  • Hello! I'm your chat assistant, and I've reviewed the Specifications - Installation and Operating Instructions for the Dwyer Series 636 Fixed Range Pressure Transmitters. This document provides detailed information on the transmitters' capabilities, including their 316 stainless steel construction, explosion-proof rating, and ±0.3% accuracy. I'm ready to answer any questions you have about using or installing these transmitters.
  • What type of media can the Series 636 pressure transmitter measure?
    What is the output signal for the standard Series 636 transmitter?
    What is the accuracy of the Series 636?
    What is the maximum loop resistance for the Series 636 transmitter
Series 636 Fixed Range Pressure Transmitter
Specications - Installation and Operating Instructions
Bulletin A-30
The Series 636 Fixed Range Pressure Transmitter converts liquid, gas or vapor
pressure into a 4-20 mA DC or 1-5 VDC (636LP) output signal. All 316 stainless steel
construction makes it compatible with most corrosive media. This explosion-proof
control is FM approved for use in hazardous locations and it meets NACE Standards
for offshore applications. It is also weatherproof, capable of resisting a direct water
spray. With these quality features and ±0.3% full-scale accuracy, the Series 636 is an
exceptional value.
The design is based on a sensitive piezoresistive sensing element consisting of four
diffused strain gages. They form a bridge circuit which varies its resistance when
stressed by the process pressure. Small size and light weight eliminate the need for
complicated mounting hardware and mechanical supports. With simple in-line wiring,
installation is quick and inexpensive. Slim prole enables mounting in spaces too tight
for many other transmitters.
SPECIFICATIONS
Service: Liquid, gas or vapor.
Wetted Materials: 316L SS.
Fill Fluid: DC 200 silicone (standard).
Accuracy: ±0.30% of calibrated span including linearity hysteresis and repeatability
(BFSL) at 25°C (77°F) and 12 VDC excitation.
Stability: ±0.5% of upper range limit for six months.
Temperature Limits: Electronics (ambient): -40 to 140°F (-40 to 60°C); Process
interface: -40 to 212°F (-40 to 100°C).
Pressure Limits: 300% upper range limit.
Compensated Temperature Range: -20 to 180°F (-29 to 82°C).
Thermal Effect: (includes zero and span). Between -20 and 180°F (-29 and 82°C).
±2.0% per 50°F (28°C).
Power Requirements: 12-30 VDC (636), 8-14 VDC (636LP), reverse polarity
protection.
Output Signal: 4-20 mA DC, limited to 30 mA DC (636), 1-5 VDC (636LP).
Zero and Span Adjustments: Null: 4.0 mA ±2% span (636),1 VDC ±1% span
(636LP); Span: 16.0 mA ±1% span (636), 4 VDC ±1% span (636LP).
Loop Resistance: 900 Ω max @ 30 V.
Electrical Connection: 3/4˝ female NPT 24˝ (61 cm), 22 AWG.
Process Connection: 1/2˝ female NPT.
Enclosure Rating: NEMA 4 (IP56).
Weight: 0.83 Ib (374 g).
Compliance: CSA, FM.
FM and CSA approved explosion-proof for Class I, Division 1, Groups B, C, and D,
Class II Groups E, F, and G Class III.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
MODEL CHART
Model Output Operating Range, psi Operating Range, bar
636-0
636-1
636-2
636-3
4-20 mA
4-20 mA
4-20 mA
4-20 mA
0 to 15
0 to 30
0 to 100
0 to 300
0 to 1
0 to 2
0 to 7
0 to 20
1/2 NPT
1 [25.40] HEX 1-1/4
[31.75]
Ø1-25/32
[45.24]
1-1/4 [31.75] HEX
3/4 NPT
4-1/16
[103.19]
1-1/8
[28.58]
#22 AWG LEADS 24 [609.60]
LEADS PLUS SHIELD/DRAIN
Printed in U.S.A. 12/21 FR# 440815-00 Rev. 1©Copyright 2021 Dwyer Instruments, Inc.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
INSTALLATION
Care should be taken during installation to prevent condensate accumulation in the
conduit compartment or sediment accumulation in the diaphragm chamber. See
Figure 2 for suggested piping arrangements in several typical situations. Use pipe joint
compound or Teon® thread tape to assure a leak-proof process connection.
ELECTRICAL CONNECTIONS
An external power supply delivering 12-30 VDC with a minimum current capability of
40 mA DC (per transmitter) or 8-14 VDC if using model 636LP, must be used to power
the control loop. See Figure 3.
To comply with good electrical practice, it is recommended that the transmitter be
grounded. This can be accomplished through either the green wire or the transmitter
case. To avoid a “ground loop” condition, DO NOT use both. The shield/drain wire is
not connected to the case. This shield/drain is normally tired to ground at the receiver
for optimal noise rejection.
The range of appropriate loop resistance, including the receiver load resistance for
the DC power supply being used is limited to that expressed by the graph in Figure 4.
Loop Resistance: 900 Ω max. @ 30 V
MAINTENANCE
After nal installation of the Series 636 Fixed Range Pressure Transmitter, no routine
maintenance is necessary. These transmitters are not eld serviceable and should be
returned to the factory, freight prepaid, if repair is needed. Be sure to include a clear
description of the problem plus any applications information available.
Figure 2
Figure 4
Figure 3
Do not exceed specied supply voltage rating. Permanent damage
not covered by warranty will result. This unit is not designed for AC
line voltage operation. Power must be off while wiring connections are being made.
CAUTION
SERIES 636
PRESSURE
TRANSMITTE
R
POWER
SUPPLY
12-30 VDC
RECEIVER
+
-
BLACK
RED
GREEN
POWER
SUPPLY
12-30 VDC
RECEIVER
+
-
GREEN
WHITE
BLACK
RED
SERIES
636 LP
PRESSURE
TRANSMITTER
12
SUPPLY VOLTAGE (VDC)
15 18 21 24 27
30
900
675
450
225
0
LOOP RESISTANCE (OHMS)
OPERATING
RANGE
VESSEL OR PIPE
FIGURE 2B
MOUNTING FOR
PROCESS WITH
SEDIMENT
FIGURE 2C HORIZONTAL MOUNT
FIGURE 2D
MOUNTING TO ELIMINATE
TRAPPED VAPOR
FIGURE 2A
VERTICAL MOUNT
1/2˝ NP
T
ELBOW
BLEEDER VALVE
CONDUIT
SUPPORT
CONDUIT DRAIN
FIELD
WIRING
CONDUIT
DRAIN TO
PREVENT
MOISTURE
BUILD-UP
/