Generac Power Systems 00847-1 Operating & Installation Manual

Category
Power generators
Type
Operating & Installation Manual
POWER SYSTEMS, INC.
®
APS 6.0 24V DC AIR-COOLED
AUXILIARY POWER SYSTEM
OPERATING & INSTALLATION MANUAL
Model: 00847-1
This Manual Should Remain With The Unit.
Generac®Power Systems, Inc.
INTRODUCTION
READ THIS MANUAL THOROUGHLY
If you do not understand any portion of this manual,
contact Generac or the nearest Generac Authorized
Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and
decals affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert you to
special instruction about a particular operation that
may be hazardous if performed incorrectly or care-
lessly. Observe them carefully. Their definitions are as
follows:
After this heading, read instructions that, if not
strictly complied with, will result in personal
injury, death or property damage.
After this heading, read instructions that, if not
strictly complied with, may result in personal injury
or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compli-
ance with the special instructions while performing
the service are essential to preventing accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates is as follows:
This symbol points out important safety informa-
tion that, if not followed, could endanger personal
safety and/or property.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use
of the equipment. Generac strongly recommends that
the operator read this Owner's Manual and thor-
oughly understand all instructions before using this
equipment. Generac also strongly recommends
instructing other users to properly start and operate
the unit. This prepares them if they need to operate
the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information,
including warranty, electrical diagrams, exploded
views and lists of repair parts, for the model 00847-1.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety
checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
equipment checked periodically by a Generac
Authorized Dealer. Normal maintenance service and
replacement of maintenance parts are the responsibili-
ty of the owner/operator and, as such, are not consid-
ered defects in materials or workmanship within the
terms of the warranty. Individual operating habits and
usage contribute to the need for maintenance service.
Proper maintenance and care of the generator ensure a
minimum number of problems and keep operating
expenses at a minimum. See a Generac Authorized
Dealer for service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs,
simply contact a Generac Authorized Dealer for
assistance. Service technicians are factory-trained
and are capable of handling all service needs.
When contacting a Generac Authorized Dealer or the
factory about parts and service, always supply the
complete model number and serial number of the
unit as given on its data decal, which is located on the
generator.
Model No. ____________ Serial No. ______________
!
DANGER
Table of Contents
Generac APS 6.0 DC Auxiliary Power System
Generac®Power Systems, Inc. 1
Introduction ......................Inside Front Cover
Read This Manual Thoroughly ......................IFC
Contents ........................................................IFC
Operation and Maintenance............................IFC
How to Obtain Service ....................................IFC
Safety Rules ......................................................2
Section 1 – General Information..................4
1.1 Generator Identification ..............................4
1.2 Operation and Maintenance ........................5
1.3 Safety... ........................................................5
1.4 Generator Applicability ................................5
1.5 Specifications ..............................................5
1.6 Fuel System..................................................5
1.6.1 Reconfiguring the Fuel System ........6
1.6.2 Recommended Fuel ..........................6
Section 2 – Installation ..................................6
2.1 Installation ..................................................6
2.1.1 Unit Location....................................6
Section 3 – Operation ....................................7
3.1 Operation ....................................................7
3.2 Electrical Connections..................................7
3.2.1 Starting Battery ................................7
3.2.2 DC Output Power ............................8
3.2.3 Alarms and Utility Input ..................8
3.3 Electrical Panel ............................................9
3.4 Electrical Operation ....................................9
3.4.1 Voltage Regulator..............................9
3.4.2 Fine and Course Voltage Adjust......10
3.4.3 Under Frequency Adjust ................10
3.4.4 Current Limit Adjust......................10
3.4.5 Field Set Up Procedure ..................10
3.4.6 Engine Control, Alarm and
Shutdown PCB ..............................11
3.4.7 Manual Operation ..........................11
3.4.8 Automatic Operation ......................11
3.4.9 Off Position ....................................11
3.4.10 Remote Start ..................................11
3.4.11 Remote Stop ..................................11
3.4.12 Alarms............................................11
3.4.13 Start Battery Voltage Alarm ............12
3.4.14 Switch Not In Auto Alarm ..............12
3.4.15 General Failure Alarm ....................12
3.4.16 Engine Run Alarm..........................12
3.4.17 Protective Shutdown Circuits ........12
3.4.18 Utility Source Voltage ....................12
3.4.19 Battery Charger ..............................12
3.4.20 Exercise Timer ..............................12
3.5 Setting the Exerciser ....................................13
3.5.1 Display ............................................13
3.5.2 Exercise Times ................................13
3.6 Push Buttons ............................................13
3.6.1 Up Arrow ....................................13
3.6.2 Down Arrow ................................13
3.6.3 Time (Time/Alarm Toggle) ..............13
3.6.4 On/Off (Alarm Select Toggle) ..........14
3.6.5 Day ................................................14
3.7 Programming Examples ............................14
3.7.1 Example 1 — Change Time
From Sunday 9:00 AM to
Wednesday 2:00 PM ......................14
3.7.2 Example 2 — Set Exerciser
On for 14 Minutes Mon.-Fri.
at 10:00 AM ..................................14
Section 4 – Maintenance ............................14
4.1 General Maintenance..................................14
4.1.1 25 Hour Break In Period................14
4.1.2 25 Hour Check Up ........................14
4.1.3 Attention Required After
Submersion....................................14
4.1.4 Effects of Moisture and Dirt ..........15
4.1.5 Engine Oil Requirements................15
4.1.6 Battery............................................15
4.1.7 Every Six Months ..........................15
4.2 Engine Protective Devices ..........................16
4.2.1 Automatic Low Oil Pressure
Shutdown ......................................16
4.2.2 High Temperature Switch ................16
4.2.3 Checking Engine Oil Level..............16
4.3 Change Engine Oil......................................16
4.4 Change Oil Filter ........................................17
4.5 Service Engine Air Cleaner ........................17
4.6 Complete Engine Tune Up..........................17
4.7 Inspect Cooling System of Generator ........17
Section 5 – Electrical Data ..........................18
Section 6 – Exploded Views and
Parts Lists ..................................20
Section 7 – Major Features and
Dimensions................................34
Section 8 – Notes ..........................................35
Section 9 – Warranty ....................Back Cover
2 Generac®Power Systems, Inc.
Study these SAFETY RULES carefully before installing,
operating or servicing this equipment. Become familiar
with this Owner’s Manual and with the unit. The gen-
erator can operate safely, efficiently and reliably only if
it is properly installed, operated and maintained. Many
accidents are caused by failing to follow simple and fun-
damental rules or precautions.
Generac cannot possibly anticipate every possible
circumstance that might involve a hazard. The warn-
ings in this manual, and on tags and decals
affixed to the unit are, therefore, not all-inclusive. If you
use a procedure, work method or operating technique
Generac does not specifically recommend, you must
satisfy yourself that it is safe for you and others. You
also must make sure the procedure, work method or
operating technique that is chosen does not render the
generator unsafe.
Despite the safe design of this generator,
operating this equipment imprudently, neglecting its
maintenance or being careless can cause possible
injury or death. Permit only responsible and capable
persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these
machines. Ensure all steps are taken to render the
machine safe before attempting to work on the
generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running gen-
erators.
GENERAL HAZARDS
For safety reasons, Generac recommends that the
installation, initial start-up and maintenance of this
equipment is carried out by a Generac Authorized
Dealer.
Installation, operation, servicing and repair of this
(and related) equipment must always comply with
applicable codes, standards, laws and regulations.
Adhere strictly to local, state and national electrical
and building codes. Comply with regulations the
Occupational Safety and Health Administration
(OSHA) has established. Also, ensure that the gener-
ator is installed, operated and serviced in accordance
with the manufacturer’s instructions and recommen-
dations. Following installation, do not do anything
that might render the unit unsafe or in noncompli-
ance with the aforementioned codes, standards, laws
and regulations.
The engine exhaust fumes contain carbon monoxide,
which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. For that reason, ade-
quate ventilation must be provided. Exhaust gases
must be piped safely away from any building or
enclosure that houses the generator to an area where
people, animals, etc., will not be harmed. This
exhaust system must be installed properly, in strict
compliance with applicable codes and standards.
Keep hands, feet, clothing, etc., away from drive belts,
fans, and other moving or hot parts. Never remove
any drive belt or fan guard while the unit is operating.
Adequate, unobstructed flow of cooling and ventilating
air is critical in any room or building housing the gen-
erator to prevent buildup of explosive gases and to
ensure correct generator operation. Do not alter the
installation or permit even partial blockage of ventila-
tion provisions, as this can seriously affect safe oper-
ation of the generator.
Keep the area around the generator clean and unclut-
tered. Remove any materials that could become haz-
ardous.
When working on this equipment, remain alert at all
times. Never work on the equipment when you are
physically or mentally fatigued.
Inspect the generator regularly, and promptly repair
or replace all worn, damaged or defective parts using
only factory-approved parts.
!
!
!
!
DANGER
Important Safety Instructions
Generac APS 6.0 DC Auxiliary Power System
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe
operation be copied and posted in potential hazard areas. Safety should be stressed to all
operators and potential operators of this equipment.
!
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
!!
!
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be
followed during installation and maintenance of the generator and batteries.
!
!
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
!!
Generac®Power Systems, Inc. 3
Before performing any maintenance on the generator,
disconnect its battery cables to prevent accidental
start-up. Disconnect the cable from the battery post
indicated by a NEGATIVE, NEG or (–) first.
Reconnect that cable last.
Never use the generator or any of its parts as a step.
Stepping on the unit can stress and break parts, and
may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.
ELECTRICAL HAZARDS
All generators covered by this manual produce dan-
gerous electrical voltages and can cause fatal electri-
cal shock. Utility power delivers extremely high and
dangerous voltages to the transfer switch as does the
standby generator when it is in operation. Avoid con-
tact with bare wires, terminals, connections, etc.,
while the unit is running. Ensure all appropriate cov-
ers, guards and barriers are in place before operating
the generator. If work must be done around an oper-
ating unit, stand on an insulated, dry surface to
reduce shock hazard.
Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
If people must stand on metal or concrete while
installing, operating, servicing, adjusting or repairing
this equipment, place insulative mats over a dry
wooden platform. Work on the equipment only while
standing on such insulative mats.
The National Electrical Code (NEC) requires the
frame and external electrically conductive parts of the
generator to be connected to an approved earth
ground and/or grounding rods. This grounding will
help prevent dangerous electrical shock that might be
caused by a ground fault condition in the generator
set or by static electricity. Never disconnect the
ground wire.
Wire gauge sizes of electrical wiring, cables and cord
sets must be adequate to handle the maximum elec-
trical current (ampacity) to which they will be sub-
jected to.
Before installing or servicing this (and related) equip-
ment, make sure that all power voltage supplies are
positively turned off at their source. Failure to do so
will result in hazardous and possibly fatal electrical
shock.
Connecting this unit to an electrical system normally
supplied by an electric utility shall be by means of a
transfer switch so as to isolate the generator electric
system from the utility electric system while in oper-
ation. Failure to isolate the two electric system power
sources from each other by such means will result in
damage to the generator and may also result in injury
or death to utility power workers due to backfeed of
electrical energy.
• Generators installed with an automatically transfer
switch will crank and start automatically when nor-
mal (utility) source voltage is removed or is below an
acceptable preset level. To prevent such automatic
start-up and possible injury to personnel, disable the
generator’s automatic start circuit (battery cables,
etc.) before working on or around the unit. Then,
place a “Do Not Operate” tag on the generator control
panel and on the transfer switch.
In case of accident caused by electric shock, immedi-
ately shut down the source of electrical power. If this
is not possible, attempt to free the victim from the
live conductor. AVOID DIRECT CONTACT WITH THE
VICTIM. Use a nonconducting implement, such as a
rope or board, to free the victim from the live con-
ductor. If the victim is unconscious, apply first aid
and get immediate medical help.
Never wear jewelry when working on this equipment.
Jewelry can conduct electricity resulting in electric
shock, or may get caught in moving components
causing injury.
FIRE HAZARDS
Keep a fire extinguisher near the generator at all
times. DO NOT use any carbon tetra-chloride type
extinguisher. Its fumes are toxic, and the liquid can
deteriorate wiring insulation. Keep the extinguisher
properly charged and be familiar with its use. If there
are any questions pertaining to fire extinguishers,
consult the local fire department.
EXPLOSION HAZARDS
Properly ventilate any room or building housing the
generator to prevent build-up of explosive gas.
Do not smoke around the generator. Wipe up any fuel
or oil spills immediately. Ensure that no combustible
materials are left in the generator compartment, or
on or near the generator, as FIRE or EXPLOSION
may result. Keep the area surrounding the generator
clean and free from debris.
Generac generator sets may operate using one of sev-
eral types of fuels. All fuel types are potentially FLAM-
MABLE and/or EXPLOSIVE and should be handled
with care. Comply with all laws regulating the stor-
age and handling of fuels. Inspect the unit’s fuel sys-
tem frequently and correct any leaks immediately.
Fuel supply lines must be properly installed, purged
and leak tested according to applicable fuel-gas codes
before placing this equipment into service.
Diesel fuels are highly FLAMMABLE. Gaseous fluids
such as natural gas and liquid propane (LP) gas are
extremely EXPLOSIVE. Natural gas is lighter than air,
and LP gas is heavier than air; install leak detectors
accordingly.
Important Safety Instructions
Generac APS 6.0 DC Auxiliary Power System
4 Generac®Power Systems, Inc.
1.1 GENERATOR IDENTIFICATION
Section 1 — General Information
Generac APS 6.0 DC Auxiliary Power System
Engine Air Intake
Oil Fill
Oil Check/Dipstick
Oil Drain Hose Oil Filter
Air Filter
(Located Behind Panel)
Air Intake
Terminal Block
Control Board
Air Intake
Voltage Regulator
Control Panel
Fuel Hose
Programmable Exerciser
Exhaust Air Out
DC Output Terminals
Air Intake
Rectifier and
Filter Air Outlet
Muffler
Lifting Point
(use bolt on lifting plates)
Lifting Point
1.2 OPERATION AND MAINTENANCE
It is the operator’s responsibility to perform all safe-
ty checks; to make sure that all maintenance for safe
operation is performed promptly; and to have the
equipment checked by an Authorized Dealer periodi-
cally. We strongly recommend that the operator read
this Owner’s Manual and thoroughly understand all
instructions before using this equipment.
It is the owner/operator’s responsibility for the fol-
lowing:
Perform all safety checks.
For safe operation, promptly perform all mainte-
nance.
Have equipment checked periodically.
1.3 SAFETY
Before attempting to use the generator set, carefully
read GENERAL SAFETY RULES inside the cover of
this Manual. Comply strictly with these RULES to
prevent accidents and damage to equipment and/or
property. We suggest that copying and posting GEN-
ERAL SAFETY RULES in potential hazard areas.
Stress safety to all operators and potential operators
of this equipment.
1.4 GENERATOR APPLICABILITY
This generator has been designed and manufactured
for supplying electrical power. You should not modify
the generator or use it for any application other than
for what it was designed. If there are any questions
pertaining to its application, write or call the factory.
Do not use the unit until a competent authority has
advised you.
1.5 SPECIFICATIONS
Engine
Type ........................................................Generac GT 990
Rated HP..................................................30 at 3600 RPM
Displacement ..........................................................992 cc
Cylinder Block ..............Aluminum With Cast Iron Sleeves
Cooling Method ................................................Air Cooled
Type of Governor ........................Mechanical Fixed Speed
Air Cleaner ............Paper Element with Foam Pre-Cleaner
Starter ......................................................12V DC Electric
Ignition System ............Solid State with Flywheel Magneto
Spark Plug Gap ................................0.030 Inch (0.8 mm)
Recommended Spark Plugs ................Champion RC12YC
Fram Autolite 65
Oil Sump Capacity ......................................1.5 US Quarts
Recommended Oil ....................................5W-30 Synthetic
Generator
Rated kW ......................................................................6.0
Output Voltage......................................27.2V DC Nominal
Output Current..........................................220A Full Load
Stator ..................................................6 Phase - Rectified
Rotor RPM ................................................................3600
Engine RPM ..............................................................2700
Weight ..................................................................550 lbs.
Length ................................................................1355 mm
Width....................................................................980 mm
Height ..................................................................730 mm
1.6 FUEL SYSTEM
The unit has been designed to be mounted above a
propane enclosure. A dividing plate has been sup-
plied to be placed under the unit to separate the gen-
erator from the propane tank. During installation it is
important that this dividing plate be positioned
beneath the generator and bolted into place.
The fuel supply line has been supplied with a bulk-
head fitting which should be attached to the dividing
plate with the locking nut provided (Figure 1.1).
Figure 1.1 — Propane Tank Connection
Once installed the bulkhead fitting will provide a
3/4”-16, 37° JIC fitting to which the propane tank can
be connected. The fuel pressure to the unit must be
regulated to 11-14” WC for the unit to perform as
designed.
With LP gas, use only the vapor withdraw type sys-
tem. This type of system uses the vapor formed above
the liquid fuel in the storage tank.
The engine has been fitted with a carburetion system
which meets the specifications of the 1997 California
Air Resources Board for tamer proof dual fuel sys-
tems. The unit will run on natural gas or propane fuel
and has been factory set to run on LP gas. Should the
primary fuel need to be changed to natural gas, then
the fuel system needs to be reconfigured (Figure 1.2
on page 6).
Section 1 — General Information
Generac APS 6.0 DC Auxiliary Power System
Generac®Power Systems, Inc. 5
6 Generac®Power Systems, Inc.
1.6.1 RECONFIGURING THE FUEL SYSTEM
To reconfigure the fuel system to run on natural gas,
follow these instructions (See Figure 1.2):
1. Loosen the hose clamp holding the fuel hose to
the 1/2” hose fitting.
2. Remove the hose from the hose fitting.
3. Remove the hose fitting from the regulator cast-
ing.
4. Remove the LP jet which is located below the hose
fitting inside the regulator casting.
5. Remove the natural gas jet from the holding sock-
et on the outside of the regulator casting.
6. Insert the natural gas jet in place of the LP jet and
place the LP jet into the holding socket.
7. Replace the hose fitting onto the regulator casting.
8. Replace the hose into the hose fitting.
9. Tighten the hose clamp to the hose fitting.
10. The unit is now configured to run on natural gas
fuel.
Figure 1.2 — Reconfiguring the Fuel System
1.6.2 RECOMMENDED FUEL
Recommended fuels should have a Btu content of at
least 1000 Btus per cubic foot for natural gas; or at
least 2520 Btus per cubic foot for LP gas. Ask your
fuel supplier for the Btu content of your fuel.
GASEOUS FUELS SUCH AS NATURAL AND LP
(propane) GAS ARE HIGHLY EXPLOSIVE. EVEN
THE SLIGHTEST SPARK CAN IGNITE SUCH
FUELS AND CAUSE AN EXPLOSION. NO LEAK-
AGE OF FUEL IS PERMITTED. NATURAL GAS,
WHICH IS LIGHTER THAN AIR, TENTS TO COL-
LECT IN HIGH AREAS. LP GAS IS HEAVIER
THAN AIR AND TENTS TO SETTLE IN LOW
AREAS.
2.1 INSTALLATION
This Owner’s Manual has been prepared under the
assumption that a competent, qualified technician
installed the generator. We also assume the installer
complied with all applicable codes, standards and
regulations pertaining to installation.
Owner/Operators must make sure to do nothing that
might render the installation unsafe or in noncompli-
ance with applicable codes, standards and instruc-
tions. They should be sure the unit has been installed
to allow adequate ventilation for cooling and exhaust
air.
2.1.1 UNIT LOCATION
The general APS 6.0 24V DC generator has been
designed specifically for use in the telecommunica-
tions industry. The unit is housed in a sound attenu-
ated weatherproof sheet metal enclosure for outside
use only.
During installation it is extremely important that cer-
tain considerations are taken to allow adequate ven-
tilation for cooling and exhaust air and access for
servicing the unit. Figure 2.1 shows the minimum
requirements to allow proper operation of the unit.
Figure 2.1 — Ventilation Requirements
The unit should never be installed up against brick
walls or in tight corners. For proper unit operation, it
is important that the hot exhaust air venting from the
rear of the enclosure does not recirculate into the
engine and control panel intakes. During installation,
ensure all vents and intakes are clear of any foreign
materials that might restrict air flow. This includes
the vents for the rectifier and filter assembly located
on the side of the unit (Figures 2.2 and 2.3).
DANGER
Section 2 — Installation
Generac APS 6.0 DC Auxiliary Power System
Hose Clamp Fuel Hose
1/2” Hose
Fitting
Natural Gas
Jet
12 VDC
Solenoid
THE ENGINE EXHAUST FROM THIS PRODUCT
CONTAINS CHEMICALS KNOWN TO THE STATE
OF CALIFORNIA TO CAUSE CANCER, BIRTH
DEFECTS, OR OTHER REPRODUCTIVE HARM.
THE GENERATOR ENGINE GIVES OFF DEADLY
CARBON MONOXIDE GAS THROUGH ITS
EXHAUST SYSTEM. THIS DANGEROUS GAS, IF
BREATHED IN SUFFICIENT CONCENTRATIONS,
CAN CAUSE UNCONSCIOUSNESS OR EVEN
DEATH. DO NOT OPERATE THE GENERATOR IF
THE EXHAUST SYSTEM IS LEAKING OR HAS
BEEN DAMAGED. SYMPTOMS OF CARBON
MONOXIDE POISONING ARE (a) inability to
think coherently; (b) vomiting; (c) twitching
muscles; (d) throbbing temples; (e) dizziness;
(f) headaches; (g) weakness and sleepiness. IF
YOU FEEL ANY OF THESE SYMPTOMS, MOVE
INTO FRESH AIR IMMEDIATELY. IF SYMPTOMS
PERSIST, GET MEDICAL HELP.
Figure 2.2 — Roof Vents
Figure 2.3 — Rectifier and Filter Assembly Vents
3.1 OPERATION
This section of the manual will describe the operation
of the unit as a whole and in some detail various com-
ponents with which the customer will interface with.
The engine/alternator assembly is housed in its own
section of the enclosure. All service points for the
engine and alternator are accessible from the front of
the enclosure. I.E., oil fill/drain, oil filter, spark plugs,
air filter and for the alternator, brush access (see
Maintenance Section for Service Periods and
Procedures).
The alternator is driven by means of a pulley and
drive belt arrangement. The drive belt and pulleys are
warranted for the life of the generator. Drive belt ten-
sion was properly adjusted before the unit was
shipped from the factory. If there is a suspicion that
drive belt tension is incorrect, contact Generac or the
local service support contractor.
It is important that both air intakes for the engine
and alternator remain free from debris at all times.
3.2 ELECTRICAL CONNECTIONS
The generator has been designed to make all electri-
cal connections to the unit simple and easy.
3.2.1 STARTING BATTERY
A 12V DC automotive type battery with a cold crank-
ing capacity of 525 Amps should be placed in the bat-
tery tray on the right hand side of the control panel
enclosure. Positive and negative cables are provided
for connection to the battery (Figure 3.1).
Figure 3.1 — Battery Cables
Servicing of the battery is to be performed or super-
vised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized person-
nel away from batteries.
!
!
Section 3 — Operation
Generac APS 6.0 DC Auxiliary Power System
Generac®Power Systems, Inc. 7
Battery Tray
Battery Cables
8 Generac®Power Systems, Inc.
When replacing the battery, use the following type of
battery: Group 26/26R 12-volt battery with a rating of
525 cold-cranking amps minimum at -17.8º C (0º F).
When using a maintenance-free battery, it is not nec-
essary to check the specific gravity or electrolyte level.
Have these procedures performed at the intervals
specified in the “Service Schedule.” A negative ground
system is used. Battery connections are shown on the
wiring diagrams. Make sure the battery is correctly
connected and terminals are tight. Observe battery
polarity when connecting the battery to the generator
set.
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following
precautions are to be observed when working
on batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or dis-
connecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to
the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, immediately
flush thoroughly with water and seek medical
attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicar-
bonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The
following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from your body before
touching the battery by first touching a grounded
metal surface.
Be sure the Auto/Off/Manual switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as
the battery cables are connected.
Be sure the utility power supply is turned off,
or sparking may occur at the battery posts as
you attach the cables and cause an explosion.
3.2.2 DC OUTPUT POWER
The DC output from the unit is taken from two 3/8”
terminals located along the bottom edge of the con-
trol panel. There is sufficient thread on these termi-
nals to add the customer power leads and extra lock
nuts without loosening the factory connections
should these connections become loose, ensure the
cables are routed exactly as supplied from the facto-
ry. A short on either of the output cables could dam-
age components within the unit (Figure 3.2).
Figure 3.2 — DC Output Connections
3.2.3 ALARMS AND UTILITY INPUT
The unit has a number of alarm outputs which can be
monitored via an external source to give information
on the status of the unit (see pages 11 and 12). These
alarm connections are located on the left hand side of
the control panel enclosure. Also on this connection
block are terminals for utility input. The unit
requires a 240V utility input to monitor. During
installation, alarms to be monitored and utility input
connections should be made at this connection block
(Figure 3.3).
!
!
!
DANGER
Section 3 — Operation
Generac APS 6.0 DC Auxiliary Power System
Generac®Power Systems, Inc. 9
Figure 3.3 — 12 Position Terminal Block
3.3 ELECTRICAL PANEL
The Electrical Panel, mounted at one end of the
enclosure contains all the electrical components for
proper unit operation (see Figure 3.4).
3.4 ELECTRICAL OPERATION
The engine runs at a speed of 2700 RPM and drives
the alternator at 3600 rpm, producing an AC 6 phase
voltage. This voltage is taken directly from the stator
windings and into two independent 3-phase bridge
rectifiers. The DC output from the rectifier is then fed
into an inductive-capacitive filter assembly designed
to reduce the AC ripple content of the DC output. The
output of the filter is then fed directly to the genera-
tor output terminals.
12 V DC fans assist in cooling both the rectifier and
filter during generator operation. During any inspec-
tion or service of the generator, the operation of both
fans should be checked and replaced if faulty.
The following section describes in some detail most
of the components the user may interface with.
3.4.1 VOLTAGE REGULATOR
A solid state voltage regulator (Figure 3.5). controls
the generator output by supplying an excitation cur-
rent to the rotor. By regulating the rotors excitation
current, the strength of its magnetic field is regulated.
This, in turn, controls the output voltage. To regulate
the field current to the rotor, the voltage regulator
must be connected to the customer DC Bus. This pro-
vides sensing voltage to the regulator. Figure 3.6
shows a simple schematic for the voltage regulator.
Figure 3.5 — Voltage Regulator
Section 3 — Operation
Generac APS 6.0 DC Auxiliary Power System
Figure 3.4 — Electrical Panel
Control PCB
12 VDC Fan Current Transformer
Smoothing
Capacitor
3-Phase Bridge
Rectifier
Ground TerminalHour Meter
Voltage
Regulator
10 Generac®Power Systems, Inc.
Figure 3.6 — Voltage Regulator Set Up
The voltage regulator will be set at the factory to pro-
vide the required output voltage. However, should
adjustment be required in the field, the regulator is
fitted with four adjustment potentiometers (Figure
3.7).
Figure 3.7 — Field Adjustment Points
NOTE:
Unnecessary adjustment of these potentiometers
by inexperienced personnel will result in the
impairment of the unit performance. Do not adjust
any pot without clear knowledge of its affect on
the generator.
3.4.2 FINE AND COURSE VOLTAGE ADJUST
These two potentiometers set the required output
voltage.
3.4.3 UNDER FREQUENCY ADJUST
This potentiometer allows the frequency at which the
voltage beings to drop off to be varied. This is one of
the devices built into this generator to protect the
engine from overload and potentially a burnout. If the
engine for some reason begins to overload, it will
slow down. Rather than the voltage regulator increas-
ing the excitation current at a set frequency (to main-
tain constant output voltage), the voltage regulator
will begin to lower the output voltage while maintain-
ing near constant speed (decreasing engine load).
3.4.4 CURRENT LIMIT ADJUST
Another protection device built into the generator is
that the potentiometer allows a maximum current
limit to be set. This is because the generator will be
connected to a bank of batteries. In a state of dis-
charge, the batteries will demand high charge cur-
rents far in excess of the rating of the generator. To
prevent overload, the output current is monitored via
a current transformer. The potentiometer has been
factory set for the output voltage to begin to drop off
at approximately 225 Amps DC in an attempt to
maintain a constant output current.
3.4.5 FIELD SET UP PROCEDURE
The following is the recommended procedure for
checking the output voltage on the generator. This
procedure should be performed after the unit has
been installed on site but BEFORE the unit is con-
nected to the Lucent Technologies Rectifier cabinet.
The voltage set point should be 26.2 VDC.
1. Attach two 12 volt automotive type batteries, con-
nected in series (to provide a 24V supply), to the
output terminals of the generator.
2. Attach a digital voltmeter to the output terminals
of the generator.
3. The voltmeter should be reading approximately
25V. If the batteries are fully charged, and the
voltmeter reads above 26.2V, then it will be nec-
essary to discharge the batteries. When a voltage
between 25V to 25.5V has been achieved, contin-
ue the setup.
4. Start the unit in the manual mode. The engine
will start and stabilize. After a delay of between
15 to 45 seconds, the voltage regulator will turn
on. This will be apparent in a sudden engine
sound change, and the voltmeter will be reading a
higher voltage than previously. This voltage is fac-
tory set at 26.2V. Confirm this, and if the voltage
is correct, shut the unit down and continue the
installation. If the voltage set point is low or high,
proceed as follows.
5. Using a combination of both the fine and coarse
voltage adjust potentiometers, readjust the out-
put voltage to 26.2V. Use caution during the
adjustment as the coarse potentiometer is very
sensitive and a small change will result in a
large voltage change.
6. If for some reason the voltage is mistakenly
turned too low and the voltmeter is again reading
battery voltage, slowly turn the voltage pots up
until the change in engine sound is heard.
Continue to adjust the voltage as described
above.
Section 3 — Operation
Generac APS 6.0 DC Auxiliary Power System
Generac®Power Systems, Inc. 11
Section 3 — Operation
Generac APS 6.0 DC Auxiliary Power System
7. Once the output voltage has been set, shut the
unit down and allow to stop. Re-start the unit and
double check that the output voltage is set to
26.2V.
8. The unit can now be connected to the Lucent
Rectifier box.
3.4.6 ENGINE CONTROL, ALARM AND
SHUTDOWN P.C.B.
The control panel performs all the start/stop and
shutdown functions of the generator both in manual
and automatic modes (Figure 3.8).
Figure 3.8 — Control Panel
3.4.7 MANUAL OPERATION
Select manual on the Manual/Off/Auto switch. The
engine generator will crank and start. In the manual
mode, all alarm and shutdown functions are opera-
tional.
3.4.8 AUTOMATIC OPERATION
Select auto on the Manual/Off/Auto switch. In Auto
mode, a printed circuit board on the control panel
constantly monitors utility power source voltage.
Should that voltage drop below a preset level
(approximately 130V) and remain at such a low state
for a period of time, the engine will crank and start.
The time interval between utility fail and engine start,
(Delay on Start), can be field selected by changing the
position of a series of dip switches mounted on the
printed circuit board (Figure 3.9).
Figure 3.9 — Dip Switches
Each unit has been factory set with a 2 minute delay
on start as a standard. Depending on the battery
bank capacity and the load requirements, this time
may need to be adjusted.
When the utility voltage returns to a pre-set level
(approximately 153V) and remains at that high level,
the printed circuit board will keep the engine running
for a duration of approximately 5 minutes as a cool
down period. During automatic operation, all alarm
and shutdown functions are operational.
3.4.9 OFF POSITION
With the manual/off/auto switch in the off position.
The unit will remain stationary indefinitely.
3.4.10 REMOTE START
When the Auto/Off/Manual switch is in the Auto posi-
tion, application of 12 VDC to this contact point will
start the engine. The engine will continue to run as
long as 12 VDC is present.
3.4.11 REMOTE STOP
When the Auto/Off/Manual switch is in the Auto posi-
tion, application of 12 VDC to this contact point will
prevent the engine from starting and running.
As long as 12 VDC is maintained, the unit will run.
This contact point can also be used to remotely reset
alarm faults.
3.4.12 ALARMS
The control panel provides a number of status alarm
outputs which can be monitored by the operator. The
alarm signals from the control panel are located on a
12 position terminal block mounted on the left hand
side of the electrical enclosure (Figure 3.10).
Only Switch 1 ON = 2 min. delay
Only Switch 2 ON = 5 min. delay
Only Switch 3 ON = 10 min. delay
Only Switch 4 ON = 15 min. delay
All Switches OFF - 20 min. delay
12 Generac®Power Systems, Inc.
Figure 3.10 — 12 Position Terminal Block
NOTE:
PCB alarms marked with “*1” relay contact clo-
sure to ground. These contacts can be used to
switch DC voltage up to 30 VDC at 1 amp current.
3.4.13 START BATTERY VOLTAGE ALARM
This status signal indicates a low or overcharged
engine start battery. A low condition would be 10V
DC or lower, and an overload would be 14.5V DC or
higher. This alarm contact is normally open.
3.4.14 SWITCH NOT IN AUTO ALARM
This signal indicates that the Manual/Off/Auto switch
is not in the auto position and will not start in the
event of utility failure.
3.4.15 GENERAL FAILURE ALARM
This alarm signal indicates a forced shutdown due to
an engine fault (see Protective Shutdown Circuits,
Page 13). This alarm contact is normally open.
3.4.16 ENGINE RUN ALARM
This status signal indicates that the engine generator
is running and producing an output. This alarm con-
tact is normally open.
3.4.17 PROTECTIVE SHUTDOWN CIRCUITS
The printed circuit board on the control panel moni-
tors a number of inputs from the engine. Should a
problem in the operation of the engine arise, the cir-
cuit board will shutdown the unit to prevent cata-
strophic failure. The protection circuits include the
following:
Low oil pressure shutdown - below 10 PSI
High engine temperature shutdown - above 284º F
Overspeed shutdown - above 3225 RPM
Overcrank shutdown - allows the unit to attempt
to start in cycles for approximately 90 seconds
then locks out the starter.
3.4.18 UTILITY SOURCE VOLTAGE
The control panel requires a 240V input to monitor
the utility voltage.
N2 - 240V AC
N1 - 240V AC
Ground Utility
3.4.19 BATTERY CHARGER
The control panel circuit board also contains an
engine start battery charger. This charger only oper-
ates while utility voltage is present. The charger pro-
vides a 1.5A maximum trickle charge. This charger is
only to keep the battery voltage floating while the
engine is stationary. During engine running periods,
the battery is charged via a winding in the stator
through a regulator at a maximum charge current of
7.5 A.
3.4.20 EXERCISE TIMER
In order to maintain system reliability and to perform
secondary functions such as engine lubrication and
battery charging, the unit is fitted with an electronic
programmable timer which, once programmed, will
exercise the generator at customer specific intervals
(Figure 3.11). For information on the programming of
the timer, see the separate Operating Instructions
supplied with each unit.
Generac strongly suggests that the unit be exercised
for a minimum of 30 minutes at least every seven
days.
Section 3 — Operation
Generac APS 6.0 DC Auxiliary Power System
Figure 3.11 — Exercise Timer
3.5 SETTING THE EXERCISER
3.5.1 DISPLAY
3.5.1.1 Current Time
The current time is selected with the time/alarm
push-button and is displayed in 12:00 hour format
on four 7-segment LED displays. The colon flashes at
a rate of 0.5 seconds on/off to indicate normal oper-
ation and display of the current time.
3.5.1.2 Exercise Time
The exercise time is selected with the time/alarm
push-button, the exercise time for the selected day is
displayed in a similar format to current time, except
that the colon does not flash but is always ON to indi-
cate the exercise time is being displayed.
To change the exercise day being displayed, use the
day” push-button when in this mode.
3.5.1.3 PM (Time)
A single LED indicates PM (ON) time or AM (OFF).
3.5.1.4 Day of Week
The day of the week is indicated on the seven indi-
vidual day LEDs which represent Sunday through
Saturday.
3.5.1.5 Exercise ON
A single LED indicates that the relay output is
switched ON (exercise period).
3.5.1.6 Power Saving
To minimize the power consumption of the unit, it
will switch to a “dim” display mode if no keyboard
activity is noted for five minutes. The display bright-
ness is reduced to 50% of normal, but returns to
100% when any key is pressed.
3.5.1.7 Default Times
When the exerciser is first powered up, or if power is
removed from the unit and the battery backup has
expired, the default times will revert to:
Current Time 9:00 am
Current Day Sunday
Sun.-Sat. Exercise 9:00 am
Exercise Period 20 minutes
3.5.2 EXERCISE TIMES
The exercise times may be set individually on a day
by day basis. Exercise periods can overlap days, i.e.,
if a time is set for 11:55 pm Sunday for 20 minutes,
it will turn off at 12:15 am Monday.
The exercise period is globally programmable (com-
mon to all days), and is limited from 10-59 minutes.
3.6 PUSH BUTTONS
3.6.1 UP ARROW
The up arrow is used to step the time forward in
increments of one second. This feature has auto-
acceleration, if the button is held on, the step incre-
ments will progressively increase to allow fast search-
ing of a required time. As soon as the button is
released, it will revert to normal speed.
3.6.2 DOWN ARROW
The down arrow is used to step the time backward in
increments of one second. It also has auto-acceleration.
3.6.3 TIME (TIME/ALARM TOGGLE)
This toggles the display between normal current time
and exercise time. When in exercise time mode the
following happens:
1. The colon stops flashing to indicate exercise time
mode.
2. The Sun LED flashes to indicate it is initially
selected. The rate of flashing is either:
a. 50:50% on/off to indicate exercise time is
enabled.
b. 90:10% on/off to indicate exercise time is not
enabled.
3. All other days that have exercise time enabled to
ON are indicated by LED on. Days that are dis-
abled are set to LED off.
✧ ✧
✧ ✧
Generac®Power Systems, Inc. 13
Section 3 — Operation
Generac APS 6.0 DC Auxiliary Power System
9 V Battery
(not supplied)
If the display is inadvertently left in this mode with no
keyboard activity for more than five minutes, it will
revert back to normal (current time) display.
3.6.4 ON/OFF (ALARM SELECT TOGGLE)
When in exercise mode, this button will toggle the
exercise enable/disable status of the displayed day.
The rate of flashing will change as above.
3.6.5 DAY
This is used to step forward through the days in
either current time or exercise time.
1. In current time mode, the days will step through
seven states indicating Sunday to Saturday.
2. In exercise time mode, the days will step through
seven states indicating Sunday to Saturday and
will then display state eight - all days LEDs flash-
ing on/off together which represents the global
exercise time period. In this mode, the exercise
period may be changed using the up/down arrows
but the on time is limited to between 10 and 59
minutes.
3.7 PROGRAMMING EXAMPLES
3.7.1 EXAMPLE 1 - CHANGE TIME FROM
SUNDAY 9:00 AM TO WEDNESDAY
2:00 PM
1. Ensure the current time is displayed by flashing
colon. If colon is not flashing, then press and
release the “time” push-button once.
2. Press and hold the “up arrow” push-button until
the time steps to almost 2:00 pm, note the pm
LED will now be on.
3. Repeatedly press and release the “up arrow”
push-button until the exact time is obtained. If
you go past 2:00 pm, use the “down arrow” to
step back to the required time.
3.7.2 EXAMPLE 2 - SET EXERCISER ON FOR
14 MINUTES MON-FRI AT 10:00 AM
1. Press and release the “time” push-button once to
display the exercise time for Sunday, indicated by
a static (ON) colon and a flashing “Sun” LED. If
the colon is still flashing, repeat this step.
2. The “Sun” LED should be flashing on/off 50:50
approximately four times/second. This means
that the exercise time is correctly set to ON for
Sunday. If it is ON but briefly flashes OFF once
every two seconds, this indicates the exercise
time is set to OFF. If ON, press and release the
on/off push-button once to toggle this state to
OFF.
3. Press and release the “day” button to advance
from Sunday to Monday, indicated by the “Mon
LED flashing.
4. Press and release the on/off push-button once to
toggle the exercise state from OFF to ON. This
will be indicated by the “Mon” LED now flashing
on/off 50:50 approximately 4 times/second.
5. Repeat steps 3 and 4 for Tuesday through
Saturday ensuring the correct on/off exercise sta-
tus for each day.
6. Press and release the “day” button once more and
the display will now show “0:20” which is the
exercise period in minutes. This is common for
all days and this display mode is indicated by all
seven “day” lights flashing simultaneously.
7. Use the up/down arrows to change the exercise
period to 14 minutes.
8. Press and release the “time” push-button once to
return the display mode to the current time.
4.1 GENERAL MAINTENANCE
4.1.1 25 HOUR BREAK IN PERIOD
The first 25 hours of operation is the break-in period
for the generator. Properly breaking in the generator
is essential to reducing oil consumption and enhanc-
ing engine performance. During this 25-hour break
in period, follow this procedure:
Run the unit at varying electrical loads, to help seat
engine piston rings properly.
Check engine oil level frequently during the break-
in period. Add oil if needed. It is normal for the
generator engine to consume more oil than is nor-
mal until the piston rings have properly seated.
After operating the unit for 25 hours, complete the
tasks recommended under “25-Hour Check Up.”
4.1.2 25 HOUR CHECK UP
After the 25-hour break-in period, contact an author-
ized service facility for the following maintenance:
Change engine crankcase oil and oil filter.
Inspect cooling and ventilation openings.
Check engine carburetor adjustments.
Check engine ignition system.
Inspect entire electrical system.
Inspect the engine exhaust system.
4.1.3 ATTENTION REQUIRED AFTER
SUBMERSION
If the generator has been submerged in water, it must
NOT be started or operated. Following any submer-
sion in water, have an authorized Generac Service
Facility thoroughly clean and dry the generator.
Section 4 — Maintenance
Generac APS 6.0 DC Auxiliary Power System
14 Generac®Power Systems, Inc.
4.1.4 EFFECTS OF MOISTURE AND DIRT
Keep the generator set as clean and dry as possible.
Protect the unit against excessive dust, dirt, corrosive
vapors, etc. Permitting dirt and moisture to accumu-
late on generator windings will have an adverse effect
on the insulation resistance of those windings.
When moisture is allowed to remain in contact with
windings, some of the moisture will be retained in
voids and cracks in the insulation. This causes a
reduced insulation resistance and will eventually
cause problems. Dirt will make the problem worse,
since dirt tends to hold moisture in contact with
windings. Salt (as from sea air) will also worsen the
problem since it tends to absorb moisture from the
air. Salt and moisture, when combined, form a good
electrical conductor.
4.1.5 ENGINE OIL RECOMMENDATIONS
Use a high quality detergent oil that meets or exceeds
API Service SF, SF/CC or SF/CD requirements for
gasoline engines.
The PRIMARY recommended oil is a synthetic oil
such as MOBILE Formula 5W-30. Synthetic oil pro-
motes easier starts in cold weather and provides
maximum protection in hot weather.
Any attempt to crank or start the engine
before it has been properly serviced with the
recommended oil may result in an engine fail-
ure. The engine crankcase must be properly
filled with the recommended oil.
4.1.6 BATTERY
All lead-acid storage batteries will discharge when
not in use. The generator battery should be inspect-
ed as follows:
4.1.7 EVERY SIX MONTHS
Have battery state of charge and condition checked.
This should be done with automotive type battery
hydrometer.
Inspect battery posts and cables for tightness, corro-
sion. Clean and/or tighten as needed.
Also check battery fluid level, and, if necessary, fill
with DISTILLED WATER ONLY. DO NOT USE TAP
WATER IN BATTERY.
Servicing of the battery is to be performed or super-
vised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized person-
nel away from batteries.
When replacing the battery, use the following type of
battery: Group 26/26R 12-volt battery with a rating of
525 cold-cranking amps minimum at -17.8º C (0º F).
When using a maintenance-free battery, it is not nec-
essary to check the specific gravity or electrolyte level.
Have these procedures performed at the intervals
specified in the “Service Schedule.” A negative ground
system is used. Battery connections are shown on the
wiring diagrams. Make sure the battery is correctly
connected and terminals are tight. Observe battery
polarity when connecting the battery to the generator
set.
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following
precautions are to be observed when working
on batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or dis-
connecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to
the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, immediately
flush thoroughly with water and seek medical
attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicar-
bonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The
following procedures are to be followed:
!
!
DANGER
!
Section 4 — Maintenance
Generac APS 6.0 DC Auxiliary Power System
Generac®Power Systems, Inc. 15
16 Generac®Power Systems, Inc.
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from your body before
touching the battery by first touching a grounded
metal surface.
Be sure the Auto/Off/Manual switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as
the battery cables are connected.
Be sure the utility power supply is turned off,
or sparking may occur at the battery posts as
you attach the cables and cause an explosion.
4.2 ENGINE PROTECTIVE DEVICES
Unlike an automobile engine, the generator may have
to run for long periods of time with no operator in the
vicinity to monitor engine conditions. For that rea-
son, the engine is equipped with several devices
which protect it against such potentially damaging
conditions as (a) low oil pressure and (b) high tem-
perature.
4.2.1 AUTOMATIC LOW OIL PRESSURE
SHUTDOWN
The engine is equipped with a normally closed (N.C.)
contacts oil pressure switch (Figure 18). Engine oil
pressure holds the switch open during cranking and
operating. Should oil pressure drop below about 10
psi, switch contacts close and the engine shuts down.
4.2.2 HIGH TEMPERATURE SWITCH
Switch (Figure 4.1) contacts close if temperature
should exceed about 285 F (140 C) to initiate an
engine shutdown.
Figure 4.1 — Engine Protective Devices
4.2.3 CHECKING ENGINE OIL LEVEL
To check the engine oil level, proceed as follows
(Figure 4.2):
1. Remove dipstick and wipe it dry with a clean
cloth.
2. Install and tighten dipstick cap, then remove
again. Oil level should be at the dipstick “full”
mark. If necessary add oil to the “full” mark only.
DO NOT FILL ABOVE THE “FULL” MARK.
3. Install and tighten the dipstick.
Figure 4.2 — Oil Dipstick and Filler Tube
Never operate the engine with oil level below
the ADD mark on dipstick. Doing this could
damage the engine.
4.3 CHANGE ENGINE OIL
Change engine oil after the first 25 hours of opera-
tion. Thereafter, change oil every 100 operating
hours. Change oil more frequently if operating con-
sistently under heavy load or at high ambient tem-
peratures. To change oil, proceed as follows:
1. Run engine until it is thoroughly warmed up, then
shut OFF the engine.
2. Immediately after the engine shuts OFF, pull OIL
DRAIN HOSE (Figure 4.2) free of its retaining
clip. Remove CAP from hose and drain oil into
suitable container.
3 When oil has drained, install cap onto end of oil
drain hose. Retain hose in clip.
4. Refill with proper recommended oil (see Page 15).
!
!
Section 4 — Maintenance
Generac APS 6.0 DC Auxiliary Power System
Oil Fill
Oil Level
Dipstick
Oil Drain
Hose
Oil Filter
Generac®Power Systems, Inc. 17
4.4 CHANGE OIL FILTER
Change engine oil filter every 200 operating hours (or
every second oil change), as follows:
1. Remove old oil filter by turning counterclock-
wise(Figure 4.4).
2. Apply a light coating of clean engine oil to gasket
of new filter.
3. Screw new filter on by hand until its gasket con-
tacts the oil filter adapter lightly. Then, tighten fil-
ter an additional 3/4 to one turn.
4. Start engine and check for leaks.
Figure 4.4 — Engine Oil Filter
4.5 SERVICE FOAM PRE-CLEANER
AND ENGINE AIR CLEANER
Clean and oil the FOAM PRE-CLEANER (Figure
4.5) every three months or every 100 operating
hours, whichever comes first. Service more fre-
quently if operating under extremely dusty or dirty
conditions.
• Annually, or every 250 hours of operation, clean
the AIR FILTER ELEMENT. Replace the air filter
element every 500 hours or sooner if extremely
dirty.
1. To remove the foam pre-cleaner and air filter ele-
ment, loosen and remove the plastic wing bolt
and the air box cover. Slide the foam pre-clean-
er off the air filter element.
2. Replace foam pre-cleaner or wash it in kerosene
or in liquid detergent and water. Wrap foam pre-
cleaner in cloth and squeeze dry.
3. Saturate foam pre-cleaner in engine oil. Squeeze
to remove excess oil.
4. Clean the air filter element by blowing air from
the inside, out.
5. Return the air filter and the foam pre-cleaner
into the air box and secure with retaining nut.
6. Replace air box cover and secure plastic wing
bolt.
Figure 4.5 — Engine Air Cleaner Assembly
DO NOT oil the PAPER FILTER. DO NOT use
any petroleum solvents, such as kerosene, to
clean the filter. DO NOT use air pressure to
clean or dry paper filter.
4.6 COMPLETE ENGINE TUNE UP
Annually, an authorized service technician should
tune up the engine. This annual tune up should
include the following tasks:
Remove engine air cleaner and inspect. Clean or
replace as necessary.
Check engine oil level.
Clean the engine and generator.
Check engine intake manifold for damaged gas-
kets.
Inspect engine governor springs for damage.
Replace any damaged components.
Check governed speed and adjust governor, if nec-
essary.
Check engine for evidence of oil leaks.
Check for proper ignition spark using an appro-
priate engine spark tester.
Check valves for lash adjustment.
Clean spark plugs, inspect and reset plug gaps.
Replace plugs if necessary.
Check exhaust muffler and engine exhaust mani-
fold for restrictions, damage.
Run engine and check operation. Adjust load block
if necessary.
4.7 INSPECT COOLING SYSTEM OF
GENERATOR
At least quarterly, inspect air inlet and outlet open-
ings in the generator compartment. All air openings
must be clean and unobstructed.
!
AIR B
OX
RETAININ
G
S
T
UD
AIR FILTER
F
O
AM PRE
C
LEANE
R
PLASTIC
AIR B
O
X
CO
VE
R
WING
B
N
UT
RETAININ
G
Section 4 — Maintenance
Generac APS 6.0 DC Auxiliary Power System
5
7
8
6
4
2
1
3
6
8
7
5
3
1
2
4
A
U
T
O.
MAN
U
A
L
17
8
2
P
C
B = EN
G
INE
CO
NTR
O
LLER
/
REM
O
TE ALARM B
O
AR
D
G
ENERAL FAIL
U
RE ALAR
M
EN
G
INE R
U
N ALAR
M
L
O
W F
U
EL ALAR
M
24
0
V
U
TILIT
Y
G
RD -
U
TILIT
Y
REM
O
TE
S
TART +12
V
REM
O
TE
S
T
O
P +12
V
S
TART BATT. V
O
LTA
G
E ALAR
M
S
WIT
C
H N
O
T IN A
U
T
O
ALAR
M
A
6
N2
N1
G
R
D
U2
A7
U1
CO
MM
ON
TB2
A4
A
3
A
5
A2
A1
TB3 = TERMINAL STRIP
,
POWER CONNECTION
S
15
1
C
T =
CU
RRENT TRAN
S
F
O
RME
R
LE
G
EN
D
F1 = 1
5
A F
USE
D1
,
D2 = DIODE
,
IGNITIO
N
C
B1 = 1
5
A
C
IR
CU
IT BREAKE
R
C
B2 =
3
A
C
IR
CU
IT BREAKE
R
DB1 = DI
O
DE BRID
GE
DB2 = DI
O
DE BRID
GE
HT
O
= HI
G
H TEMP
O
IL
S
WIT
CH
HRM = H
OU
R METE
R
SC
=
S
TARTER
CO
NTA
C
T
OR
TB1 = TERMINAL BL
OCK
S
M =
S
TARTER M
O
T
OR
TD
C
=
U
TILITY INP
U
T
S
TEP D
O
WN TRAN
S
F
O
RME
R
R
3
= RE
S
I
S
T
O
R
5
O
HM 2
5
WAT
T
L
O
P = L
O
W
O
IL PRE
SSU
RE
S
WIT
CH
TB2 = ALARM
CO
NN. TERMINAL
S
TRI
P
SC
R =
S
TARTER
CO
NTA
C
T
O
R RELA
Y
R1
/
R2 = RE
S
I
S
T
O
R 1
/
4
O
HM 2
5
WAT
T
J
B1 =
JU
N
C
TI
O
N BL
OCK
J
B2 =
JU
N
C
TI
O
N BL
OCK
IM1 = I
G
NITI
O
N MA
G
NET
O
- #1
C
YL
.
IM2 = I
G
NITI
O
N MA
G
NET
O
- #2
C
YL
.
S
P1 =
S
PARK PL
UG
- #1
C
YL
.
S
P2 =
S
PARK PL
UG
- #2
C
YL
.
S
W =
S
TART
/
S
T
O
P
S
WIT
CH
F
S
= F
U
EL
SO
LEN
O
I
D
6
17
C
H
O
K
E
1
5
CUS
T
O
MER P
O
WER TAKE
O
F
F
C
APA
C
IT
OR
1
00
V
+
FAN
0
C
H
O
K
E
J
B
1
-
J
B
2
TRAN
S-
F
O
RME
R
1
5
0
14
0
0
U1
0
66
7
4
1
1
83
0
1
5
0
4
3
5
0
1
4
56
85
86
1
8
14
TD
C
E
C7
277
E
C1
8
5
2
6
9
3
E
C3
E
C9
N1
1
N2
L1
4
6
4
5
FAN
0
14
L
2
L1
L
3
0
66
0
0
0
0
1
3
0
1
5
0
0
1
3
0
4
6
4
5
14
C
B
1
1
3A
0
77
66
14
4
5
0
4
3
6
4
6
TB1
85
1
8
86
56
14
14
14
0
F
S
14
1
5
14
1
4
R
3
3
4A
4
66
77
4
2A
CO
NTR
O
L PANE
L
1
5C
1
5C
14
17
8
1
83
0
1
5A
HRM
277
27
8
17
8
17
1
83
SW
1
3
2
27
8
6
4
5
BATT.
C
HAR
G
E
R
1
2
V
O
L
T
RE
G.
1
M K III PR
OG
RAMMABL
E
PM
EXER
C
I
S
E
R
M
S
T
T
W
EX
S
F
O
F
F
TIME
DAY
18 Generac®Power Systems, Inc.
Section 5 — Electrical Data
Generac APS 6.0 DC Auxiliary Power System
Wiring Diagram – Drawing No. 0E3498-A
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

Generac Power Systems 00847-1 Operating & Installation Manual

Category
Power generators
Type
Operating & Installation Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI