Tripp Lite Metered Rack PDU Owner's manual

Category
Power distribution units (PDUs)
Type
Owner's manual

This manual is also suitable for

Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA
www.tripplite.com/support
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be
followed during the installation, operation and storage of this
product. Failure to heed these instructions may affect your warranty.
Important Warnings
• OperatethePDUatindoortemperaturesbetween32°Fand104°F(between0°Cand40°C)only.
• Provideadequateprotectionagainstexcesscurrents,shortcircuits,andgroundfaultsin
accordancewithlocalandnationalelectricalcode,suchasNECintheU.S.
• ThemainssocketthatsuppliesthePDUshouldbenearthePDUandeasilyaccessible.
• ThePDUprovidesconvenientmultipleoutletsbutitDOESNOTprovidesurgeorlinenoise
protectionforconnectedequipment.
• ThePDUisdesignedforindooruseonlyinacontrolledenvironmentawayfromexcessmoisture,
temperatureextremes,conductivecontaminants,dustordirectsunlight.
• DonotconnectthePDUtoanungroundedoutletorextensioncordsoradaptersthateliminatethe
connectiontoground.
• ThepowerrequirementforeachpieceofequipmentconnectedtothePDUmustnotexceedthe
individualoutlet'sloadrating.
• ThetotalpowerrequirementforequipmentconnectedtothePDUmustnotexceedthemaximum
loadratingforthePDU.
• DonotdrillintoorattempttoopenanypartofthePDUhousing.Therearenouser-serviceablepartsinside.
• DonotattempttomodifythePDU,includingtheinputplugsandpowercables.
• DonotattempttousethePDUifanypartofitbecomesdamaged.
• DonotattempttomountthePDUtoaninsecureorunstablesurface.
• Neverattempttoinstallelectricalequipmentduringathunderstorm.
• Useofthisequipmentinlifesupportapplicationswherefailureofthisequipmentcanreasonablybe
expectedtocausethefailureofthelifesupportequipmentortosignificantlyaffectitssafetyor
effectivenessisnotrecommended.Donotusethisequipmentinthepresenceofaflammable
anestheticmixturewithair,oxygenornitrousoxide.
Metered Rack PDUs
Español p. 8 Français p. 15
Copyright©2011TrippLite.Allrightsreserved.
Warranty
Registration
Register online today for a
chance to win a FREE Tripp Lite
product! www.tripplite.com/warranty
Low-Voltage Models: PDUMH15, PDUMH15S, PDUMH20
High-Voltage Models: PDUMH20HV, PDUMH30HV, PDUMH32HV
201103062 93-3059.indd 1 4/29/2011 2:33:39 PM
2
Installation
Note: The illustrations may differ somewhat from your PDU model.
1
Determine Installation Configuration.
The PDUs covered by this owner’s manual
supporttheseinstallationconfigurations:2U,
1Uand0Urackmount;wall-mountandunder-
counter. See below for installation
configurations pertaining to your specific
model.Chooseaconfigurationandfollowthe
installation instructions in the appropriate
sectionofStep1beforeproceedingtoStep2.
Note: Regardless of installation
configuration, the user must determine the
fitness of hardware and procedures before
mounting. The PDU and included hardware
are designed for common rack and rack
enclosure types and may not be appropriate
for all applications. Exact mounting
configurations may vary.
1-1
2U Rack Installation. Attach the
includedbracketstothesideofthePDUwith
theincludedscrews(A).Afterinstallingthe
brackets, position the PDU in the rack and
installfouruser-suppliedscrewsthroughthe
unit’sbracketsandintotherackrails(B).
1-2
1U Rack Installation.AttachthePDU
to the rack by inserting four user-supplied
screws (A) through the PDU mounting
brackets(B)andintothemountingholesof
therackrailasshown.
1-3
0U Rack Installation.Part1:Remove
the screws (C) attaching the mounting
bracketstothePDU,changetheorientation
of the brackets as shown and reattach the
brackets. Use only the screws supplied by
the manufacturer or their exact equivalent
(#6-32, 1/4” flat head). Part 2: Attach the
PDU vertically by inserting two or more
user-supplied screws (A) through the PDU
mounting brackets (B) and into mounting
pointsintherackorrackenclosure.
1-4
Wall Installation.AfterrepeatingPart1
above,attachthePDUtoastablemounting
surface by inserting two or more user-
supplied screws (A) through the PDU
mounting brackets (B) and into secure
mountingpointsonthemountingsurface.
1-5
Under-Counter Installation. After
repeatingPart1above,attachthePDUtoa
stable mounting surface by inserting four
user-supplied screws (A) through the PDU
mountingbrackets(B)andintosecuremountingpointsonthemountingsurface.
A
B
B
A
C
A
B
C
B
C
A
C
A
1-1
B
1-5
1-4
1-2
1-3
201103062 93-3059.indd 2 4/29/2011 2:33:40 PM
3
2
2
Attach the input plug of the PDU to a grounded
outlet. Insert theplug directlyinto agrounded outlet
thatdoesnotshareacircuitwithaheavyelectricalload
(suchasanairconditionerorrefrigerator).
Note: Select models include an input plug adapter that
converts plug types for various applications. See below
for details.
2-1
NEMA Adapter Connection (Optional -
PDUMH20HV Only):ThePDUMH20HVincludesa
plug adapter that adds a NEMA L6-20P plug to the
inputpowercord.Usethisadapteronlyifyouwillbe
connecting the PDUMH20HV to a NEMA L6-20R
outlet.InserttheIEC60320C19connector
A
ofthe
adapter into the IEC 60320 C20 connector
B
of the
input power cord. Secure the connection with the
retention bracket
C
by using the included bolts to
fasten the two halves of the bracket around the
connectionasshown.
Caution: To avoid the risk of electric shock, ensure that
the Neutral (L2) conductor has been identified before
connecting the PDU.
2-2
Input Power Cord Connection (PDUMH20HV
Only): InserttheIEC60320C19connector
A
ofthe
inputpowercordintotheIEC60320C20inlet
B
ofthe
PDU.Connecttheotherendoftheinputpowercord
C
to a compatible source ofACpower, such as a UPS
system, PDU or utility outlet. The PDU should be
providedwith over-currentprotection. PDUMH20HV
shouldbeprovidedwithamaximum20Abranch-rated
over-currentprotectiondevice.
Note: The AC power source should not share a circuit
with a heavy electrical load (such as an air conditioner
or refrigerator).
Installation (continued)
2-1
A
B
C
88
PDUMH20HV
2-2
A
B
C
2-1C
201103062 93-3059.indd 3 4/29/2011 2:33:41 PM
4
Installation (continued)
3
Attach equipment to the PDU.Donotexceedthe
load rating of the PDU. The total electrical current
usedbythePDUwillbedisplayedonthedigitalmeter
inamperes.
3-1
3-2
3-3
201103062 93-3059.indd 4 4/29/2011 2:33:42 PM
5
Features
Input Plug (Varies by Model)
Outlets (Vary by Model): Duringnormaloperation,theoutlets
distributeACpowertoconnectedequipment.
Circuit Breaker: Ifthecurrentdrawnbytheequipment
connectedtothePDUexceedstheMaximumLoadRating,the
circuitbreakerwilltriptopreventpossibledamage.Whena
circuitbreakertrips,itsplungerwillpopup.Disconnectexcess
equipmentandallowthebreakertocoolatleastoneminute
beforedepressingtheplungertoresetthebreaker.
Ammeter: ThetotalelectricalcurrentusedbythePDUwillbe
displayedonthedigitalmeterinamperes.
Grounding Lug: UsethisscrewtoconnectthePDUtoground.
Power Inlet (Select Models):TheIEC-320-C20powerinlet
connectstotheincludedpowercordoracompatibleuser-
suppliedpowercord.Theinletincludesabrackettosecurethe
cordconnection.
Input Plug Adapter (Select Models): Convertsplugtypesfor
variousapplications.
1
2
3
4
6
5
7
NEMA 5-15P
NEMA L5-20P
1
NEMA L6-20P/L6-30P
IEC-320-309P
NEMA 5-15R
NEMA 5-15/20R
IEC-320-C13
IEC-320-C19
5
IEC-320-
C20 INLET
6
NEMA 5-20P
NEMA L5-20R
NEMA L6-20P
IEC-320-C19
2 7
4
3
Thermal 2-Pole Breaker
(PDUMH32HV)
Magnetic, 2-Pole Branch-Rated
Breaker (PDUMH30HV)
201103062 93-3059.indd 5 4/29/2011 2:33:43 PM
6
Longer 1U Mounting Brackets: Usethesebracketstomountthe1UPDUhorizontallyinastandard
rackorrackenclosure.Themountingdepthcanbeadjustedbyattachingthebracketstodifferent
positionsonthePDU.
Shorter 0U Mounting Brackets: UsethesebracketstomountthePDUina0Urack,wallorunder-
counterconfigurationfor1UPDUmodels.
2U Mounting Brackets: Usethesebracketstomountthe2UPDUhorizontallyinastandardrackor
rackenclosure,orinanunder-counterconfiguration.
Cord Retention Shelves (Optional):WheninstalledonthePDU,theseshelvesprovidesecure
attachmentpointsforconnectedequipmentpowercords.Usetheincludedcabletiestosecurecordsto
theshelf.
Features (continued)
8
9
10
11
8 9 10 11
201103062 93-3059.indd 6 4/29/2011 2:33:43 PM
7
Warranty & Warranty Registration
LIMITED LIFETIME WARRANTY
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material
and workmanship for its lifetime. If the product should prove defective in material or workmanship within that period, Seller will
repair or replace the product, at its sole discretion. Service under this Warranty can only be obtained by Buyer delivering or
shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite, 1111 W. 35th Street, Chicago, IL 60609. Seller
will pay return shipping charges. Call Tripp Lite at (773) 869-1234 before sending any equipment back for repair.
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE,
ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET
FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING
ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET
FORTH ABOVE; THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some
states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation
of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you
specific legal rights, and you may have other rights which vary from jurisdiction to jurisdiction).
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since
individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of these devices
for any specific application.
WARRANTY REGISTRATION
Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product. You'll be automatically entered
into a drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique
series number. The series number can be found on the product nameplate label, along with all required approval markings and
information. When requesting compliance information for this product, always refer to the series number. The series number
should not be confused with the marking name or model number of the product.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when
customers buy new electrical and electronic equipment from Tripp Lite they are entitled to:
• Sendoldequipmentforrecyclingonaone-for-one,like-for-likebasis(thisvariesdependingonthecountry)
• Sendthenewequipmentbackforrecyclingwhenthisultimatelybecomeswaste
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
201103062 93-3059-EN
201103062 93-3059.indd 7 4/29/2011 2:33:43 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Tripp Lite Metered Rack PDU Owner's manual

Category
Power distribution units (PDUs)
Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI