red lion MDMU Pre User manual

Category
Electrical timers
Type
User manual
O
LCD, POSITIVE REFLECTIVE OR NEGATIVE TRANSMISSIVE
WITH YELLOW/GREEN OR RED BACKLIGHTING
O
COUNTER, TIMER, & TACH ALL IN A SINGLE UNIT
O
RATE MULTIPLIER/PRESCALER FROM 0.0001 TO 1.9999 IN
COUNT AND TACH MODES
O
9 RANGES IN TIMER MODE
O
SELECTABLE DECIMAL POINTS
O
5 VDC POWERED
O
PANEL MOUNT OR PC BOARD MOUNT
DESCRIPTION
The MDMU is a complete 6 digit Counter/Timer/Tach in a small panel or
printed circuit board mounted package. It is designed to operate from a 5 VDC
power supply. It has a 6 digit LCD, with 0.35" high digits, and 5 selectable
decimal points. In the timer modes, a flashing annunciator is supplied to indicate
that the signal input of the MDMU is active. The displays are available in
positive image reflective (black digits, reflective background) or negative image
transmissive (illuminated digits, dark background) with red or yellow/green
backlighting.
The MDMU has four Mode Select and three Decimal Point Select inputs
available for determining the basic operation. Certain functions can also be
selected through programming. In most applications, the MS and DP inputs are
hard wired to select the appropriate function (counter, timer and tach) and
decimal point position (counter and tach only). If changes to the MDMU
configuration are required, or if a rate multiplier/prescale is desired, the
PROGRAM input must be used to enter the appropriate information.
The COUNTER mode is selected by setting the Mode select inputs to the
appropriate levels (Hardware selection). Decimal points may also be set using
the DP Inputs (Hardware selection). If a prescale is required, a value of 0.0001
to 1.9999 and a decimal point of 0 through 0.00000 can be selected using the
PROGRAM input. Either the Count (CNT) or LSC (digitally debounced input)
inputs can be used.
Note: If programming options are entered, the counter increments on the
opposite edge of the input signal.
The TIMER mode and range is selected by either setting the Mode Select
inputs to the appropriate levels (Hardware selection) or by selecting the range
using the PROGRAM input. The timing range increments available are 1 msec,
10 msec, 100 msec, 1 sec, 0.1 min, 1 min, 0.01 hr, 0.1 hr, and 1 hr. The TIMER
ACTIVE annunciator will flash at a 2 Hz rate when the input to the timer is
activated. Either the CNT or the LSC inputs can be used. The Inhibit (INH)
input can be used to enable or disable Leading Zero Blanking (LZB).
The TACH mode can be selected by setting the Mode Select inputs to the
appropriate levels (Hardware selection). In the tach mode, the MDMU operates
as a fixed 1 second time base tachometer. Using the PROGRAM input, the time
base can be set to 1 through 7 seconds (in whole second increments). The rate
multiplier can also be programmed from 0.0001 thru 1.9999. Decimal points
can be set from 0 thru 0.00000. Decimal points may also be set using the DP
Inputs. Either the CNT or the LSC inputs can be used.
Note: If Programming options are entered, the counter increments on the
opposite edge of the input signal.
The integrated circuit is bonded directly to the printed circuit board and is
mechanically protected. Internal electrical interface connections use elastomeric
connectors to provide a corrosion resistant connection. This reliable
construction also reduces the space requirements.
MODEL MDMU - MINIATURE DISPLAY MODULE COUNTER/TIMER/TACH
DIMENSIONS Note: Recommended minimum clearance behind the panel for mounting clip installation is 2.25" (57.2)W x 1.5" (38.1)H
In inches (mm)
PANEL MOUNT UNIT PANEL CUT-OUT
PRINTED CIRCUIT BOARD MOUNT UNIT RECOMMENDED PCB LAYOUT
1
Bulletin No. MDMU-E
Drawing No. LP0391
Released 6/08
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
INSTALLATION
The MDMUs are available in either a panel mount or printed circuit board
mount design. The panel mount units are provided with a mounting clip to
securely hold the unit in the panel cutout.
Panel Mount Installation:
1. Cut panel opening to specified
dimensions. Remove burrs
and clean the panel opening.
2. Install MDMU through the
panel cutout as shown in
Figure 1.
3. Slide mounting clip over rear
of unit until clip is against the
back of panel. The unit has
slots for the locking tabs to
hold it in the panel opening.
Note: Hold the MDMU front
bezel in place when sliding the
mounting clip in to position
PCB Mount Installation:
1. Prepare printed circuit board hole pattern to the specifications.
2. Unit should be hand soldered using good soldering techniques and hand
cleaned if necessary.
SPECIFICATIONS
1. DISPLAY: 6 Digit LCD, 0.35" (8.89 mm) high characters, available in
positive image reflective (black digits, reflective background) or negative
image transmissive (illuminated digits, dark background) with red or
yellow/green backlighting.
2. POWER REQUIREMENTS:
Reflective Versions: 5.0 VDC ±10% 100 µA max.
Backlight Versions: 5.0 VDC ±10% 25 mA max.
3. DECIMAL POINTS:
Timer: Determined by the timing mode selected.
Counter and Tach: 5 programmable positions.
4. ANNUNCIATOR: Flashes at a 2 Hz rate in the Timer mode when the signal
input (CNT or LSC) is activated.
5. CONSTRUCTION: High impact black plastic case (mounting clip included
with panel mount models).
6 RELATIVE HUMIDITY: Less than 85% RH (non condensing)
7. WEIGHT:
Reflective Panel Mount: 0.256 oz (7.26 g)
Reflective PCB Mount: 0.24 oz (6.8 g)
Transmissive Panel Mount: 0.368 oz (10.43 g)
Transmissive PCB Mount: 0.344 (9.75 g)
MAXIMUM RATINGS
CAUTION
This device contains CMOS circuitry which requires special anti-static
handling to the same degree required by standard CMOS integrated
circuits. Units should be stored in the conductive package used to ship the
device. Containers should be opened and units handled only on a
conductive table top by personnel wearing wrist-strap grounding
equipment. These devices have the same protection circuits as standard
CMOS devices to prevent damage to inputs due to nominal over-voltage.
RATING SYMBOL VALUE UNITS REMARKS
DC Supply Voltage VDD 6.5 VDC
Input Voltage, all inputs
except LSC
V
IN
-0.5 to (V
DD +0.5)
VDC
Input Voltage, LSC VLSC -0.5 to (VDD +0.5) VDC
Higher voltages can
be applied with an
external resistor
limiting the LSC
input current to less
than 450
µA.
Operating Temperature T
A
-35 to +85 °C
Storage Temperature TSTG -40 to +85 °C
SYMBOL PARAMETER MIN TYP MAX UNITS NOTES
V
DD
Supply Voltage 4.5 5.0 5.5 VDC Voltages outside these parameters may cause display problems
IDD Supply Current - Transmissive 20 25 mA VDD = 5.0 VDC - 10 KHz Counting Rate.
IDD Supply Current - Reflective 35 100
µA
VDD = 5.0 VDC - 10 KHz Counting Rate.
VIH
Valid High Voltage - CNT, LSC, PGM,
INH (Count mode), LATCH, RST
3.5 VDC
VIH Valid High Voltage - MS1-4, DP1-3 3.0 VDC
VIL
Valid Low Voltage - CNT, LSC, PGM,
INH (Count mode), LATCH, RST
1.0 VDC
VIL Valid Low Voltage - MS1-4, DP1-3 1.0 VDC
I
IN
Input pulldown load current - LSC 0.5 5.0
µA
VIN = 5.0 VDC. For input voltages greater that 5.0 V, current must be
externally limited to less than 450
µΑ.
IIN Input leakage current - all other inputs 0.1 1.0
µA
Fc Count Frequency - CNT 500 1000 KHz
Fc Count Frequency - LSC
0
30
42
30
42
225
Hz
MDMU increments on each pulse
Indeterminate
MDMU increments once for each burst of pulses
TR,L RST, LATCH Pulse width. 10 0.5
µsec
ACCT Timer Accuracy. 0.025
%
Using CNT input. If the LSC input is used, an additional error of up to
30 msec per activation may be accumulated.
A
CCTB
Time Base Accuracy. 0.025
%
ELECTRICAL SPECIFICATIONS - V
DD = 5.0 VDC =
±±
10% @ 25
°°
C unless otherwise specified.
Figure 1
2
MODE SELECT INPUTS - Hardware Selection
The MDMU has 4 Mode Select Inputs, MS1 through MS4. The mode of
operation is selected by setting these inputs to either the V
DD
(1) or V
SS
(0)
states.
Note: The MS Inputs are read only when power is applied to the MDMU. Any
changes to the MS settings after power is applied will have an unpredictable
effect on the operation of the MDMU.
Note: If the PGM features are used, only modes 0, 11, and 12 should be used.
Refer to PROGRAMMING for more details.
DECIMAL POINT INPUTS - Hardware Selection
The Decimal Point Inputs can be
used to select the desired position for a
decimal point in the Counter and Tach
modes. Using these inputs in any of the
Timer modes, or when using the
programming options, may cause
unexpected results and should be tied
low (0 V).
Note: The DP Inputs are read only
when power is applied to the
MDMU. Any change to the DP
inputs after power is applied will
have an unpredictable effect on the operation.
PROGRAMMING
The MDMU’s mode of operation (Counter, Timer, or Tach) can be modified
by selecting the various features of the Program mode. The PROGRAM mode
uses the PGM input to select the digit to be modified and to switch between
Program features. The RST input is used to set the value of the specified digit.
Both inputs are normally held HIGH and are pulsed LOW momentarily to make
the selections desired. Once the PGM mode is entered, all Programming
selections must be entered before returning to the operating mode.
Notes:
1. Only the modes specified for PGM features should be used for the Program
mode (Timer - Mode 0, Tach - Mode 11, and Counter - Mode 12). Using the
Programming features in other hardware selected modes may produce
unexpected results. The PGM input should be tied high (+V) if programming
is not desired.
2. All options entered by programming will be lost if power is removed from the
unit
3. Upon entering the PGM mode for the first time, the Rate Multiplier/Prescaler
is set to 0.0000. Some value between 0.0001 and 1.9999 must be entered in
order for the MDMU to operate properly. Previously stored values are
retained until changed by the user.
Timer Mode Programming Options - Mode 0
Timer Mode Selection
When the MS Inputs are set for 0000, the MDMU will be placed into the
0.001 Sec timer mode. However, if the PGM input is pulsed, the MDMU will
enter the PROGRAM mode, which will allow the unit to be set to any of the
Timer ranges. These ranges will function the same as the ranges selected
through using the MS Inputs (Hardware selection). When the PGM input is
pulsed LOW, the MDMU display will change to 0. The 0 indicates the Timer
Range or Mode number (0.001 Sec). If the RST Input is pulsed, the display
will increment to 1 (0.01 Sec). Pulsing the RST Input again will continue to
increment the display (and Timer range) until 9 is reached. At this time, the
display will return to 0. Pulsing the PGM Input will return the previous
display from the timer mode with the new timer range and decimal point
position enabled. Any new time accumulated will be at the new rate.
Note: To avoid incorrect display information, it is recommended that the
MDMU be reset after making programming changes.
Tach Mode Programming Options - Mode 11
When the MS Inputs are set for 1011, the MDMU will be placed into the 1
Sec T.B. Tach mode. However, if the PGM input is pulsed, the MDMU will
enter the PROGRAM mode, which will allow the rate multiplier, decimal point,
and time base to be changed.
Rate Multiplier Selection
To enter the PROGRAM mode, the PGM Input should be pulsed LOW. The
MDMU display will change to 0.0000 with the least significant digit (LSD)
flashing at a 2 Hz rate. Pulsing the RST Input will cause the LSD to
increment once for each pulse. After the digit has been incremented to 9, it
will change back to a 0 on the next pulse of the RST Input. Pulsing the PGM
input will lock in the present value of the LSD and the next digit will begin
to flash. All subsequent digits will work the same until the most significant
digit (MSD). This digit can only be set to a 0 or a 1.
Decimal Point Selection
Pulsing the PGM Input at this time will cause the unit to switch to the
Decimal Point Selection mode. In this mode, the display will read 0.0000.
Pulsing the RST Input will move the decimal point to the next position. The
display will change from 0.00000 to 000000, then to 0, etc. Since the MDMU
uses an integrated circuit which has 8 digit capability and the MDMU display
is only 6 digits, the display will not appear to change after 000000 is
displayed until the RST Input is pulsed twice. At this time the display will
update to 0.
Time Base Selection
Pulsing the PGM Input will cause the unit to switch to the Time Base
Selection mode. The display will indicate a 6 which selects a 6 second time
base period. Pulsing the RST Input will allow the time base to be changed
from 0 to 7 seconds (in whole second increments). A 0 time base will inhibit
the MDMU from displaying the rate. Pulsing the PGM Input will return the
unit to the Tach mode using the new time base selected and the new decimal
point position. Any new rate pulses will be affected by the rate multiplier
value.
Counter Mode Programming Options - Mode 12
When the MS Inputs are set for 1100, the MDMU will be placed into the
Counter mode. However, if the PGM input is pulsed, the MDMU will enter the
PROGRAM mode, which will allow the prescaler, and decimal point settings to
be changed.
Prescaler Selection
To enter the PROGRAM mode, the PGM input should be pulsed LOW. The
MDMU display will change to 0.0000 with the least significant digit (LSD)
flashing at a 2 Hz rate. Pulsing the RST input will cause the LSD to
increment once for each pulse. After the digit has been incremented to 9, it
will change back to a 0 on the next pulse of the RST input. Pulsing the PGM
input will lock in the present value of the LSD and the next digit will begin
to flash. All subsequent digits will work the same until the most significant
digit (MSD). This digit can only be set to a 0 or a 1.
Decimal Point Selection
Pulsing the PGM input at this time will cause the unit to switch to the
Decimal Point Select mode. In this mode, the display will read 0.0000.
Pulsing the RST input will move the decimal point to the next position. The
display will change from 0.00000 to 000000, then to 0, etc. Since the MDMU
uses an integrated circuit which has 8 digit capability and the MDMU display
is only 6 digits, the display will not appear to change after 000000 is
displayed until the RST input is pulsed twice. At that time, the display will
update to 0. Pulsing the PGM input will return the previous display from the
counter mode with the new decimal point position enabled. Any new count
pulses will be affected by the rate multiplier value.
Note: The incrementing edge of the count signal will change when
PROGRAM mode options are used. To avoid incorrect display
information, it is recommended that the MDMU be reset after making
programming changes.
INPUT CONDITIONS FOR DETERMINING COUNT EDGE
Accessing PROGRAM mode will complement the incrementing edge of the
input signal.
DP3
DECIMAL POINT INPUTS
DISPLAY
DP2 DP1
0
0 0 0 0
0 1
0 1
0 0.0
0.00
0 1 1 0.000
1 0 0 0.0000
1 0
1
1 0.00000
1
0
000000
.000000
1 1
1
RUNVDDVDD
RUNVSSVDD
STOPVDDVSS
RUNVSSVSS
NORMAL AND W/PGM OPTIONS
ACTIONCNTLSC
TIMER
INCREMENTING EDGE
Rising
Falling
Rising
Falling
NORMAL
OTHER
INPUT TIED
TO
VDD
VSS
VDD
VSS
INPUT
SIGNAL
USED
Falling
Rising
CNT
Falling
Rising
LSC
W/PGM
COUNTER AND TACH
3
0.001 Sec Timer and All PGM Timers
1 Sec T.B. Tach and PGM Tach
Counter and PGM Counter
1
0
1
0
0
1
1
1
11
12
Not Used010110
Factory Use Only10019
1 Hr Timer00018
0.1 Hr Timer11107
0.01 Hr Timer
0
1
1
06
1 Min Timer1
0
0
1
0
5
1 Sec Timer
0.1 Min Timer
1
0 0
1
0
0
1
2
0
0
3
4
0.01 Sec Timer
0.1 Sec Timer
10
1
00
0
1
00000
MODE OF OPERATION
MS1MS2MS3MS4Mode
MODE SELECT INPUTS
TYPICAL APPLICATIONS
WIRING CONNECTIONS
The electrical connections are
made via terminal pins located on
the back of the unit. The terminal
pins are on 0.100" center lines and
can be mated with the RLC Model
HWK7 cable assembly or many
standard 0.100" center line
connectors. When wiring the unit,
refer to Figure 2 to identify the
wire position with the proper
function.
There are certain considerations
that should be observed when
running the signal wires. A length
of wire can act like an antenna,
and the closer it is to a source of
electrical noise, the more it
becomes susceptible to that noise.
These are a few rules that should be followed when running these wires.
1. Never run signal wires in the same conduit or raceway with A.C. power lines,
conductors feeding motors, solenoids, SCR controls, heaters, etc.
2. Signal wires within enclosures should be routed as far away as possible from
contactors, control relays, transformers, and other noisy components.
3. When shielded wire is used, connect the shield to the common of the MDMU
unit, and leave the other end of the shield disconnected and insulated from
machine ground.
4. Connect common of the MDMU to machine ground at one point only.
PIN DESCRIPTIONS
(All unused inputs must be tied to high or low, whichever is appropriate)
VDD : +5.0 VDC ± 10% supply terminal. A clean power supply is required
for the proper operation of the MDMU. A slow voltage rise at power up may
cause erratic operation.
DP1, DP2, DP3 : The Decimal Point Select Inputs are used to select the
desired decimal point position. These inputs are intended to be used in the
non-programmed Counter and Tach modes only. To avoid conflicts with the
decimal points set with the programming options, or by the Timer ranges,
these inputs should be left tied to V
SS.
MS1, MS2, MS3, MS4 : The Mode Select Inputs are used to select the mode
of operation: Counter, Timer and Tach. The Timer range can also be selected
using the MS inputs. If programming is required, modes 0 (Timer), 11
(Tach), or 12 (Counter) should be used.
RST : Schmidt trigger input. In the Counter and Timer modes, a LOW level
on the RST input will reset the display and all internal divider registers to 0.
When the RST input is in the HIGH state, the counter/timer will operate
normally. The RST input should be tied high and not used in the Tach mode.
The RST input is also used in the PROGRAM modes to increment the
selected digit.
LATCH : Schmidt trigger input. In the Counter and Tach modes, a HIGH level
on the LATCH input will freeze the display while allowing the counter or
timer to continue to accept the signal input. When the LATCH input is in the
LOW state, the counter/timer will operate normally. The LATCH input
should be tied low and not used in the Tach mode.
INHIBIT : Schmidt trigger input. In the Counter and Tach modes, a LOW
level on the INHIBIT input will prevent further signal inputs from
incrementing the counter or tach. When the INHIBIT input is in the HIGH
state, the counter/tach will operate normally.
For Timer modes, a LOW level on the INHIBIT input will enable leading
zero blanking while a HIGH level on the INHIBIT input will disable the
LZB.
PGM : Schmidt trigger input. A momentary LOW pulse on the PGM will put
the MDMU into the PROGRAM mode. Further pulsing of the PGM input
will step through the various digit positions or to the next programming
option. A final pulse of the PGM input will return the MDMU to the normal
operating mode.
LSC : The Low Speed Signal Input (working in conjunction with the CNT
Input) is one of the two signal sources for all of the counting, timing, and tach
functions of the MDMU. The LSC input is able to accept low frequency
signal voltages in excess of V
DD (Input current must be limited to less than
450 µA to prevent damage to the unit).
Ιn the COUNT mode, the LSC input is internally filtered so that signals
below 30 Hz are registered as individual count pulses. Signals from 42 Hz to
225 Hz are treated as a single burst (each burst of pulses is treated as a single
count).
In the TIMER modes, the LSC input can be used to actuate the timer.
Notes:
1. Due to the internal digital filtering to the LSC input, up to 30 msec of error
may be added per activation of the LSC input.
2. Although the LSC and CNT inputs will work at the same time, it is not
advised since there is no Anti-coincidence provided.
3. Although the LSC input can be used in the TACH mode, it may not be
practical since the usable frequency is limited to 30 Hz.
CNT : Schmidt trigger input. The Count input (working in conjunction with
the LSC input) is one of the two signal sources for all of the counting, timing,
and tach functions of the MDMU. The CNT input is able to accept high
frequency signals with an amplitude of 5.0 VDC.
Note: Although the LSC and the CNT inputs will work at the same time, it is
not advised since Anti-coincidence is not provided.
VSS : GND or Common supply terminal.
Figure 2
Note: All inputs will be at line potential
1 MINUTE TIMER - With Leading Zero
Blanking enabled. Time starts with the
switch closed. Time stops and holds the
display with the switch open.
COUNTER - Displays the number of activations of
solenoid. Counts increments on the rising edge of LSC.
Display decimal point is set to 0.00. D1 prevents LSC
input from negative swing of input signal. R1 value is
selected to prevent input current from exceeding 450
µA. The solenoid is activated by an external AC power
source.
TACH - With user programmed rate multiplier,
decimal point position and time base. Falling
Edge triggered.
4
PROGRAMMING EXAMPLES
SCALING A COUNTER
Example: An encoder generates 600 pulses per foot. The Desired Display is
tenths of inches. The Prescaler is determined using the formula below.
Prescaler =
Where:
Desired Display = The number of Desired Display units (revolutions, feet,
10ths of feet, meters, etc.).
Number of Pulses = The number of pulses required to achieve the Desired
Display
Decimal Point Value = The desired decimal point
placement on the display.
Example: Display tenths of inches when using
Prescaler =
= 10/50 = 0.2
SCALING FOR RATE
For a Time Base (TB) of 1 second, the Rate Multiplier (RM) equals a Desired
Display (DD) divided by the Pulses per Second (PPS) at that DD value. For
other time bases, the PPS must be multiplied by the desired TB.
RM =
When display units are a function of RPM then,
RM =
Example 1: Show inches per minute with an encoder generating 600 pulses per
foot, with a 1 foot circumference wheel.
Step 1: Since the rate is in minutes, we choose 6 inches as the desired display.
Step 2: Use the general formula.
RM =
RM = 1.2
Example 2: A belt moves 1 foot for 4 revolutions of a shaft. The shaft encoder
generates 60 PPR. Show the rate in feet per minute with one decimal place.
RM =
RM = 2.5
This value is above the available range of 0.0001 to 1.9999. Increasing the
Time Base to 2 sec. will allow us to decrease the rate multiplier needed to
1.25 which is within the available range. The same result could be achieved by
increasing the pulses per revolution generated.
RM =
RM = 1.25
1 foot/min x 10 x 60

4 RPM x 60 PPR x 2 sec
1 foot/min x 10 x 60

4 RPM x 60 PPR x 1 sec
6 in/min x 1 x 60
−
0.5 RPM x 600 pulses/foot x 1 sec.
Desired Display x Decimal Point Value x 60

RPM (@DD) x PPR x TB
Desired Display value

PPS @ DD value x Time Base
1 (inch) x 10 (Decimal Point Value)

600 pulses/foot x 1 foot/ 12 inches
Desired Display Units x Decimal Point Value

Number of Pulses
ACCESSORY: MDM CABLE ASSEMBLY
MODEL NO DESCRIPTION PART NUMBER
Panel Mount W/Reflective Display MDMU0000
Panel Mount W/Yel-Grn Backlighting MDMU0010
Panel Mount W/Red Backlighting MDMU0020
PC Board Mount W/Reflective Display MDMU0100
PC Board Mount W/Yel-Grn Backlighting MDMU0110
MDMU
PC Board Mount W/Red Backlighting MDMU0120
HWK7 MDM Cable Assembly HWK70000
ORDERING INFORMATION
Decimal
Point Value
Multiply By
0 1
0.0 10
0.00 100
0.000 1000
0.0000 10000
0.00000 100000
5
6
This page intentionally left blank.
7
This page intentionally left blank.
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship
for a period limited to two years from the date of shipment, provided the products have been stored,
handled, installed, and used under proper conditions. The Company’s liability under this limited
warranty shall extend only to the repair or replacement of a defective product, at The Company’s
option. The Company disclaims all liability for any affirmation, promise or representation with
respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products
containing components manufactured by RLC and based upon personal injuries, deaths, property
damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those
expressly contained herein. The Customer acknowledges the disclaimers and limitations contained
herein and relies on no other warranties or affirmations.
Red Lion Controls
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls AP
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683
Red Lion Controls BV
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

red lion MDMU Pre User manual

Category
Electrical timers
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI