Hubbell Wiring Device-Kellems 30920069 Installation guide

  • Hello! I've reviewed the installation instructions for Kellems non-conductive pulling grips. The document provides guidance on proper assembly, including cable insertion, mesh smoothing, and taping. These grips are designed for cable pulling, not rope, and different models are recommended for higher loads. I'm ready to answer any questions you have about these grips or their installation process.
  • What should I do before using a pulling grip?
    How should the cable be inserted into the grip?
    How much tape should be used?
    When should I use different kind of grips?
INSTALLATION OF
KELLEMSWNON-CONDUCTIVE PULLING GRIPS
The following steps should be taken to assure proper assembly of Non-conductive Pulling Grips.
1. Thoroughly examine the grip for damage or excessive wear and tear. Do not use damaged or excessively worn grips.
2. Assemble the grip so the cable is inserted into the molded shoulder protector.
3. All slack should be smoothed out of the mesh starting at the molded shoulder protector and working back toward
the tail.
4. Apply vinyl plastic electrical tape starting three inches from the tail of the grip winding onto three inches of the
cable. Continue back and forth, wrapping tape tightly, until two to three layers of tape have been applied. Taping is
required to insure maximum reliability and guard against accidental release.
Note: When higher loads are required, use Kellems Multiple Strength or DUA-pullWGrips.
Note: DO NOT USE FOR PULLING ROPE. FOR PULLING ROPE, USE KELLEMS DUA-pullW GRIPS.
W
DUA-pull is a trademark of the Kellems Division, Hubbell Incorporated
END OF CONDUCTOR
SHOULDER PROTECTOR SHOULDER
MESH
COLOR CODED
END TABS
VINYL PLASTIC
ELECTRICAL TAPE
EYE APPROX. - 3 INCHES ONTO GRIP
APPROX. - 3 INCHES ONTO CABLE
CABLE
TAIL
309-20-069
GRIP PART NUMBER COLOR CODE WORK LOAD (LBS)* SIZE RANGE O.D. (INCHES)
036-28-001 Green 800 .50 – .62
036-28-002 Yellow 1000 .63 – .74
036-28-003 Red 1200 .75 – .99
036-28-004 Blue 1200 1.00 – 1.24
036-28-005 White 1200 1.25 – 1.49
036-28-006 Pink 1200 1.50 – 1.74
*Rated working load is determined by using a safety factor of 5 based on approximate breaking strength.
309-20-069
Wiring Device-Kellems, Hubbell Incorporated (Delaware)
185 Plains Road, Milford, CT 06460-8897 (203) 882-4900 Rev. 12/01
/