Fujitsu UTR-DPB24T is a drain pump unit designed to be assembled with a ceiling type room air conditioner. It features a float switch and drain pump to prevent water leakage and ensure proper drainage of condensate water. The drain pump can lift water up to a maximum height of 500 mm (19-3/4 in.) and can handle a flow rate of up to 24 liters per hour. It also includes a drain pan assembly and various hoses and fittings for easy installation. With its compact size and ease of use, the Fujitsu UTR-DPB24T is an ideal solution for maintaining proper drainage in air conditioning systems.

Fujitsu UTR-DPB24T is a drain pump unit designed to be assembled with a ceiling type room air conditioner. It features a float switch and drain pump to prevent water leakage and ensure proper drainage of condensate water. The drain pump can lift water up to a maximum height of 500 mm (19-3/4 in.) and can handle a flow rate of up to 24 liters per hour. It also includes a drain pan assembly and various hoses and fittings for easy installation. With its compact size and ease of use, the Fujitsu UTR-DPB24T is an ideal solution for maintaining proper drainage in air conditioning systems.

En-1
PART NO. 9360929082
UTR-DPB24T
Français
Español
Italiano
Ελληνικά
Português
Русский
Türkçe
English
Deutsch
DRAIN PUMP UNIT
(AIR CONDITIONER / OPTIONAL PARTS)
INSTALLATION MANUAL
For authorized service personnel only.
Contents
1. SAFETY PRECAUTIONS .........................................................................................1
2. MAIN UNIT AND ACCESSORIES ............................................................................ 1
3. DRAIN UP MECHANISM ASSEMBLY ......................................................................2
4.
INSTALLATION TO INDOOR UNIT .......................................................................... 3
5.
AIR CONDITIONER INSTALLATION .......................................................................6
6.
DRAIN PIPE INSTALLATION ...................................................................................6
7.
TEST RUN ................................................................................................................ 6
1. SAFETY PRECAUTIONS
• Be sure to read this Manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information
pertaining to your safety. Be sure to observe them.
WARNING
This mark indicates procedures which, if improperly performed,
might lead to the death or serious injury of the user.
When installing the Drain Pump, please thoroughly read this manual.
Faulty installation will cause frosting, water leakage, electric shock, re, and/or injury.
Do not turn ON the power until all work has been completed.
Turning ON the power before the work is completed can cause serious accidents such
as electric shock or re.
Connect the indoor unit and drain pump unit with the air conditioner hose and cords
available standards parts. This installation manual describes the correct connections
using the installation set available from our standard parts.
Installation work must be performed in accordance with national wiring standards by
authorized personnel only.
CAUTION
This mark indicates procedures which, if improperly performed,
might possibly result in personal harm to the user, or damage to
property.
The Drain Pump is used by assembling it with a ceiling type room air conditioner. The
Drain Pump cannot be used alone.
Handle the Drain Pump carefully. Dropping it onto the floor or subjecting it to strong
shock will cause erroneous operation or accidents.
When installing the Drain Pump, please refer to the operating manual and installation
manual supplied with the indoor unit.
When using the Drain Pump, the connection pipe outlet direction is up only.
Set up the drain hose for a maximum rise of 500 mm (19-3/4 in.) and give the drain pipe
a down gradient of 1/25 to 1/100. (Fig. 12)
When wiring the power cable and the remote control cable, ensure that they do not
contact the drain pan assy.
2. MAIN UNIT AND ACCESSORIES
The parts listed below are packed with the Drain Pump. Check them before starting in-
stallation work.
Do not discard any accessories needed for installation until the installation work has
been completed.
Name and Shape Q’ty Name and Shape Q’ty
Drain pan assy
1
Installation Manual
1
Drain hose A
1
Drain pump assy
1
Drain hose B
1
En-2
Name and Shape Q’ty Name and Shape Q’ty
Wire (Float switch)
Red
1
Wire (Drain pump)
Blue
1
Cable Tie L
4
Cable Tie LL
2
Insulation
1
Tapping screw
8
Drain pump mount A
(For Type 2)
1
Drain pump mount B
(For Type 2)
1
Drain pump mount C
(For Type 2)
1
Tapping screw
(For Type 2)
6
Type 1 Type 2
Type 1 / Type 2 represent sample images only; the width may vary depending on the
capacity.
3. DRAIN UP MECHANISM ASSEMBLY
(1) Install drain hose B to the drain pump assy. (Fig. 1)
Fig.1
Cable tie L
Drain pan assy
Red
Wire
(Float switch)
Blue
Drain pump assy
Insulation
Drain hose A
Drain hose B
Wire (Drain pump)Cable tie L
(2) Clamp drain hose B with cable tie L. (Fig. 1-1)
Fig.1-1
Cable tie L
Drain pump assy
Drain hose B
4 mm or less
(3) Install drain hose A to the drain pan assy. (Fig. 1)
En-3
(4) Clamp drain hose A with cable tie L.
After cutting the insulation (Fig. 2), cover the connection
parts with insulation. (Fig. 2-1) (Fig. 2-2)
Fig.2 Fig.2-1
Cut
INSULATION
70
±
10 mm
(2-3/4
±
13/23 in.)
Drain hose A
Drain pan assy
Insulation
Cable tie L
Fig.2-2
Cable tie L
Insulation
Drain hose A
No gap
Drain pan assy
or
Indoor unit drain pipe
Type 1: 20±1mm (13/16 ±1/16 in)
Type 2: 10±1mm (3/8 ±1/16 in)
For Type 2
Attach Drain pump mount A, Drain pump mount B, and Drain pump mount C.
Fix them using the tapping screw.
Drain pump mount B
Tapping Screw (2)
Drain pump mount C
Tapping Screw (2)
Drain pump mount A
Tapping Screw (2)
(5) Connect the wire ( oat switch) and wire (drain pump). (Fig. 1)
4.
INSTALLATION TO INDOOR UNIT
When attaching the L-shaped pipe, it is recommended to attach the L-shaped pipe before
attaching the drain pump unit.
For Type 1
(1) Cut a knockout hole for air conditioner top piping (Fig. 4). Remove the burrs created by
cutting using a le, etc.
(2) Remove the indoor unit air lter, grille, side cover, and decoration cover.
(3) Install the Drain pump assy to the indoor unit. (Fig. 3)
(4) Tighten 4 tapping screws. (Fig. 4)
(5) Install the Drain pan assy to the indoor unit. (Fig. 3)
(6) Tighten 4 tapping screws. (Fig. 4)
(7) Insert drain hose A into the indoor unit drain pipe and clamp drain hose A with cable tie
L (Fig. 4), and cover the connecting part with insulation. (Fig. 2-2)
(8) After removing the control box cover, remove the control box body screws.
(9) Insert the wire (Drain pump) and the wire (Float switch) into PCB (Fig. 5) Insert the
lead wire rmly until the connector clicks lock up. The connector No. and the connector
position are di erent in each PCB depending on PCB type. Refer to the table 1-2.
Fig.3
Drain up Mechanism
Grille
Control box cover
Side cover
Decoration cover
A side
Drain pump assy
Drain pan assy
En-4
Fig.4 A side view
Drain hose A
Insulation
Second step
Tapping Screw (4)
for Drain pan assy
Indoor unit
drain pipe
Knockout hole
Drain hose B
First step
Tapping Screw (4)
for Drain pump assy
Cable tie L
Fig.5
Wire (Float switch)
Red
Blue
Wire
(Drain pump)
CN15
CN6
Control box
Red
Blue
(Example. TYPE A)
For Type 2
(1) Cut a knockout hole for air conditioner top piping. Remove the burrs created by cutting
using a le, etc.
(2) Install the Drain pump assy to the indoor unit. (Fig. 6)
(3) Tighten 4 tapping screws. (Fig. 8)
(4) Install the Drain pan assy to the indoor unit. (Fig. 6)
(5) Tighten 4 tapping screws. (Fig. 8)
Prepare a short screw driver because the screw position has a narrow space.
(6) Insert drain hose A into the indoor unit drain pipe and clamp drain hose A with cable tie
L (Fig. 7), and cover the connecting part with insulation. (Fig. 2-2)
(7) Wire the insert the wire (drain pump) and the wire ( oat switch) as shown in Fig.9.
(8) Insert the wire (Drain pump) and the wire (Float switch) into PCB (Fig. 10) Insert the
lead wire rmly until the connector clicks lock up. The connector No. and the connector
position are di erent in each PCB depending on PCB type. Refer to the table 3.
Fig.6
Drain up Mechanism
Drain pump assy
Drain pan assy
Fig.7
Knockout hole
Drain hose B
Indoor unit
drain pipe
Insulation
Cable tie L
Drain hose A
En-5
Fig.8
First step
Tapping Screw (4)
Second step
Tapping Screw (4)
Fig.9
Wire (Float switch)
Clamp
Wire (Drain pump)
Fig.10
Wire (Drain pump)
Blue
Red
Wire (Float switch)
CN9
CN106
Red
Blue
(Example. TYPE F)
Table.1
TYPE A TYPE B TYPE C
PCB
CN15
FLOAT SWITCH
Red
CN6
DRAIN PUMP
Blue
Red
Blue
CN15
FLOAT SWITCH
SUB
PCB
CN5
DRAIN PUMP
CN9
Red
Blue
CN106
DRAIN PUMP
FLOAT SWITCH
FLOAT SWITCH
CN15 (Red) CN15 (Red) CN9 (Red)
DRAIN PUMP CN6 (Blue) CN5 (Blue) CN106 (Blue)
Table.2
TYPE D TYPE E
PCB
CN106
SUB
PCB
CN1
FLOAT
SWITCH
Red
DRAIN PUMP
Blue
CN106
SUB
PCB
CNA05
FLOAT
SWITCH
Red
DRAIN PUMP
Blue
FLOAT SWITCH CN1 (Red) CNA05 (Red)
DRAIN PUMP CN106 (Blue) CN106 (Blue)
En-6
Table.3
TYPE F
PCB
CN106
CN9
FLOAT SWITCH
Red
DRAIN PUMP
Blue
FLOAT SWITCH CN9 (Red)
DRAIN PUMP CN106 (Blue)
5.
AIR CONDITIONER INSTALLATION
(1) Install the indoor unit with Drain Up Mechanism mounted to the ceiling.
When installing the indoor unit, read the installation manual supplied with the indoor
unit.
(2) Set up drain hose B along the connection piping and clamp it with cable tie LL so that it
does not loose.
Fig.11
Cable tie LL
Connection pipe
Drain hose B
Ceiling
6.
DRAIN PIPE INSTALLATION
(1) Connect a drain pipe to drain hose B, as required.
Clamp the connecting part with cable tie L so there will be no water leakage and cover
the connecting part with insulation. Use a drain pipe with a good insulating e ect.
(2) Set up the drain hose for a maximum rise 500 mm (19-3/4 in.) and give the drain pipe a
downward gradient of 1/25 to 1/100. (Fig. 12)
(3) Install the drain pipe so there is no rise, trap, or air bleed. (Fig. 13)
Fig.12
1.5 to 2 m (5 to 6.5 ft)
Max. rise 500 mm
(19-3/4 in.)
Supporter
Indoor unit
Indoor unit
Fig.13
Rise
Trap
Air Bleeding
PROHIBITED
Indoor unit
Indoor unit Indoor unit
7.
TEST RUN
(1) After installation, run the air conditioner in the cooling mode and slowly pour 1.5 to 2.0
liters (3 to 4 pints) of water into the air conditioner outlet section indoor unit drain pan
and check that drain is normal and there is no water leaking from the connections.
(2) To check operation of the safety devices, lift the oat switch with a screwdriver, or
similar device, and check that the indoor unit stops.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Fujitsu UTR-DPB24T Installation guide

Type
Installation guide

Fujitsu UTR-DPB24T is a drain pump unit designed to be assembled with a ceiling type room air conditioner. It features a float switch and drain pump to prevent water leakage and ensure proper drainage of condensate water. The drain pump can lift water up to a maximum height of 500 mm (19-3/4 in.) and can handle a flow rate of up to 24 liters per hour. It also includes a drain pan assembly and various hoses and fittings for easy installation. With its compact size and ease of use, the Fujitsu UTR-DPB24T is an ideal solution for maintaining proper drainage in air conditioning systems.