BE-VXP STANDARD MODULES
FC-SCB: Slave Command Board
• System status LEDs. • System micro-controller.
• Audio input. • Auxiliary power output.
• Tone generators. • Programming dip switches.
• Provides mounting location for all standard and optional
modules.
FC-VTM: Voice Transponder Module
• Houses third FC-AAM25 amplifier when used as backup to
primary and secondary amps.
• Provides five SLC/FlashScan points (4 control, 1 monitor).
• Provides dual, 3 Amp NACs,
OR...
dual firefighter-telephone
circuits (switch point only, no jacks),
OR...
a combination of
one NAC and one FFT circuit.
• Includes slide switches to independently disable SLC points.
• Provides “10’s” code switch and “1’s” slide switch to set
address of first SLC point.
• Mounts directly to FC-SCB.
FC-AAM25: Audio Amplifier Module
• 25 Watt, 25 VRMS audio amplifier module.
• Provides single Class A or Class B speaker circuit.
• Utilizes plug-in style terminal blocks for ease of service and
maintenance.
• Fully supervised and power-limited.
• Diagnostic LEDs include: yellow trouble LED (cable fault,
70 VRMS fault, amp fault) and green, amp functional LED.
• Also available:
1)
as an option for system expansion to 50
watts (providing dual 25-watt speaker circuits); or
2)
as a
backup to the primary 25-watt amplifier, where one-to-one
backup is required; or
3)
as a backup to either FC-AAM25
in systems configured for 50 watts, in the event that either
amp fails.
• Optional second FC-AAM25 mounts to FC-SCB while third
optional amp mounts to FC-VTM.
FC-PSM: Power Supply Module
• Power supply/battery charger module.
• Ground fault detection with diagnostic LED (yellow).
• Brownout detection with battery transfer.
• Battery trouble detect with diagnostic LED (yellow).
• Battery saver operation.
• Independent AC loss relay provides AC loss delay per UL,
for independent monitoring by DACT (2 Amps @ 24 VDC).
• AC power on LED (green).
• 18 AH battery charging capacity — up to 25 AH may be
utilized in CAB-A3 enclosure.
• Large, teeter-plate terminal blocks easily accept up to 12
AWG (3.25 mm²) for power terminations.
• Mounts adjacent to FC-SCB.
OPTIONAL MODULES
FC-XRM70: Optional Transformer Module
• Converts 25 VRMS audio outputs to 70.7 VRMS for retrofit
applications.
• Plugs directly on FC-AAM25 module(s), allowing
independent conversion to 70.7 VRMS.
FC-LPS: Optional Local Playback Speaker
• Provides local digital message playback for user review of
field-recorded custom messages.
FC-MGM: Optional Message Generator Module
• Optional Digital Message Generator for VXP with standard,
factory-prerecorded, emergency evacuation message.
• Message generator includes 60-second capacity, with
primary and secondary message capability (30 seconds
each).
• Custom messages are field recordable through PCB-
mounted microphone or integral RCA-type jack.
• Digital message may be field-selected for 1, 2, 4, 8 or infinite
repeat.
STANDARDS AND CODES
The VXP-25/50 will comply with the following standards:
• NFPA 72-1996 National Fire Alarm Code
• NFPA 101-1994 Life Safety Code
•UL 864 Standard for Control Units for Fire Alarm Systems
SPECIFICATIONS
Primary (AC) Power:
• 1.0 Amp max. @ 120 VAC, 60 Hz.
Secondary Power (Battery) Charging Circuit:
• Supports lead acid batteries only.
• Float charge voltage: 27.6V.
• Maximum charge current: 800 mA.
• Maximum battery capacity: 18 AH.
Trouble Contact Rating:
• 2.0 Amps at 30 VDC (resistive), 0.06 Amps @125 VAC
resistive.
Auxiliary Power Output:
• Specific application power: 35 mA maximum.
CABINET SPECIFICATIONS
Door: 20.13" (51.13 cm) high x 24.13" (61.29 cm) wide x
1.25" (3.175 cm) deep. Backbox: 20.0" (50.80 cm) high x
24.0" (60.96 cm) wide x 5.22" (13.259 cm) deep.
CONTROLS AND INDICATORS
LED INDICATORS:
• Power On (green).
• ALARM (red).
• System Trouble (yellow).
• Tone Generator Trouble (yellow).
• Message Generator Trouble (yellow) on FC-MGM option.
• Record (green) on FC-MGM option.
• Playback (green) on FC-MGM option.
SWITCH CONTROLS:
• Record (on FC-MGM option).
• Playback (on FC-MGM option).
ORDERING INFORMATION
BE-VXP: Basic Equipment Kit, includes: FC-SCB, FC-VTM,
FC-AAM25, FC-PSM, FC-CHS (chassis), and installation in-
structions.
FC-DR-A3: VXP Door only, “A” style, dead-front, one (1) tier.
SBB-A3: Backbox only, “A” style, one (1) tier.
FC-AAM25: Optional 25 Watt, 25 VRMS Audio Amplifier Mod-
ule with single Class A or Class B speaker circuit (may be
used as a backup).
FC-PSM: Replacement 120 VAC, 60 Hz Power Supply/Bat-
tery Charger Module (included with BE-VXP).
FC-XRM70: Optional 70.7 VRMS Converter Module (one re-
quired per amplifier).
Consult factory for availability.
FC-MGM: Optional Digital Message Generator.
Consult fac-
tory for availability.
FC-VTM: Replacement five-SLC-point Transponder Module.
FC-LPS: Optional Local Playback Speaker.
PS-12120: Battery, 12 volt, 12.0 AH, (two required).
PS-12180: Battery, 12 volt, 18.0 AH, (two required).
PS-12600: Battery, 12 volt, 60.0 AH, (two required).
BB-55: Battery Box, required to mount PS-12250 or PS-12600
batteries (when CHG-120 is installed in CAB-A3).
CHG-120: 25 AH to 120 AH battery charger (required for 60-
hour battery-backed systems).
APS-6R: Auxiliary Power Supply, one requIred to power two
NAC outputs on FC-VTM.