
refrigerant piping which has an excellent
heat-resistance (over 120 °C).
2 Precautions in high humidity circumstance:
This air conditioner has been tested
according to the "KS Standard Conditions
with Mist" and confirmed that there is not
any default. However, if it is operated for a
long time in high humid atmosphere (dew
point temperature: more than 23 °C),
water drops are liable to fall. In this case,
add heat insulation material according to
the following procedure:
- Heat insulation material to be prepared...
Adiabatic glass wool with thickness 10 to
20 mm.
- Stick glass wool on all air conditioners
that are located in ceiling atmosphere.
Indoor unit
Thermal insulator
(accessory)
Fastening band
(accessory)
Refrigerant piping
- Remove the control box cover for electrical
connection between the indoor and outdoor
unit. (Remove screws
¿
.)
- Open the control box cover and connect the
Remote controller cord and Indoor power
wires.
- Use the cord clamper to fix the cord.
A
Control box
Control terminal board
Control box cover
(On which the Electric
Wiring Connection is put)
1
1
1(L1) 2(L2) 3
Power Supply
High Voltage
(208/230 V)
Conduit
Conduit panel
Lock nut
Connection method of the
connecting cable(Example)
WARNING
Loose wiring may cause the terminal to
overheat or result in unit malfunction.
A fire hazzard may also exist.
Therefore, be sure all wiring is tightly
connected.
!
Control box
1
1
1
1(L1) 2(L2) 3
Power Supply
High Voltage
(208/230 V)
Conduit
Conduit panel
Lock nut
<TYPE A> <TYPE B/C>
<TYPE A>
<TYPE A>
<TYPE B/C>
<TYPE B/C>
Wiring Connection
Heat insulation
(TYPE B / C / D)
/