Potter IFS Series Industrial Flow Switch Owner's manual

Type
Owner's manual

Potter IFS Series Industrial Flow Switch

The Potter IFS Series Industrial Flow Switch is a versatile device designed to monitor and control flow in a variety of liquid applications. It is commonly used to start and stop electrically operated equipment based on flow or no-flow conditions.

The IFS Series is available in several models to meet different application requirements. The IFS-1 and IFS-2 models feature one or two SPDT (Form C) switches, respectively, while the IFS-HC-1 and IFS-HC-2 models offer higher current capacity with their SPDT (Form C) switches. The device is constructed with a durable formed sheet metal enclosure with a powdercoat finish for protection against harsh environments.

Potter IFS Series Industrial Flow Switch

The Potter IFS Series Industrial Flow Switch is a versatile device designed to monitor and control flow in a variety of liquid applications. It is commonly used to start and stop electrically operated equipment based on flow or no-flow conditions.

The IFS Series is available in several models to meet different application requirements. The IFS-1 and IFS-2 models feature one or two SPDT (Form C) switches, respectively, while the IFS-HC-1 and IFS-HC-2 models offer higher current capacity with their SPDT (Form C) switches. The device is constructed with a durable formed sheet metal enclosure with a powdercoat finish for protection against harsh environments.

MFG. #5401022 - rev P-1
6/10
PrINTeD IN USA PAGe 1 OF 3
IFS/IFSS SERIES
INDUSTRIAL FLOW SWITCH
Listings/Approvals:
• UL Guide (NKPZ) for industrial control equipment per UL
Standard508Industrial
• ULGuide(MFHX)forheating/coolingapplianceswitchperUL
Standard353LimitControls
• CSAClass(321106)forindustrialcontrolequipmentperCSA
StandardC22.2No.14-MIndustrialControlEquipment
Maximum Service Pressure: 250 PSI
Enclosure: NEMAType1(Forindooruseonly)
 Formedsheetmetalwithpowdercoatnish.
 (Notforuseinhazardouslocations.)
IFS Contacts:
 IFS-1/IFSS-1:OneSPDT(FormC)switch
 IFS-2/IFSS-2:TwosetsofSPDT(FormC)switchestoprovide
versatilityinwiringtwoseparatecircuits.
 15Ampsat125/250VAC
 .5Ampsat125VDC
 .25Ampsat250VDC
Motor Ratings : 120VAC 240VAC
Horsepower :  1/8 1/4
AC F.L.A. : 3.8 2.9
AC L.R.A. : 22.8 17.4
Pilot Duty Rating :125VA 120/240VAC
IFS-HC Contacts:
 IFS-HC-1/IFSS-HC-1:OneSPDT(FormC)switch
 IFS-HC-2/IFSS-HC-2:TwosetsofSPDT(FormC)switchesto
provideversatilityinwiringtwoseparatecircuits.
 22Ampsat125/250VAC
Motor Ratings :120VAC 240VAC
Horsepower : 1/2 1
AC F.L.A. : 9.8 8.0
AC L.R.A. : 58.8 48.0
Pilot Duty Rating :125VA 120/240VAC
Ambient Temperature Range:
 32°F/176°F(0°C/80°C)
Media Temperature Range:
 32°F/250°F(0°C/121°C)
IFS / IFS-HC Pipe Connection:
 1in.NPTBrass
IFSS / IFSS-HC Pipe Connection:
1in.NPT316StainlessSteel
Conduit Entrance: Twoopeningsfor1/2"conduit
Usage: Forpipesizes1"-8"
Note: ModelIFS-WPavailablewithNEMA4enclosurefor
 outdooruse.(Seebulletinno.5401041).
IFS-1StockNo.9000001(CEMarked)
IFS-2StockNo.9000002(CEMarked)
IFS-HC-1StockNo.9000003
IFS-HC-2StockNo.9000004
IFSS-1StockNo.9000310(CEMarked)
IFSS-2StockNo.9000311(CEMarked)
IFSS-HC-1StockNo.9000312
IFSS-HC-2StockNo.9000313
General
TheModelIFSisaowswitchusedinliquidowlinescarryingwater
or any uid not harmful to brass, stainless steel, or EPDM and not
classiedasahazardousuid.
Thisswitchcanserveasawaytostartandstopelectricallyoperatedequipment
whenaowornoowconditionoccursinavarietyofapplications.
Thisdeviceisdesignedforuseonlyasanoperatingcontrol.Wherean
operatingcontrolfailurewouldresultinpersonalinjuryand/orlossof
property,itistheresponsibilityoftheinstallertoadddevices(safety,
limit controls) that protect against, or systems (alarm, supervisory
systems)thatwarnofcontrolfailure.
PotterElectricSignalCompany,LLC•St.Louis,MOCustService:866-572-3005•TechSupport:866-956-0988•Canada888-882-1833 www.pottersignal.com
Thisdeviceisnotintendedforapplicationsinexplosiveenvironments.
firealarmresources.com
MFG. #5401022 - rev P-1
6/10
PrINTeD IN USA PAGe 2 OF 3
IFS/IFSS SERIES
INDUSTRIAL FLOW SWITCH
Mounting And Installation
TheModelIFSmaybemountedinahorizontalpipelineoravertical
pipelinewithupwardliquidow.Itisnotrecommendedforinstallations
whereowisdownward.Whenmountedinahorizontalpipelinethe
switchwilltripatalowerowratethanshowninFig.7.
Mountthedeviceinasectionofpipewherethereisastraightrunof
atleast5pipediametersoneachsideoftheowswitch.Donotlocate
adjacenttovalves,elbowsororices.Theswitchshouldbemountedso
theterminalsorwireleadsareeasilyaccessibleforwiring.
IFSmodelswithexiblepaddlesarefurnishedwith4paddles.Rigid
paddlemodelsarefurnishedwith2paddles.Forpipesizes1",2",3",6",or
8",usethepaddlesprovided.Intermediatesizesmaybetrimmedfrom
theappropriatepaddleusingthepaddletemplateinFig.5.Thepaddle
mustnottouchtheinsideofthepipeorbindinanyway.Paddlessmaller
thantheactualpipesizeshouldbeusedforaddedsupportandhigher
sensitivity.SeeFig.3.Thepaddlesmustbeproperlyattachedandthe
screwthatholdsthepaddlemustbesecurelytightened.
Fora1"pipeapplicationmountinastandard1"x1"x1"tee.Usea
reducingteeforlargersizesofpipetokeepowswitchclosetopipe
andprovideadequatepaddlelengthintheowstream.
Example:Usea2"x2"x1"teefor2"pipe.Aweldoletmayalsobe
used.ScrewthedeviceintotheteettingasshowninFig.4.Theatof
thepaddlemustbeatarightangletotheow.Thearrowonthesideof
thebushingmustpointinthedirectionofow.
Fig. 3
Typicalpaddlearrangement
for6"to8"pipe.
Note: Turnscrewclockwise
toincreasetheow
raterequiredto
activatetheswitch.
 Turnscrewcounter-
clockwisetodecrease
theowraterequired
toactivatetheswitch.
Fig. 1
Fig. 2
Fig. 4
ScrewthedeviceintotheTEEttingasshown.Caremustbetakento
properlyorientthedeviceforthedirectionoftheow.Donottightenby
graspingtheswitchenclosure.Usethewrenchingatsonthebushing
only.TurningradiusrequiredformountingtheIFSis3".
firealarmresources.com
MFG. #5401022 - rev P-1
6/10
PrINTeD IN USA PAGe 3 OF 3
IFS/IFSS SERIES
INDUSTRIAL FLOW SWITCH
Usedrawingasatemplateandtrimatthedottedarcwhentrimming
theappropriatepaddleforintermediatepipesizes.
Fig. 5
Thepaddlemustnottouchtheinsideofthepipeorbindinanyway.
firealarmresources.com
MFG. #5401022 - rev P-1
6/10
PrINTeD IN USA PAGe 4 OF 3
IFS/IFSS SERIES
INDUSTRIAL FLOW SWITCH
Notes:
1. Typicalowratesfor1"to11/2"pipesizesareaverageswhichmay
varyapproximately±1GPMwiththeuseofabronzereducingtee.
2. Typicalowratesfor2"to8"pipesizesareaverageswhichmay
vary±10%withtheuseofa1"weldolet.
 (*)Flowratesforthesesizesarecalculated.
Fig. 7
TypicalFlowRates-GPMRequiredtoActuateSwitch(ForVerticalPipeInstallations)
PipeSize(Inches) 1 1¼ 2 2½ 3 4 *5 6*8
Minimum
Adjustment
Flow
Increase 4.5 4.5 6 7.5 13.5 18 35 50 70 210
Flow
Decrease 3.5 3.5 5 5.5 9.5 13 25 40 60 190
Maximum
Adjustment
Flow
Increase 9.5 10 13.5 20 29 50 70 120 180 410
Flow
Decrease 7 8.5 10.5 18.5 26 45 65 105 160 380
Wiring
Useproperlyratedtemperaturesupplywirefortheanticipated
servicetemperature.
MakeallelectricalconnectionsinaccordancewiththeNational
ElectricalCodeandlocalregulations.
SeeFigs.6Aand6Bfordiagramsillustratingswitchaction.
Checktheinstallationfor"no-ow"switchoperation.Make
appropriateadjustmentstothesensitivityadjustmentscrewtobe
suretheswitchrestoresfullyatthedesiredowrate.
Adjustment
Removeswitchcoverandturnthesensitivityadjustingscrew
clockwisetoincreasetheowraterequiredtoactuatetheswitch.
Turnthesensitivityadjustingscrewcounter-clockwisetodecrease
theowraterequiredtoactuatetheswitch.(SeeFig.1.)Besureto
replacethecoveruponcompletionoftheinstallationandadjustment.
IFS-1/IFS-2SwitchInformation
Fig. 6A
SWITCH ACTION
ON FLOW
DECREASE
SWITCH ACTION
ON FLOW
INCREASE
SWITCH ACTION
ON FLOW
INCREASE
SWITCH ACTION
ON FLOW
DECREASE
SECOND SWITCH
PROVIDED ON
MODEL IFS02
SECOND SWITCH
PROVIDED ON
MODEL IFSH2
DWG# 1022-2
COM. N.C. N.O.
COM. COM. COM.
COM. COM.
N.O. N.O.
N.O.
N.O. N.O.
N.C. N.C.
N.C. N.C. COM. N.O. N.C.
TOP OF SWITCH(ES)
N.C. N.C.
N.O.
COM.
TOP OF SWITCH(ES)
IFS-HC-1/IFS-HC-2SwitchInformation
Fig. 6B
firealarmresources.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Potter IFS Series Industrial Flow Switch Owner's manual

Type
Owner's manual

Potter IFS Series Industrial Flow Switch

The Potter IFS Series Industrial Flow Switch is a versatile device designed to monitor and control flow in a variety of liquid applications. It is commonly used to start and stop electrically operated equipment based on flow or no-flow conditions.

The IFS Series is available in several models to meet different application requirements. The IFS-1 and IFS-2 models feature one or two SPDT (Form C) switches, respectively, while the IFS-HC-1 and IFS-HC-2 models offer higher current capacity with their SPDT (Form C) switches. The device is constructed with a durable formed sheet metal enclosure with a powdercoat finish for protection against harsh environments.