Autronica BG-201 maritime replacement kit Operating instructions

Category
Fire protection
Type
Operating instructions
REPLACEMENTOF601FTPBG201WIP
116P601FBG201MOUNT/DGB,Rev.A,20160204Protectinglife,environmentandproperty
CaseA;Retrofitof601FmountedonFDI(FlameDetectorInterface)
Equipmentandconnections:
FDI:
1. FromtheServiceMenuonthepanel:
Disablethedetectorloop.
2. Turnandliftofftheoldflamedetector
601Ffromitsbase.Unscrewtheblack
andredwirefromthescrewterminalsin
thedetectorbaseandremovethe
detectorbase.
3. Unscrewtheloopwiresfromthe
interfaceinthedetectorbase(FDI).
(Makeamark,orlabeleachwire,to
makesuretheyarereconnectedthe
samewayinBG201).
4. Removetheinterface(FDI).
5. InstallandconnecttheBG201.The
cablesaretobeconnectedthroughthe
glands.
6. Makesuretheinterfacesettingis
“Legacy”whichisthesettingfor601F
flamedetectorreplacement.Tomakeit
“Legacy”cutthepathonJ4.
7. AfterReplacement(s);enablethe
detectorloop.IfAutroprimepanelis
used,besuretosaveconfigurationand
restartthepanel.
BG201:Loopconnections:

FDI BG201
1+ 1Input+
2+ 3Output+
32Input‐
44Output‐
BG201&BG21FDI:FlameDetectorInterface
REPLACEMENTOF601FTPBG201WIP

AutronicaFireandSecurityAS
|
Tel.:+4773582500
|
Email:info@autronicafire.no
|
www.autronicafire.com
|
Page2
CaseB;Retrofitof601Fusedasaconventionaldevice
CuttheJ5bridgeontheBG201detectortoenableconventionaloperation.ThedeviceisnowfunctionallyidenticaltoaBG
21.UsethesameEOLasforthe601Fyouarereplacing.
TheBG21Conventionaldetectorcanbeusedwithanypanelproviding1024Vloopvoltageandisbasedonthecurrent
increaseprincipletogivealarm.Thedeviceisalsocompatiblewithconventionalloopinterfaceunits;BN33A,BNB330and
BNB331.Analarmresistormustbefittedbetweenterminal3and4ontheconnectionblock.
Thevalueofthealarmresistorcanbedimensionedforcorrectalarmcurrentdependingonthepanel.Themostcommonly
usedalarmresistorsare470or680Ω(680providedfromAutronica).E.g.ina24Vloopsystema680Ωresistorwillresultin
alarmcurrentof35mA.
Equipmentandconnections:
Connectiontothefirst/betweendetectors:
TerminalConnection
1+in
2‐in/out
3+out/alarmresistor
4alarmresistor
Connectiontothelast/singledetector:
TerminalConnection
1+in
2‐in/EOL
3alarmresistor/EOL
4alarmresistor
EOL
Alarm
resistor Alarm
resistor Alarm
resistor
Frompanelor
Interfaceunit
Tolastdetector
Theaboveconnectionbetweendetectorsonaconventionalloopwillsecurefaultactivationatthepanelifoneofthe
connectorsisunplugged.
  • Page 1 1
  • Page 2 2

Autronica BG-201 maritime replacement kit Operating instructions

Category
Fire protection
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI