REPLACEMENTOF601FTPBG‐201WIP
116‐P‐601FBG201MOUNT/DGB,Rev.A,2016‐02‐04Protectinglife,environmentandproperty
CaseA;Retrofitof601FmountedonFDI(FlameDetectorInterface)
Equipmentandconnections:
FDI:
1. FromtheServiceMenuonthepanel:
Disablethedetectorloop.
2. Turnandliftofftheoldflamedetector
601Ffromitsbase.Unscrewtheblack
andredwirefromthescrewterminalsin
thedetectorbaseandremovethe
detectorbase.
3. Unscrewtheloopwiresfromthe
interfaceinthedetectorbase(FDI).
(Makeamark,orlabeleachwire,to
makesuretheyarereconnectedthe
samewayinBG‐201).
4. Removetheinterface(FDI).
5. InstallandconnecttheBG‐201.The
cablesaretobeconnectedthroughthe
glands.
6. Makesuretheinterfacesettingis
“Legacy”whichisthesettingfor601F
flamedetectorreplacement.Tomakeit
“Legacy”cutthepathonJ4.
7. AfterReplacement(s);enablethe
detectorloop.IfAutroprimepanelis
used,besuretosaveconfigurationand
restartthepanel.
BG‐201:Loopconnections:
FDI BG‐201
1+ 1Input+
2+ 3Output+
3‐2Input‐
4‐4Output‐
BG‐201&BG‐21FDI:FlameDetectorInterface