INSTALLATION MANUAL
OUTDOOR UNIT (1 phase type)
For authorized service personnel only.
MANUEL D’INSTALLATION
UNITÉ EXTÉRIEUR (Type 1 phase)
Pour le personnel de service agrée uniquement.
AIR TO WATER HEAT PUMP
En-1
1. SAFETY PRECAUTIONS
Be sure to read this manual carefully before installation.
The warnings and precautions indicated in this manual contain important information
pertaining to your safety. Be sure to observe them.
Hand this manual, together with the operating manual, to the customer. Request the cus-
tomer to keep them on hand for future use, such as for relocating or repairing the unit.
WARNING
Indicates a potentially or imminently hazardous situation which,
if not avoided, could result in death or serious injury.
Installation of this product must be done by experienced service technicians or profes-
sional installers only in accordance with this manual. Installation by nonprofessional or
improper installation of the product may cause serious accidents such as injury, water
leakage, electric shock, or re. If the product is installed in disregard of the instructions in
this manual, it will void the manufacturer’s warranty.
To avoid getting an electric shock, never touch the electrical components soon after the
power supply has been turned off. After turning off the power, always wait 10 minutes or
more before you touch the electrical components.
Do not turn on the power until all work has been completed. Turning on the power be-
fore the work is completed can cause serious accidents such as electric shock or re.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a ame, it produces a toxic gas.
Installation must be performed in accordance with regulations, codes, or standards for
electrical wiring and equipment in each country, region, or the installation place.
Do not use this equipment with air or any other unspeci ed refrigerant in the refrigerant
lines. Excess pressure can cause a rupture.
If there is a refrigerant leak, make sure that it does not exceed the concentration limit.
If a refrigerant leak exceeds the concentration limit, it can lead to accidents such as
oxygen starvation.
During installation, make sure that the refrigerant pipe is attached rmly before you run
the compressor.
Do not operate the compressor under the condition of refrigerant piping not attached
properly with 3-way valve open. This may cause abnormal pressure in the refrigeration
cycle that leads to rupture and even injury.
When installing and relocating the air conditioner, do not mix gases other than the
speci ed refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to
an abnormally high value and cause rupture, injury, etc.
To connect the indoor unit and outdoor unit, use air conditioner piping and cables avail-
able locally as standard parts. This manual describes proper connections using such
installation set.
Do not modify power cable, use extension cable or branch wiring. Improper use may
cause electric shock or re by poor connection, insuf cient insulation or over current.
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.
There is no extra refrigerant in the outdoor unit for air purging.
Use a vacuum pump for R410A exclusively.
Using the same vacuum pump for different refrigerants may damage the vacuum pump
or the unit.
Use a clean gauge manifold and charging hose for R410A exclusively.
During the pump-down operation, make sure that the compressor is turned off before
you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 3-way
valve open.
This may cause abnormal pressure in the refrigeration cycle that leads to rupture and
even injury.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised to ensure that they
do not play with the appliance.
To avoid danger of suffocation, keep the plastic bag or thin lm used as the packaging
material away from young children.
CAUTION
Indicates a potentially hazardous situation that may result in
minor or moderate injury or damage to property.
For the air conditioner to work appropriately, install it as written in this manual.
This product must be installed by quali ed personnel with a capacity certi cation of
handling refrigerant uids. Refer to regulation and laws in use on installation place.
Install the product by following local codes and regulations in force at the place of instal-
lation, and the instructions provided by the manufacturer.
This product is part of a set constituting an air conditioner. The product must not be
installed alone or be installed with a device not authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3 mm for this product.
To protect the persons, earth (ground) the product correctly, and use the power cable
combined with an Earth Leakage Circuit Breaker (ELCB).
This product is not explosion proof, and therefore should not be installed in explosive
atmosphere.
Do not touch the ns of the heat exchanger. Touching the heat exchanger ns could
result in damage to the ns or personal injury such as skin rupture.
This product contains no user-serviceable parts. Always consult experienced service
technicians for repairing.
When moving or relocating the air conditioner, consult experienced service technicians
for disconnection and reinstallation of the product.
Do not place any other electrical products or household belongings under the product.
Condensation dripping from the product might get them wet, and may cause damage or
malfunction to the property.
• This product is conformed to IEC/EN61000-3-2.
• This product is designed for professional use.
• On the power supply connection, obtain the connection permission of the distribution
network operator.
• Be sure to use a dedicated power circuit.
Never use a power supply shared by another appliance.
This unit must be connected to a power supply with impedance of 0.414 ohm and
below. If the power supply does not satisfy this requirement, please consult the power
supplier.
INSTALLATION MANUAL
OUTDOOR UNIT [Original instructions]
PART No. 9380545279 English
Contents
1. SAFETY PRECAUTIONS ............................................................................................... 1
2. ABOUT THE UNIT .......................................................................................................... 2
2.1. Precautions for using R410A refrigerant .............................................................. 2
2.2. Special tools for R410A ....................................................................................... 2
2.3. Accessories ......................................................................................................... 2
3. INSTALLATION WORK .................................................................................................. 2
3.1. Selecting an installation location ......................................................................... 2
3.2. Drain installation .................................................................................................. 3
3.3. Installation dimensions ........................................................................................ 3
3.4. Transporting the unit ............................................................................................ 4
3.5. Installing the unit .................................................................................................. 4
4. PIPE SELECTION .......................................................................................................... 5
4.1. Selecting the pipe material .................................................................................. 5
4.2. Protection of pipes ............................................................................................... 5
4.3. Refrigerant pipe size and allowable piping length ............................................... 5
5. PIPE INSTALLATION-1 .................................................................................................. 5
5.1. Opening a knock out hole .................................................................................... 5
5.2. Brazing ................................................................................................................ 5
5.3. Flare connection .................................................................................................. 6
5.4. Pipe connection ................................................................................................... 6
5.5. Connection System ............................................................................................. 7
5.6. Sealing test .......................................................................................................... 7
5.7. Vacuum process .................................................................................................. 7
5.8. Additional charging .............................................................................................. 7
6. ELECTRICAL WIRING ................................................................................................... 8
6.1. Selecting circuit breaker and wiring ..................................................................... 8
6.2. Notes for electrical wiring .................................................................................... 8
6.3. Knock out holes for wiring ................................................................................... 9
6.4. Wiring method ..................................................................................................... 9
7. PIPE INSTALLATION-2 ................................................................................................ 10
7.1. Installing insulation ............................................................................................ 10
7.2. Filling with putty ................................................................................................. 10
8. HOW TO OPERATE FIELD SETTING BUTTONS ....................................................... 10
8.1. Display and buttons position .............................................................................. 10
8.2. Description of display and button ...................................................................... 10
9. FIELD SETTING ........................................................................................................... 10
9.1. Function settings ............................................................................................... 10
10. EXTERNAL INPUT AND OUTPUT ............................................................................. 12
10.1. External input ................................................................................................... 12
10.2. External output ................................................................................................ 13
11. TEST RUN .................................................................................................................. 13
12. ERROR CODES ......................................................................................................... 13
12.1. Error display mode .......................................................................................... 13
12.2. Error code check table ..................................................................................... 14
13. PUMP DOWN ............................................................................................................. 14
13.1. Preparation for pump down ............................................................................. 14
13.2. Pump down procedure .................................................................................... 14
En-2
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts. The use of non-prescribed parts can cause serious accidents
such as the unit falling, water leakage, electric shock, or re.
• The following installation parts are supplied. Use them as required.
• Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Name and shape Q’ty Description
Installation
manual
1
(This manual)
Drain cap
9
For outdoor unit drain piping work
Drain pipe
1
For outdoor unit drain piping work
Auxiliary pipe
1
For connecting gas pipe
(L type)
Push mount cable tie
2
For binding connection cable
Grommet edging
2
For power supply cable and con-
nection cable installation.
Attach to the knockout hole.
3. INSTALLATION WORK
• Make sure to obtain the customer’s approval for selecting and installing the outdoor
unit.
3.1. Selecting an installation location
WARNING
Securely install the outdoor unit at a location that can withstand the weight of the unit.
Otherwise, the outdoor unit may fall and cause injury.
Be sure to install the outdoor unit as prescribed, so that it can withstand earthquakes
and typhoons or other strong winds. Improper installation can cause the unit to topple
or fall, or cause other accidents.
Do not install the outdoor unit near the edge of a balcony. Otherwise, children may
climb onto the outdoor unit and fall off of the balcony.
2. ABOUT THE UNIT
2.1. Precautions for using R410A refrigerant
WARNING
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
areas. Touching the refrigerant directly can cause frostbite.
If a refrigerant leak occurs during operation, immediately vacate the premises and thor-
oughly ventilate the area. If the refrigerant comes in contact with a ame, it produces a
toxic gas.
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
• Since the working pressure is 1.6 times higher than that of conventional refrigerant
(R22) models, some of the piping and installation and service tools are special. (See
the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refriger-
ant R410A model, always replace the conventional piping and are nuts with the
R410A piping and are nuts.
• Models that use refrigerant R410A have a different charging port thread diameter to
prevent erroneous charging with conventional refrigerant (R22) and for safety. There-
fore, check beforehand. [The charging port thread diameter for R410A is 1/2-20 UNF.]
• Be careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant models. Also, when storing the piping, securely seal the openings by
pinching, taping, etc.
• When charging the refrigerant, take into account the slight change in the composition
of the gas and liquid phases. And always charge from the liquid phase where refriger-
ant composition is stable.
2.2. Special tools for R410A
WARNING
To install a unit that uses R410A refrigerant, use dedicated tools and piping materials that
have been manufactured speci cally for R410A use. Because the pressure of R410A
refrigerant is approximately 1.6 times higher than R22, failure to use dedicated piping
material or improper installation can cause rupture or injury. Furthermore, it can cause
serious accidents such as water leakage, electric shock, or re.
Tool name
Contents of change
Gauge manifold
Pressure is high and cannot be measured with a conventional
gauge. To prevent erroneous mixing of other refrigerants, the
diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa
(-1 to 53 bar) for high pressure. –0.1 to 3.8 MPa (-1 to 38 bar)
for low pressure.
Charge hose
To increase pressure resistance, the hose material and base
size were changed.
Vacuum pump
A conventional vacuum pump can be used by installing a
vacuum pump adapter. Be sure that the pump oil does not
back- ow into the system. Use one capable for vacuum suc-
tion of –100.7 kPa (5 Torr, –755 mmHg).
Gas leakage
detector
Special gas leakage detector for HFC refrigerant R410A.
En-3
CAUTION
Do not install the outdoor unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts,
causing the parts to fail or the unit to leak water.
• Area lled with mineral oil or containing a large amount of splashed oil or steam,
such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit
to leak water.
• Area that generates substances that adversely affect the equipment, such as
sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed
joints to corrode, which can cause refrigerant leakage.
• Area containing equipment that generates electromagnetic interference. It will
cause the control system to malfunction, preventing the unit from operating
normally.
• Area that can cause combustible gas to leak, contains suspended carbon bers or
ammable dust, or volatile in ammables such as paint thinner or gasoline. If gas
leaks and settles around the unit, it can cause a re.
• Area that has heat sources, vapors, or the risk of the leakage of ammable gas in
the vicinity.
• Area where small animals may live. It may cause failure, smoke or re if small
animals enter and touch internal electrical parts.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not tilt the outdoor unit more than 0.3 degrees.
Install the outdoor unit in a well-ventilated location away from rain or direct sunlight.
If the outdoor unit must be installed in an area within easy reach of the general public,
install as necessary a protective fence or the like to prevent their access.
Install the outdoor unit in a location that would not inconvenience your neighbors, as
they could be affected by the air ow coming out from the outlet, noise, or vibration. If it
must be installed in proximity to your neighbors, be sure to obtain their approval.
If the outdoor unit is installed in a cold region that is affected by snow accumulation,
snow fall, or freezing, take appropriate measures to protect it from those elements. To
ensure a stable operation, install inlet and outlet ducts.
Install the unit in an area that would not cause problems even if the drain water is
discharged from the unit. Otherwise, provide drainage that would not affect people or
objects.
Install the outdoor unit in a location that is away from exhaust or the vent ports that
discharge vapor, soot, dust, or debris.
Install the indoor unit, outdoor unit, power supply cable, connection cable, and remote
controller cable at least 1 m away from a television or radio receivers. The purpose of
this is to prevent TV reception interference or radio noise. (Even if they are installed
more than 1 m apart, you could still receive noise under some signal conditions.)
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
Keep the length of the piping of the indoor and outdoor units within the allowable range.
For maintenance purposes, do not bury the piping.
3.2. Drain installation
CAUTION
Perform drain work in accordance with this Manual, and ensure that the drain water
is properly drained. If the drain work is not carried out correctly, water may drip down
from the unit, wetting the furniture.
When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may
freeze in extremely cold weather. (Reverse cycle model only)
• If you are installing the drain pipe and drain caps,
please provide a working space under the base of
the outdoor unit.
• As the drain water ows out of the outdoor unit
during heating operation, install the drain pipe and
connect it to a commercial 16 mm hose. (Reverse
cycle model only)
• When installing the drain pipe, plug all the holes
other than the drain pipe mounting hole in the
bottom of the outdoor unit with putty so there is no
water leakage. (Reverse cycle model only)
Base of the outdoor unit
Drain pipe
Drain pipe mounting hole
446
600
Air
Unit: mm
Drain cap mounting
hole × 9
Drain pipe
mounting hole
3.3. Installation dimensions
CAUTION
Consider the transportation route, installation space, maintenance space, and access,
and install the unit in a location with suf cient space for the refrigerant piping.
Keep the space shown in the installation
examples.
If the installation is not performed accordingly, it
could cause a short circuit and result in a lack of
operating performance.
Air intake
Rear
Front
Do not obstruct the air intake of the outdoor unit
with piping, wiring, stand, etc.
Installation methods not shown in the following examples are not recommended.
Performance may drop signi cantly.
3.3.1. Single outdoor unit installation
When the upward area is open (Unit : mm)
(1) Obstacles at rear only
(2) Obstacles at rear and sides
(3) Obstacles at front only
(4) Obstacles at front and rear
1000 or more
100
or more
300
or more
80
or more
1000 or more
100 or more
100
or more
En-4
When an obstruction is present also in the upward area (Unit : mm)
(1) Obstacles at rear and above
(2) Obstacles at rear, sides, and above
100
or more
Max. 500
1000
or more
1500
or more
80
or more
100
or more
300
or more
3.3.2. Multiple outdoor unit installation
• Provide at least 100 mm of space between the outdoor units if multiple units are
installed.
• When routing the piping from the side of an outdoor unit, provide space for the piping.
• No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the
following example when an obstruction is present also in the upward area.
When the upward area is open (Unit : mm)
(1) Obstacles at rear only
(2) Obstacles at front only
1500 or more
300 or more
(3) Obstacles at front and rear
500 or more
1500 or more
When an obstruction is present also in the upward area (Unit : mm)
• Obstacles at rear and above only
1500 or more
500 or more
Max. 300
1500 or more
3.3.3. Outdoor unit installation in multi row
* The following settings are not recommended in case of cooling by a low outside tem-
perature. (Unit: mm)
(1) Single parallel unit arrangement (2) Multiple parallel unit arrangement
100 or
more
600 or more
1000 or more
2000 or
more
500 or
more
600 or more
1500 or more
3000 or
more
3.4. Transporting the unit
WARNING
Do not touch the ns. Otherwise, personal injury could result.
CAUTION
When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or ngers may be pinched.
Hoisting method
• When hoisting the outdoor unit, hook the rope on the outside of the foot as shown in
the gure.
• Use suf ciently strong rope to bear the unit’s weight.
• Place protective board or ller cloth at the place where the cabinet may come into
contact with the rope to prevent damages. Without using them, the cabinet may be
damaged or deformed.
• The center of gravity of the outdoor unit is shifted to the right. Be careful not to tilt to
the heavy side causing it to fall.
• To prevent accidents caused by the unit swinging or falling down, do not apply any
impact to the unit when it is hanging.
• When hoisting, do not hook the rope to the thermistor holder on the back of the
outdoor unit.
Protective
boards
Foot
Light
side
Heavy
side
700 to
1000 mm
Lifting by forklift
• When using the forklift to lift the unit, pass
the forklift arms through the opening space
of the wooden delivery pallet.
• Be careful not to damage.
Wooden delivery
pallet
Carrying by hand
• Carry slowly in the manner
as shown on “Fig. B” hold-
ing the handles “Fig. A”
in right and left sides. (Be
careful not to touch with
hands or objects.)
• Be sure to hold the
handles on the sides of
the unit. Otherwise, the
suction grilles on the
sides of the unit may be
deformed.
Handle
Handle
Handle
Fig. A Fig. B
3.5. Installing the unit
• Install 4 anchor bolts at the locations indicated with arrows in the figure.
• To reduce vibration, do not install the unit directly on the ground. Install it on a secure
base (such as concrete blocks).
The foundation shall support the legs of the unit and have a width of 80 mm or more.
• Depending on the installation conditions, the outdoor unit may spread its vibration during
operation, which may cause noise and vibration. Therefore, attach damping materials
(such as damping pads) to the outdoor unit during installation.
• Install the foundation, making sure that there is enough space for installing the connec-
tion pipes.
• Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially avail-
able M10 to M12 bolts, nuts, and washers.)
• The bolts should protrude 20 mm. (Refer to the figure.)
• If overturning prevention is required, purchase the necessary commercially available
items.
Air
688 195195
80 80
19
20
516
Unit: mm
Bolt
Nut
Base
Product mass
(Kg)
137
En-5
• Do not install directly on the ground, this may result in equipment failure.
• The drain water is discharged from the bottom of the equipment. Construct a drain ditch
around the base and discharge the drain water properly
• Provide ample space for ice buildup from condensate between the bottom of the unit and
the flat surface on which it is mounted. Otherwise, there is risk that the drainage water
will freeze between the device and the surface, disabling drainage.
Base
CAUTION
If the unit is installed in a region that is exposed to
high winds, freezing conditions, freezing rain, snow
fall or heavy snow accumulation, take appropriate
measures to protect it from those elements.
To ensure stable operation, the outdoor unit must be
installed on a raised stand or rack, at or above the
anticipated snow depth for the region.
The installation of snow hoods and drift prevention
fencing is recommended when blowing and drifting
snow is common to the region.
4. PIPE SELECTION
4.1. Selecting the pipe material
CAUTION
Do not use existing pipes.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material: Phosphor deoxidized seamless copper pipes.
It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion
(especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A
incurs pressure higher than when using conventional refrigerant, it is necessary to
choose adequate materials.
• Thicknesses of copper pipes used with R410A are as shown in the table.
• Never use copper pipes thinner than those indicated in the table even if they are
available on the market.
Table. A (Wall thickness and pipe material for each diameter)
Outside Diameter mm
6.35 9.52 12.70 15.88 19.05
Wall Thickness *2 mm
0.8 0.8 0.8 1.0 1.2
Material
COPPER *1
JIS H3300 C1220T-O or equivalent
Please select the pipe size in accordance with local rules.
*1: Allowable tensile stress 33 (N/mm
2
)
*2: Endurance pressure of the pipes 4.2MPa
4.2. Protection of pipes
• Protect the pipes to prevent the entry of moisture and dust.
• Especially, pay attention when passing the pipes through a hole or connecting the
end of a pipe to the outdoor unit.
Location Working period Protection method
Outdoor
1 month or more Pinch pipes
Less than 1 month Pinch or tape pipes
Indoor - Pinch or tape pipes
4.3. Refrigerant pipe size and allowable piping length
CAUTION
Keep the piping length between the indoor unit and outdoor unit within the allowable
tolerance.
Pipe diameter <Liquid/Gas> [mm (in.)] 9.52 (3/8) / 15.88 (5/8)
Max. piping length (L) [m] 30*
Min. piping length (L) [m] 5
Max. height difference <H1/H2>
<Indoor unit to outdoor unit> [m]
15 / 25
View (Example)
H1
L
H2
L
*: For the standard pipe diameter.
5. PIPE INSTALLATION-1
5.1. Opening a knock out hole
CAUTION
Be careful not to deform or scratch the panel while opening the knock out holes.
To protect the piping insulation after opening a knock out hole, remove any burrs from
the edge of the hole. It is recommended to apply rust prevention paint to the edge of
the hole.
• Pipes can be connected from 3 directions, front, lateral side and bottom. (Fig. A)
• When connecting at the bottom, remove the service panel and piping cover on the front
of the outdoor unit, and open the knockout hole provided at the bottom corner of the
piping outlet.
9221
61 100
94 21
61 94
60 12
14 90
Unit: mm
Fig. A
Service panel
Top view of
the base
Front connection Lateral connection Bottom connection
• It can be installed as shown on “Fig. B” cutting out the 2 slits as indicated on “Fig. C”.
(When cutting slits, use a steel saw.)
Slit
Slit
Fig. B
Bottom
connection
Fig. C
5.2. Brazing
CAUTION
If air or another type of refrigerant enters the refrigeration cycle, the internal pressure in
the refrigeration cycle will become abnormally high and prevent the unit from exerting
its full performance.
Apply nitrogen gas while brazing the pipes. If a pipe is brazed without applying nitro-
gen gas, an oxidation lm will be created.
This can degrade performance or damage the parts
in the unit (such as the compressor or valves).
Nitrogen gas pressure: 0.02 MPa
(= pressure felt suf ciently on the back of the hand)
Pressure regulating valve
Cap
Brazing area
Nitrogen gas
En-6
CAUTION
For brazing material, use phosphor copper that does not require ux. Do not use ux to
braze pipes. If the ux is the chlorine type, it will cause the pipes to corrode.
Furthermore, if the ux contains uoride, it will adversely affect the refrigerant pipe
system such as by degrading the refrigerant.
If uoride is contained, quality of refrigerant deteriorates and affects the refrigerant
piping system.
5.3. Flare connection
CAUTION
Do not use mineral oil on a ared part. Prevent mineral oil from getting into the system
as this would reduce the lifetime of the units.
While welding the pipes, be sure to blow dry nitrogen gas through them.
The maximum lengths of this product are shown in the table. If the units are further
apart than this, correct operation cannot be guaranteed.
5.3.1. Flaring
• Use special pipe cutter and are tool exclusive for R410A.
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2)
Hold the pipe downward so that the cuttings will not enter the pipe and remove any burrs.
(3) Insert the are nut (always use the are nut attached to the indoor and outdoor
units respectively) onto the pipe and perform the are processing with a are tool.
Leakage of refrigerant may result if other are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
Check if [L] is ared uniformly
and is not cracked or scratched.
B
L
Pipe
A
Die
Pipe outside diameter
[mm (in.)]
Dimension A
[mm]
Dimension B
[mm]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
• When using conventional are tools to are R410A pipes, the dimension A should
be approximately 0.5 mm more than indicated in the table (for aring with R410A
are tools) to achieve the speci ed aring. Use a thickness gauge to measure the
dimension A.
Width across ats
5.4. Pipe connection
5.4.1. Bending pipes
CAUTION
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of
curvature of 100 mm to 150 mm.
If the pipe is bent repeatedly at the same place, it will break
.
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes at an angle of more than 90°.
• When pipes are repeatedly bent or stretched, the material will harden, making it
dif cult to bend or stretch them anymore.
• Do not bend or stretch the pipes more than three times.
5.4.2. Pipe connection
CAUTION
Be sure to install the pipe against the port on the indoor unit and the outdoor unit
correctly. If the centering is improper, the are nut cannot be tightened smoothly. If the
are nut is forced to turn, the threads will be damaged.
Do not remove the are nut from the outdoor unit pipe until immediately before
connecting the connection pipe.
After installing the piping, make sure that the connection pipes do not touch the
compressor or outer panel. If the pipes touch the compressor or outer panel, they will
vibrate and produce noise.
(1) Detach the caps and plugs from the pipes.
(2) Center the pipe against the port on the outdoor unit, and then turn the are nut by
hand.
(3) Tighten the are nut of the connection pipe at the outdoor unit valve connector.
3-way valve (Liquid)
3-way valve (Gas)
Flare nut
Connection pipe
(Liquid)
Flare nut
Connection pipe
(Gas)
(4) After tightening the are nut by hand, use a torque wrench to fully tighten it.
CAUTION
Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to
tighten the are nut correctly.
• Outer panel may be distorted if fastened only with a wrench. Be sure to x the
elementary part with a spanner and fasten with a wrench (refer to below diagram).
• Do not apply force to the blank cap of the valve or hang a wrench, etc., on the cap. It may
cause leakage of refrigerant.
90°
Blank cap
Flare nut
Torque wrench
Holding
wrench
Torque wrench
Flare nut
[mm (in.)]
Tightening torque
[N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1100)
* Connection example
Front connection Lateral connection
Liquid pipe
(locally purchased)
Gas pipe
(locally purchased)
Auxiliary pipe
(accessory)
Gas pipe
(locally purchased)
Auxiliary pipe
(accessory)
Liquid pipe
(locally purchased)
Pipe outside
diameter
[mm (in.)]
Width across ats
of Flare nut
[mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
0
- 0.4
En-7
5.4.3. Handling precautions for the valves
• Mounted part of Blank cap is sealed for protection.
• Fasten blank cap tightly after opening valves.
Table A
Blank cap [mm (in.)] Tightening torque [N·m (kgf·cm)]
6.35 (1/4) 20 to 25 (200 to 250)
9.52 (3/8) 20 to 25 (200 to 250)
12.70 (1/2) 28 to 32 (280 to 320)
15.88 (5/8) 30 to 35 (300 to 350)
19.05 (3/4) 35 to 40 (350 to 400)
Operating the valves
• Use a hexagon wrench (size 3/16 in (4 mm)).
Opening:
(1) Insert the hexagon wrench into the
valve shaft, and turn it counterclock-
wise.
(2) Stop turning when the valve shaft can
no longer be turned. (Open position)
Closing:
(1) Insert the hexagon wrench into the
valve shaft, and turn it clockwise.
(2) Stop turning when the valve shaft can
no longer be turned. (Closed position)
Opening
direction
Hexagon wrench
Seal
(blank cap
installation
portion)
Liquid
pipe
Gas pipe
Opening
direction
5.5. Connection System
Fig. A Connection system
Outdoor unit
Pressure gauge
Vacuum
pump
Scale
R410A
Pressure regulating valve
Nitrogen
Indoor unit
Fig. B
Charging cap
Valve
Cap
Close
Hexagon
wrench
Close
Open
Open
Spindle
Table. A
Pipe Spindle Cap Charging cap
Liquid valve
6.0 to 7.0 N·m
(60 to 70 kgf·cm)
20.0 to 25.0 N·m
(200 to 250 kgf·cm)
10.0 to 12.0 N·m
(100 to 120 kgf·cm)
Gas valve
6.0 to 7.0 N·m
(60 to 70 kgf·cm)
30.0 to 35.0 N·m
(300 to 350 kgf·cm)
10.0 to 12.0 N·m
(100 to 120 kgf·cm)
5.6. Sealing test
CAUTION
Use only nitrogen gas.
Never use refrigerant gas, oxygen, in ammable gas, or poisonous gas to pressurize
the system.
(If oxygen is used, there is the danger of an explosion.)
Do not apply shock during sealing test.
It can rupture the pipes and cause serious injury.
Do not turn on the power unless all operations are complete.
CAUTION
Do not block the walls and the ceiling until the sealing test and the charging of the
refrigerant gas have been completed.
After connecting the pipes, perform a sealing test.
(1) Recheck that the spindle of the 3-way valve are closed before performing a sealing
test. (Refer to “5.5. Connecction System”, Fig. B)
(2) Pressurize nitrogen gas to 4.2 MPa to perform the sealing test.
(3) Add nitrogen gas to both the liquid pipes and the gas pipes.
(4) Check all are connection areas and welded areas. Then, check that the pressure
has not decreased.
(5) Compare the pressures after pressurizing and letting it stand for 24 hours, and
check that the pressure has not decreased.
* When the outdoor temperature changes 5 °C, the test pressure changes 0.05 MPa.
If the pressure has dropped, the pipe joints may be leaking.
(6) If a leakage is found, immediately repair it and perform the sealing test again.
* Decrease the pressure of nitrogen gas before blazing.
(7) After completing the sealing test, release the nitrogen gas from both valves.
Release the nitrogen gas slowly.
5.7. Vacuum process
CAUTION
Do not turn on the power unless all operations are complete.
If the system is not evacuated suf ciently, its performance will drop.
Be sure to evacuate the refrigerant system using a vacuum pump.
The refrigerant pressure may sometimes not rise when a closed valve is opened after
the system is evacuated using a vacuum pump. This is caused by the closure of the
refrigerant system of the outdoor unit by the electronic expansion valve. This will not
affect the operation of the unit.
Use a clean gauge manifold and charging hose that were designed speci cally for use
with R410A. Using the same vacuum equipment for different refrigerants may damage
the vacuum pump or the unit.
Do not purge the air with refrigerants, but use a vacuum pump to evacuate the system.
If moisture might enter the piping, follow below.
(I.e., if doing work during the rainy season, if the actual work takes long enough that
condensation may form on the inside of the pipes, if rain might enter the pipes during
work, etc.)
After operating the vacuum pump for two hours, pressurize to 0.05 MPa (i.e., vacuum
breakdown) with nitrogen gas, then depressurize down to -100.7kPa (-755mmHg) for
an hour using the vacuum pump (vacuum process).
If the pressure does not reach -100.7kPa (-755mmHg) even after depressurizing for at
least two hours, repeat the vacuum breakdown - vacuum process.
After vacuum process, maintain the vacuum for an hour and make sure the pressure
does not rise by monitoring with a vacuum gauge.
Evacuation procedure
(1) Remove the caps of the gas pipe and liquid pipe and check that the valves are
closed.
(2) Remove the charging cap.
(3) Connect a vacuum pump and a pressure gauge to a charging hose and connect it
to the charging port.
(4) Activate the vacuum pump and vacuum the indoor unit and connection piping until
the pressure gauge becomes -100.7kPa (-755mmHg).
Evacuate from both the gas pipe and the liquid pipe.
(5) Continue evacuating the system for 1 hour after the pressure gauge reads
-100.7kPa (-755mmHg).
(6) Remove the charging hose and reinstall the charging cap.
5.8. Additional charging
CAUTION
Do not turn on the power unless all operations are complete.
After evacuating the system, add refrigerant.
Do not charge the system with a refrigerant other than R410A.
Always keep to the limit on the total amount of refrigerant. Exceeding the limit on the
total amount of refrigerant will lead to malfunction during charging of refrigerant.
Do not reuse recovered refrigerant.
Use an electronic scale to measure the charging amount of refrigerant.
Adding more refrigerant than the speci ed amount will cause a malfunction.
Add refrigerant by charging the system with the refrigerant in the liquid state.
When charging the refrigerant, take into account the slight change in the composition
of the gas and liquid phases, and always charge from the liquid phase side whose com-
position is stable. Adding refrigerant through the gas pipe will cause a malfunction.
En-8
6.2. Notes for electrical wiring
WARNING
Wiring connections must be performed by a qualified person in accordance with speci-
fications.
The voltage rating for this product is 230 V at 50 Hz. Use a voltage within the range of
198 to 264 V (50 Hz).
Make sure to perform earthing (grounding) work. Improper earthing (grounding) work
can cause electric shocks.
Before connecting the cables, make sure the power supply is OFF.
Be sure to install an earth (ground) leakage breaker. Otherwise, it will cause electric
shock or fire.
Select a breaker (Included with earth leakage circuit breaker) of appropriate capacity
and install one at every power supply of an outdoor unit. Wrong selection of breakers or
transition wiring will lead to electric shock and fire.
Do not connect AC power supply to the transmission line terminal board.
Improper wiring can damage the entire system.
Install a breaker (Included with earth leakage circuit breaker) in accordance with the
related laws and regulations.
Connect the connector cable securely to the terminal.
Faulty installation can cause a fire.
Make sure to secure the insulation portion of the connector cable with the cable clamp.
A damaged insulation can cause a short circuit.
Never install a power factor improvement condenser. Instead of improving the power
factor, the condenser may overheat.
Before servicing the unit, turn the power supply switch OFF. Then, do not touch electric
parts for 10 minutes due to the risk of electric shock.
Always use a separate power supply line protected by a circuit breaker operating on all
cables with a distance between contact of 3 mm for this unit.
Do not modify power cable, use extension cable or branch wiring. Improper use may
cause electric shock or fire by poor connection, insufficient insulation or over current.
Use ring terminals and tighten the terminal screws to the specified torques, otherwise,
abnormal overheating may be produced and possibly cause serious damage inside the
unit.
Securely install the electrical box cover on the unit. An improperly installed service
panel can cause serious accidents such as electric shock or fire through exposure to
dust or water.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
CAUTION
The primary power supply capacity is for the air conditioner itself, and does not include
the concurrent use of other devices.
Connect the power cables in positive phase sequence. If there is a missing phase con-
nection, the unit will not operate normally.
Do not use crossover power supply wiring for the outdoor unit.
If the electrical power is inadequate, contact your electric power company.
Install a breaker (Included with earth leakage circuit breaker) in a location that is not
exposed to high temperatures.
If the temperature surrounding the breaker is too high, the amperage at which the
breaker cuts out may decrease.
Use a breaker (Included with earth leakage circuit breaker) that is capable of handling
high frequencies. Because the outdoor unit is inverter controlled, a high-frequency earth
leakage circuit breaker is necessary to prevent a malfunction of the breaker itself.
When the electrical switchboard is installed outdoors, place it under lock and key so that
it is not easily accessible.
Never bundle the power supply cable and connection cable, remote control cable
together. Separate these cable by 50 mm or more. Bundling these cables together will
cause miss operation or breakdown.
Always keep to the maximum length of the connection cable. Exceeding the maximum
length may lead to erroneous operation.
The static electricity that is charged to the human body can damage the control PC
board when handling the control PC board for address setting, etc.
Please keep caution to the following points.
Provide the grounding of Indoor unit, Outdoor unit and Option equipment.
Cut off the power supply (breaker).
Touch the metal section (such as the unpainted control box section) of the indoor or
outdoor unit for more than 10 seconds. Discharge the static electricity in your body.
Never touch the component terminal or pattern on the PC board.
How to connect wiring to the terminal
Caution when wiring cable
• When stripping off the coating of a lead wire, always use a special tool such as a wire
stripper. If there is no special tool available, carefully strip the coating with a knife etc.
(1) Use ring terminals with insulating sleeves as shown in the gure below to connect
to the terminal block.
(2) Securely clamp the ring terminals to the wires using an appropriate tool so that the
wires do not come loose.
Sleeve
Strip : 10 mm
Ring terminal
CAUTION
Check if the steel cylinder has a siphon installed or not before lling. (There is an indi-
cation “with siphon for lling liquid” on the steel cylinder.)
Filling method for cylinder with siphon
Set the cylinder vertical and ll with the liquid.
(Liquid can be lled without turning bottom up with the
siphon inside.)
Liquid
Gas
R410A
Filling method for other cylinders
Turn bottom up and ll with liquid.
(Be careful to avoid turning over the cylinder.)
Liquid
Gas
R410A
Be sure to use the special tools for R410A for pressure resistance and to avoid mixing
of impure substances.
If the units are further apart than the maximum pipe length, correct operation cannot be
guaranteed.
Make sure to back closing valve after refrigerant charging. Otherwise, the compressor
may fail.
Minimize refrigerant release to the air. Excessive release is prohibited under the Freon
Collection and Destruction Law.
5.8.1. If additional refrigerant is required
When the piping is longer than chargeless piping length, additional charging is neces-
sary.
1) Remove the charging cap from the liquid pipe.
2) Attach a charging hose to the refrigerant cylinder, and connect it to the charging
port.
3) Add refrigerant by calculating the additional refrigerant volume in accordance with
the table below.
4) Remove the charging hose and install the charging cap.
5) Remove the body caps (gas pipe, and liquid pipe), and open the valves.
6) Close the body caps.
* Tighten the body caps and charging caps to the torque values speci ed in the Table A.
To open and close the valves;
Use an M5 hexagon wrench for liquid pipes.
Use an M10 hexagon wrench for gas pipes.
Piping length (L1) *Chargeless [m]
15
Additional charging amount
L1* > Chargeless piping length
Refrigerant pipe size
[mm (in.)]
Piping length
Standard ~15 m 20 m 25 m 30 m g/m
Liquid Gas
9.52 (3/8)
15.88 (5/8)
None
250 g 500 g 750 g 50 g/m
Refer to “4.3. Refrigerant pipe size and allowable piping length”.
6. ELECTRICAL WIRING
6.1. Selecting circuit breaker and wiring
• Decide the diameter of wire referring to below table “Breaker and wiring
speci cations” in accordance with local and national codes.
Breaker and wiring speci cations
Breaker
capacity
[A]
Power supply cable Connection cable*
Conductor size
[mm²]
Conductor size
[mm²]
Max. length
[m]
32 6.0 min. 1.5 min. 50
*: If the Connection cable is longer than 50m, use a bigger conductor size.
• Use con rmed cable with type 60245 IEC 57.
• Perform all electrical work according to standard.
• Install a circuit breaker with a contact gap of at least
3 mm in all poles near the units. (Both indoor units and outdoor units)
• Install the circuit breaker near the units.
En-9
(3) Use the speci ed wires, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
Wire
Screw with special washer
Ring terminal
Terminal blocks
Screw with
special washer
Wire
Ring terminal
(6) See the table below for the terminal screw tightening torques.
Tightening torque [N·m (kgf·cm)]
M4 screw 1.2 to 1.8 (12 to 18)
M5 screw 2.0 to 3.0 (20 to 30)
6.3. Knock out holes for wiring
CAUTION
Be careful not to deform or scratch the panel while opening the knockout holes.
After opening the knockout holes, remove burr on the edges, and attach the one-touch
bush (accessory), grommet or conduit etc. to prevent damaging the cables.
It is recommended to apply rust proof paint on the edges to prevent rust.
Knockout holes are provided in front and lateral sides for wiring.
Unit: mm
Ø50
Ø50
Ø34.5
Ø34.5
Ø22.2
Ø22.2
L
Length of the grommet edging Mounting the grommet edging
Grommet edging
(accessories)
Knockout hole
Knockout hole
diameter (mm)
Dimension L
(mm)
Ø 50 147
Ø 34.5 100
Ø 22.2 60
6.4. Wiring method
6.4.1. Connection diagrams
3
2
1
3
2
1
N
L
Power supply line
Power line
Earthing (Grounding) line
Indoor unit
side terminal
Outdoor unit
side terminal
Control line
EARTH
(GROUND)
EARTH
(GROUND)
EARTH
(GROUND)
6.4.2. Connection cable preparation
• Keep the earth wire longer than the other wires.
Earth wire
30 mm
Power supply cable or
Connection cable
35 mm
6.4.3. Wiring procedure
(1) Remove the service panel, the terminal cover and connect the wires to the terminal
in accordance with the terminal nameplate. (Fig. A, Fig. B)
(2) Secure the cables using the cable clamps under the terminal blocks. (Fig. B)
• Connect the wires without applying excessive tension.
(3) Secure the cables using the cable ties at the base of the valves. (Fig. A)
Fig. A
Push mount
cable tie
(accessory)
Cable tie
Power supply
cable
Connection cable
Terminal blocks
Fig. B
L N
POWER INDOOR UNIT
1 2 3
Terminal nameplate
Power supply
cable
Terminal blocks
Connection cable
(indoor unit and
outdoor unit con-
nection cable)
(4) Be sure to install the terminal cover after the wiring is complete.
En-10
7. PIPE INSTALLATION-2
7.1. Installing insulation
• Use an insulation on the refrigerant pipes to prevent burn injury, condensation and
dripping.
7.2. Filling with putty
WARNING
Putty
Insulation
Fig. A
Fill the piping holes and wiring holes with putty
(locally purchased) to avoid any gap (Fig A). If
small animals such as insects enter the external
unit, a short circuit may be caused near electrical
components in the service panel.
If the outdoor unit is installed at a level that is higher
than the indoor unit, the water that has condensed
in the 3-way valve of the outdoor unit could travel
to the indoor unit. Therefore, use putty in the space
between the pipe and the insulation to prevent the
entry of water to the indoor units.
8. HOW TO OPERATE FIELD SETTING BUTTONS
8.1. Display and buttons position
WARNING
Never touch electrical components such as the terminal blocks except the button on
the display board. It may cause a serious accident such as electric shock.
CAUTION
Once refrigerant charging is completed, be sure to open the valve prior to performing
the local settings. Otherwise, the compressor may fail.
Discharge any static electricity from your body before touching the push buttons.
Never touch any terminal or pattern of any parts on the control board.
• Remove the front panel of the outdoor unit to access the print circuit board of the
display unit.
• The positions of the buttons on the outdoor unit control board are shown in the gure
below.
• Various settings can be adjusted by changing Push buttons on the board of the outdoor
unit.
LED display and button
• The printed characters for the LED display are shown below.
SW107
SW108 SW109 SW112 SW110
LED display part
Button part
8.2. Description of display and button
Display lamp
Function or operation method
(1) POWER / MODE Green
Lights on while power on. Local setting in out-
door unit or error code is displayed with blink.
(2) ERROR Red
Blinks during abnormal air-conditioner
operation.
(3) PUMP DOWN
(L1)
Orange
Lights on during pump down operation.
(4) LOW NOISE
MODE
(L2, L3)
Orange
Lights on during “Low noise” function when
local setting is activated. (Lighting pattern of L2
and L3 indicates low noise level)
*See page 11.
(5) PEAK CUT
(L4, L5, L6)
Orange
Lights on during “Peak cut” function when local
setting is activated. (Lighting pattern of L4, L5
and L6 indicates peak cut level)
*See page 11.
Button
Function or operation method
SW107 MODE/EXIT
To switch between “Local setting” and “Error code
display”.
SW108 SELECT
To switch between the individual “Local settings”
and the “Error code displays”.
SW109 ENTER
To x the individual “Local settings” and the “Error
code displays”.
SW112 EXIT To return to “Operation status displays.”
SW110 PUMP DOWN To start the pump down operation.
9. FIELD SETTING
CAUTION
Discharge the static electricity from your body before setting up the switches.
Never touch the terminals or the patterns on the parts that are mounted on the board.
9.1. Function settings
• Various functions can be set. Follow the setting methods described in 9.1.1. to 9.1.4.
to set as per the requirement.
Perform these settings after the indoor unit stops.
En-11
Table. Settings List
No Setting Item
LED display
Factory
setting
Content
POWER/
MODE
ERROR
PUMP
DOWN
LOW NOISE PEAK CUT
(L1) (L2) (L3) (L4) (L5) (L6)
1
Low noise
mode
Level 1
Blink
(9 times)
○○○ ○○
By using the “Low noise mode”, the limit of the
noise level will be set to decrease the noise
level. The mode comes in 2 levels which can
be set accordingly.
To turn on the mode, use the external input
terminal (CN131).
*By using this mode, the cooling/heating perfor-
mance may decrease.
*Depending on the operating condition, the
noise level may not decrease even if the Low
noise mode is on.
Level 2
Blink
(9 times)
○○○
2
Peak cut
mode
Level 1
Blink
(9 times)
○○ ○○○
The capacity limit can be selected when
operating with the “Peak cut mode.” The opera-
tion selection can be done by external input
terminal (CN132)
The higher the level, the more the effect of
energy saving, but the cooling/heating perfor-
mance decreases.
Level 2
Blink
(9 times)
○○ ○○
Level 3
Blink
(9 times)
○○ ○○
Level 4
Blink
(9 times)
○○ ○○
3
Base heater
control
Level 1
Blink
(9 times)
○○ ○○
This mode changes the operating time of the
base heater. In order to control the base heater,
connection to a separate base heater (locally
purchased) is necessary.
By changing the mode to Level 1, the base
heater control mentioned in “10.3.2.” will be On
at all times.
Level 2
Blink
(9 times)
○○
4
Defrost determi-
nation control
Level 1
Blink
(9 times)
○○○○
Setting this function enables quicker defrost
determination.
Level 2
Blink
(9 times)
○○○
Sign “
”: Lights off, “
”: Lights on
9.1.1. Setting for Low noise mode
(1)
Switch to “Local setting mode” by pressing [MODE] button (SW107) for 3 seconds or more.
(2) Con rm (POWER / MODE) blinks 9 times, and press [ENTER] button (SW109).
POWER/
MODE
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
Blink
(9 times)
○○○○
Sign “
”: Lights off, “
”: Lights on, () : Number of blinking
(3) Press [SELECT] button (SW108), and adjust LED display as shown below.
(Current setting is displayed)
LOW NOISE
(L2) (L3)
Low noise mode
Blink
Sign “
”: Lights off
(4) Press [ENTER] button (SW109).
LOW NOISE
(L2) (L3)
Low noise mode
Sign “
”: Lights off, “
”: Lights on
(5) Press [SELECT] button (SW108), and adjust LED lamp as shown in below gure.
PEAK CUT
(L4) (L5) (L6)
Level 1 (Low)
○○
Blink
Level 2 (Lower)
Blink
Sign “
”: Lights off
The noise of Level 2 is lower than the one of Level 1.
(6) Press [ENTER] button (SW109) and x it.
PEAK CUT
(L4) (L5) (L6)
Level 1 (Low)
○○
Level 2 (Lower)
Sign “
”: Lights off, “
”: Lights on
(7)
Return to “Operating status display (Normal operation)” by pressing [EXIT] button (SW112).
• In case of missing how many times [SELECT] and [ENTER] button are pressed,
restart from the beginning of operation procedure after returning to “Operation status
display (normal operation)” by pressing the [EXIT] button once.
9.1.2. Setting for peak cut mode
(1)
Switch to “Local setting mode” by pressing [MODE] button (SW107) for 3 seconds or more.
(2) Con rm (POWER / MODE) blinks 9 times, and press [ENTER] button (SW109).
POWER/
MODE
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
Blink
(9 times)
○○○○○
Sign “
”: Lights off, “
”: Lights on, () : Number of blinking
(3) Press [SELECT] button (SW108), and adjust LED lamp as shown below. (Current
setting is displayed)
LOW NOISE
(L2) (L3)
Peak cut mode
Blink
Sign “
”: Lights off
(4) Press [ENTER] button (SW109).
LOW NOISE
(L2) (L3)
Peak cut mode
Sign “
”: Lights off, “
”: Lights on
(5) Press [SELECT] button (SW108), and adjust LED lamp as shown in below gure.
PEAK CUT
(L4) (L5) (L6)
Level 1 100% of rated input ratio
○○Blink
Level 2 75% of rated input ratio
Blink
Level 3 50% of rated input ratio
Blink Blink
Level 4 0% of rated input ratio
Blink
○○
Sign “
”: Lights off
En-12
(6) Press [ENTER] button (SW109) and x it.
PEAK CUT
(L4) (L5) (L6)
Level 1 100% of rated input ratio
○○
Level 2 75% of rated input ratio
Level 3 50% of rated input ratio
Level 4 0% of rated input ratio
○○
Sign “
”: Lights off, “
”: Lights on
(7) Return to “Operating status display (Normal operation)” by pressing [EXIT] button
(SW112).
• When pressed number is lost during operation, restart from the beginning of operation
procedure after returning to “Operation status display (normal operation)” by pressing
the [EXIT] button once.
9.1.3. Setting for Base heater control
(1)
Switch to “Local setting mode” by pressing [MODE] button (SW107) for 3 seconds or more.
(2) Con rm (POWER / MODE) blinks 9 times, and press [ENTER] button (SW109).
POWER/
MODE
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
Blink
(9 times)
○○○○
Sign “
”: Lights off, “
”: Lights on, () : Number of blinking
(3) Press [SELECT] button (SW108), and adjust LED display as shown below.
(Current setting is displayed)
LOW NOISE
(L2) (L3)
Base heater control
Blink Blink
Sign “
”: Lights off
(4) Press [ENTER] button (SW109).
LOW NOISE
(L2) (L3)
Base heater control
Sign “
”: Lights off, “
”: Lights on
(5) Press [SELECT] button (SW108), and adjust LED lamp as shown in below gure.
PEAK CUT
(L4) (L5) (L6)
Level 1 (On at all times)
○○
Blink
Level 2 (Normal)
Blink
Sign “
”: Lights off
The noise of Level 2 is lower than the one of Level 1.
(6) Press [ENTER] button (SW109) and x it.
PEAK CUT
(L4) (L5) (L6)
Level 1 (On at all times)
○○
Level 2 (Normal)
Sign “
”: Lights off, “
”: Lights on
(7)
Return to “Operating status display (Normal operation)” by pressing [EXIT] button (SW112).
• In case of missing how many times [SELECT] and [ENTER] button are pressed,
restart from the beginning of operation procedure after returning to “Operation status
display (normal operation)” by pressing the [EXIT] button once.
9.1.4. Setting for Defrost determination control
(1)
Switch to “Local setting mode” by pressing [MODE] button (SW107) for 3 seconds or more.
(2) Con rm (POWER / MODE) blinks 9 times, and press [ENTER] button (SW109).
POWER/
MODE
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
Blink
(9 times)
○○○○○
Sign “
”: Lights off, “
”: Lights on, () : Number of blinking
(3) Press [SELECT] button (SW108), and adjust LED lamp as shown below. (Current
setting is displayed)
PUMP DOWN LOW NOISE
(L1) (L2) (L3)
Defrost determina-
tion control
Blink
○○
Sign “
”: Lights off
10. EXTERNAL INPUT AND OUTPUT
Outdoor unit PC board
10.1. External input
10.1.1. Wiring of connector
ON/OFF of the “Low noise mode”, and “Peak cut mode” functions can be enabled with an
external eld device.
When installing connection cable, speci ed part (UTY-XWZXZ3) must be used.
Refer to section 9.1. Table. Settings List, for the required function. The function must be
set for the external input to work.
Input Connector
Low noise mode CN131
Peak cut mode CN132
* Make the distance from the PC board to the connected unit within 10m (33ft).
(4) Press [ENTER] button (SW109).
PUMP DOWN LOW NOISE
(L1) (L2) (L3)
Defrost determina-
tion control
○○
Sign “
”: Lights off, “
”: Lights on
(5) Press [SELECT] button (SW108), and adjust LED lamp as shown in below gure.
PEAK CUT
(L4) (L5) (L6)
Level 1 (Normal)
○○
Blink
Level 2 (Quicker)
Blink
Sign “
”: Lights off
(6) Press [ENTER] button (SW109) and x it.
PEAK CUT
(L4) (L5) (L6)
Level 1 (Normal)
○○
Level 2 (Quicker)
Sign “
”: Lights off, “
”: Lights on
(7) Return to “Operating status display (Normal operation)” by pressing [EXIT] button
(SW112).
• When pressed number is lost during operation, restart from the beginning of operation
procedure after returning to “Operation status display (normal operation)” by pressing
the [EXIT] button once.
En-13
The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
CN131
CN132
Circuit diagram example
Outdoor unit control
PC board
Connected unit
(Locally purchased)
Example) Switch
Connection cable (option)
Signal
Connector
*10m (33ft)
10.1.2. Low noise mode (CN131)
This features reduces the operating sound of the outdoor unit from the normal sound.
The air conditioner is set to the “Low noise mode” when closing the contact input of a
commercial timer or ON/OFF switch to a connector on the outdoor control PC board.
* Performance may drop depending on the outside air temperature condition, etc.
* Set the “Low noise mode” level, refer to “9.1. Function settings”.
Input Signal ···ON : Low noise mode
···OFF : Normal operation
Input Signal
Low noise mode
ON
ON
OFF
OFF
10.1.3. Peak cut mode (CN132)
Operation that suppressed the current value can be performed by means of the
connected unit. The air conditioner is set to the Peak cut mode by applying the contact
input of a commercial ON/OFF switch to a connector on the outdoor control PC board.
* Set the “Peak cut mode” level, refer to “9.1. Function settings”.
Input Signal ···ON : Peak cut mode
···OFF : Normal operation
Input Signal
Peak cut mode
ON
ON
OFF
OFF
10.2. External output
10.2.1. Wiring of connector
When installing connection cable, speci ed part (UTY-XWZXZ3) must be used.
Output Connector
Error status CN136
Base heater control CN137
* Make the distance from the PC board to the connected unit within 10m (33ft).
1) Power supply
• Voltage (Chart sign=Vcc) : DC 24V or less
2) Load
• Load : DC 500mA or less is recommended
10.2.2. Error status output (CN136)
CN136
Circuit diagram example
Outdoor unit control
PC board
Connected unit
(Locally purchased)
Connection
cable
Signal
*10m (33ft)
Connector
Load
Power
supply
An air conditioner error status signal is produced when a malfunction occurs.
Error status
Output signal
Error
ON
Normal
OFF
10.2.3. Base heater control output (CN137)
This is the output signal for the base heater. The output signal is on, when the outdoor
temperature drops below 2
o
C, and signal is off when it rises to 5
o
C.
Outdoor unit control
CN137
PC board
Connector
Relay
DC power
AC power
Heater *
*: The allowable current is 1A or less.
11. TEST RUN
CAUTION
Always turn on the power 6 hours prior to the start of the operation in order to protect
the compressor.
Before performing the test run, make sure that the 3-way valve is open.
• Perform test run described in installation manual of indoor unit.
12. ERROR CODES
You can determine the operating status by the lighting up and blinking of the LED lamp.
SW107
SW108 SW109 SW112 SW110
LED display part
Button part
12.1. Error display mode
12.1.1. Display when an error occurs
POWER/
MODE
ERROR
LOW NOISE PEAK CUT
(L1) (L2) (L3) (L4) (L5)
Blink
(Hi speed)
○○○○
(1) Check that the “ERROR” LED blinks, and then “short-press” the [ENTER] switch once.
12.1.2. Display while an error code is blinking
POWER/
MODE
ERROR
LOW NOISE PEAK CUT
(L1) (L2) (L3) (L4) (L5)
Blinks
(Twice)
Blinks
○○○○
(2) The “POWER MODE” LED will blink twice and the “ERROR” LED will blink several times.
• The number of blinks of the “ERROR” LED varies according to the type of error. For
details, refer to the “Error code check table”.
En-14
12.2. Error code check table
Number of
blinks (LED)
Error type
1 Serial forward transfer error
2 Discharge thermistor error
3 Pressure sensor error
4 Heat-exchange thermistor (outlet) error
5
Heat-exchange thermistor (intermediate)
error
6 Expansion valve thermistor error
7 Outdoor temperature thermistor error
8 Compressor thermistor error
9 Heatsink thermistor (inverter) error
10 Heatsink thermistor (P.F.C.) error
11
Discharge temperature protection
(permanent stoppage)
12
Compressor temperature protection
(permanent stoppage)
13 Current trip (permanent stoppage)
14
Detection of compressor position error
(permanent stoppage)
15
Compressor start up error (permanent
stoppage)
16 Fan motor (1) error (permanent stoppage)
17 Fan motor (2) error (permanent stoppage)
18 Inverter error
19 P.F.C. error
20 Low pressure abnormal
21 Connection with indoor unit error
22 Indoor unit abnormality condition
23 Discharge (high pressure) pressure sensor error
24 Suction (low pressure) pressure sensor error
13. PUMP DOWN
WARNING
Never touch electrical components such as the terminal blocks except the button on
the display board. It may cause a serious accident such as electric shock.
During the pump-down operation, make sure that the compressor is turned off before
you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2-way or
3-way valve open. This may cause abnormal pressure in the refrigeration cycle that
leads to breakage and even injury.
CAUTION
Perform the pump down operation before disconnecting any refrigerant pipe or electric
cable.
Collect refrigerant from the service port or the 3-way valve if pump down cannot be
performed.
In case of a group control system installation, do not turn the power off until pump down
is completed in all outdoor units.
(Group control system installation described in “SPECIAL INSTALLATION METHODS”
in the installation manual of the indoor unit.)
• Operate [PUMP DOWN] button on the display board in the manner described
below.
SW107
SW108 SW109 SW112 SW110
LED display part
Button part
13.1. Preparation for pump down
• Con rm that the power is off, and then open the service panel.
13.2. Pump down procedure
(1) Check the 3-way valves (both the liquid side and gas side) are opened.
(2) Turn the power on.
POWER/
MODE
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
○○○○○
Sign “
”: Lights off, “
”: Lights on
(3) Press [PUMP DOWN] button for 3 seconds or more after 3 minutes after power on.
POWER/
MODE
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
○○●●●
Sign “
”: Lights off, “
”: Lights on
LED display lights on as shown in the above gure, and the fans and the
compressor start operating.
• If the [PUMP DOWN] button is pressed while the compressor is operating, the
compressor will stop, then start again in about 3 minutes.
(4) LED display will change as shown below about 3 minutes after the compressor
starts. Fully close the 3-way valve on the liquid pipe side at this stage.
POWER/
MODE
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
○○○●●
Sign “
”: Lights off, “
”: Lights on
• If the valve on the liquid pipe side is not closed, the pump down cannot be performed.
En-15
(5) When LED display changes as shown in the below gure, close the 3-way valve on
the gas pipe side tightly.
POWER/
MODE
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
○○○○●
Sign “
”: Lights off, “
”: Lights on
• If the valve on the gas pipe side is not closed, refrigerant may ow into the piping
after the compressor stops.
Step (5)
Closing direction
Step (4)
Hexagon wrench
Liquid pipe
Gas pipe
Closing direction
(6) LED display changes after 1 minute as shown in the gure below.
POWER/
MODE
ERROR
PUMP
DOWN
LOW NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
○○○○○
Sign “
”: Lights off, “
”: Lights on
Fans and compressor stop automatically.
• If the pump down is successfully completed (the above LED display is shown), the
outdoor unit remains stopped until the power is turned off.
(7) Turn the power off.
POWER/
MODE
ERROR
PUMP
DOWN
LOW NOISE
PEAK
CUT
(L1) (L2) (L3) (L4) (L5) (L6)
○○○○○
Sign “
”: Lights off
Pump down is completed.
NOTES:
• To stop pump down, press the [PUMP DOWN] button again.
• To start the pump down again after the compressor is automatically stopped due to
an error, disconnect the power supply and open the 3-way valves. Wait 3 minutes,
reconnect the power supply and start the pump down again.
• When starting the operation after completion of the pump down, disconnect the power
supply, and then open the 3-way valves. Wait 3 minutes, reconnect the power supply
and perform a test run in the “COOL” operation mode.
• If an error occurs, recover the refrigerant from service port.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16