Potter SB24 Bell Strobe Series Bell/Select-A-Strobe Combination Owner's manual

Category
Fire protection
Type
Owner's manual
S
B24 BELL
STROBE SERIES
BELL/SELECT-A-STROBE
CO
MBI
N
ATI
ON
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.amseco-kai.com
MKT. #8850042 - REV A
5/06 PAGE 1 OF 2
PRINTED IN USA
A Brand
Model Number Housing Color Bell Gong
Size Rated Voltage
(VDC) Strobe Output
(cd) Sync Module UL Rating
(dB/10ft.) ULC Rating
(dB/10ft.)
SB624-153075 Red 6” 24 15 or 30 SMD10-3A 83 85
SB824-153075 Red 8” 24 15 or 30 SMD10-3A 83 85
SB1024-153075 Red 10” 24 15 or 30 SMD10-3A 84 85
Engineering Speci cations
The visual alarm indicating appliance shall be Amseco model SB24 Bell Strobe Series or equivalent device. The strobe shall
be listed under UL 1971 standard for signaling devices for the hearing impaired and shall be approved for re protective
service. The candela output shall be eld selectable, having a dual setting of 15/75 cd or 30/120 cd output. The signaling
strobe shall operate on 24V DC from a non-coded regulated DC supply or full-wave recti ed, un ltered supply. It is designed
to produce a signal ash of one ash per second with continuously applied minimum voltage. The strobe shall be capable of
wall or ceiling mounting to an electrical back box. Visual signaling devices shall be mounted to 80” above the highest oor
point or 6” below ceiling, whichever is lowest. They are to be installed as per plans and speci cations.
Ordering Information
• Strobe with two eld selectable settings 15cd or 30 cd
• Designed to meet or exceed NFPA/ANSI standards
and ADA accessibility giodelines
Polarized models with wide listed voltage ranges using
ltered DC or un ltered FWR input voltage
• Wire terminals for in/out wiring supervision
All models mount to 4” square back box
Available in 24VDC polarized models
• Strobe synchronization requires an Amseco
SMD10-3A (daisy chain) sync module
• Stickers show selected candela rating
Amseco’s Bell/Select-A-Strobe Series is designed to be ADA compliant and meet UL standard 1971 requirements for
emergency signaling devices for the hearing impaired. The strobe features a unique candela intensity tamper-proof eld
selector switch for switching the candela output from 15cd to 30cd. The selector switch is accessible without the need to
disassembled the unit. The Bell/Strobe combination is polarized for connecting to supervised re alarm circuits. The bell is
motor driven and draws as little as 12.1mA at 24V DC and is available in 6”, 8”, and 10”.
The Bell/Strobe combination is polarized for connecting to supervised re alarm circuits. The series is only available with a
red housing, 15cd or 30cd, in 24V DC. The strobe can be synchronized by using the SMD10-3A sync module to comply with
NFPA recommendations concerning photosensitive epilepsy when installing two or more visual appliances within the eld of
view. The strobe signals are listed for indoor use, ceiling and wall mount, under UL 1971 standard.
The SB24 Bell Strobe Series is recommended for use in areas such as; meeting rooms, schools, corridors, apartments, of ce
buildings, restaurants, hotels, and any other application where effective audible visual warning is required by federal, state, or
local authority having jurisdiction.
S
T
A
T
E
O
F
C
A
L
I
F
O
R
N
I
A
S
T
A
T
E
F
I
R
E
M
A
R
S
H
A
L
L
L
I
S
T
I
N
G
S
E
R
V
I
C
E
firealarmresources.com
MKT. #8850042 - REV A
5/06 PAGE 2 OF 2
PRINTED IN USA
A Brand
Wiring Diagram
Dimensions: inches (mm)
S
B24 BELL
STROBE SERIES
BELL/SELECT-A-STROBE
CO
MBI
N
ATI
ON
3 3/8
Square
(85.7)
3 3/8
Square
(85.7)
5 1/2
(140)
3 31/32
Square
(101)
3 9/32
(83)
11 (280)
F
I
R
E
5/16
(8)
2 9/32
(5 8 )
3 1/32
(7 7 )
10
(250)
8
(200)
6
(150)
6 3/ 8
(60.5)
+
+
_
_
Control
Panel
To Next De vi ce o r
End-Of Line-Resistor
Mounting
*The Sync module is rated for 3.0 amperes at 24 VDC.
+
++
__
++
S
Control Panel
SMD10-3A
Sync Module
TO NEXT DEVICE
or END-OF-L INE
-RESISTOR
TO NEXT DEVICE
or END-OF-L INE
-RESISTOR
S
+_
__
_
4 x 4 x 1-1/2
ba ckbo x
F
I
R
E
15 30
Slit
15cd 30 cd
UP
DOWN
Use a jewelers screwdriver
to select the light output.
firealarmresources.com
  • Page 1 1
  • Page 2 2

Potter SB24 Bell Strobe Series Bell/Select-A-Strobe Combination Owner's manual

Category
Fire protection
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI