Unbranded R8GD Installation guide

Type
Installation guide
In stal la tion In struc tions
Horizontal Unit Applications
Warn ing:
Recognize this symbol as an indication of Important Safety Information!
Read all instructions prior to installation.
Disconnect electrical power to the unit before servicing.
Failure to do so can cause electrical shock resulting in personal injury or death.
Improper installation, adjustment, alteration, service or maintenance can cause injury
or property damage. Refer to this manual. For assistance or additional information
consult a qualified installer or service agency.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE
This product is certified to meet
California Title 24, Part 6
Low Leak and FDD requirements
2-5 Ton Pack age Unit Low Leak Mod u lat ing
Economizer w/ W7220A JADE Con trol
OCTOBER 5, 2015, 2015
NEIHEJ06
Before You Begin:
Inspect economizer for shipping damage and correct
parts with list below.
1 - Economizer Assembly w/ Filter
1 - Adaptor Panels (Attached to Economizer)
1 - Wiring Diagram Label
1 - Barometric Relief Hood
1 - Mixed Air Sensor (MAS)
1 - Wire Tie
2 - #10 x 16 x ½” Self-Tapping Screws
10 - #10 x 16 x ½” Type A Screws
BAROMETRIC RELIEF HOOD
ADAPTOR PANEL
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
Note:
Reference Unit Technical Service Literature for application requirements.
Note: For rooftop or other installations that requires
the economizer to be lifted or hoisted, always lift
economizer with the supplied packaging in
place to prevent damage from lifting and rigging
equipment.
2
FORM# 482E-0715 (NEW)
Figure 1
Optional Accessory Kits:
CO
2
Sensor Kit, Wall Mount (920317)
CO
2
Sensor Kit, Duct Mount (920318)
Differential Enthalpy Kit (922431)
HP isolation relay kit (older heat pump models) (922598)
Power Exhaust Kit:
Model # 547843 (208-230v/1 Ph.)
Model # 555580 (208-230v/3 Ph.)
Model # 555581 (460v/3 Ph.)
FRESH AIR HOOD
RETURN DUCT
OPENING
CONTROL AND
FILTER ACCESS
32.875
26.196
22.1879.187 1.835
15.625
0.587
0.789
11.702
J
24.327
13.673
4.809
Figure 2
Unit Weights (lbs)
Shipping Net
183 86
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
WARNING:
Disconnect electrical power to the unit. Failure to do
so can cause electrical shock resulting in personal
injury or death.
RETURN ACCESS PANEL
ECONOMIZER WIRE HARNESS
ROUTING
ELECTRICAL ACCESS PANEL
Step 1
Shutdown unit and disconnect from electrical power.
Figure 3
Step 2:
Take the economizer plug and attach to the unit economizer
plug located inside the return air section above the duct
opening. (Factory jumper plug must first be removed.)
Note: Secure and leave unit jumper plug in the
economizer control panel for later use if the economizer
needs to be bypassed.
Step 2a: (Optional)
Install differential enthalpy control and DCV (CO
2
) sensor
according to that kit's instructions. (See products technical
service literature.)
Step 3:
Slide Economizer over horizontal return opening of the unit.
Secure Economizer using the screws that where provided.
Step 4:
Locate the mixed air sensor (MAS) on the blower deck next
to the blower intake opening using the self-tapping screw
provided. Connect MAS to two (2) prewired red wires in
blower compartment. See Figure 4.
Step 4a: (Optional)
If installed, make sure differential enthalpy control and DCV
(CO
2
) sensor wiring connections are made in accordance
with the kit's instructions.
Step 5:
Attach return duct to economizer and seal to eliminate water
entering the unit using standard construction methods and
materials.
Step 6:
If the barometric relief is to be installed cut a 10" x 20" hole in
the return air duct near Economizer. See Figure 6.
Figure 4
MIXED AIR SENSOR
ECONOMIZER DUCT CONNECTION
UNIT RETURN DUCT
CONNECTION
Figure 5
SUPPLY DUCT
RETURN DUCT
ECONOMIZER
CUT OPENING 10" X 20"
Figure 6
3
Step 7:
Secure barometric relief damper near Economizer over
hole in return air duct using (4) screws provided. See
Figure 7.
Step 8:
Place the adhesive backed wiring diagram on the electrical
access panel by the unit diagram.
Step 9:
Turn power back on to the unit. Setup and configure
economizer. (See Appendix "A" on page 5).
Note to Installer
l When this economizer is used in conjunction with heat
pumps, unit WHITE wire from economizer plug pin #7
MUST be relocated from defrost control board "T1" to
low voltage terminal board "A1".
l When this economizer is used with any 2-5 ton package
unit (Gas/Electric, A/C, or Heat Pump) WITHOUT A
COMMERCIAL THERMOSTAT, the GREEN wire from
economizer plug pin #1 MUST be relocated from low
voltage terminal board "G" to low voltage terminal board
"R" to force dampers to remain in minimum position 100
percent of the time, while in heating mode, to meet the
minimum fresh air requirements. When used in
conjunction with a commercial thermostat, see Note 2
on wiring diagram.
l Some older 2-5T package heat pumps may not be
equipped with a reversing valve isolation relay, required
for use with economizers that have a Jade control
system. Nordyne kit #922598 is required for these
applications.
MAIN TE NANCE
Return Air Filter Replacement is recommended every
30 days. (16 x 16 x 1)
Step 1:
Remove economizer filter access panel. See Figure 9.
Step 2:
Slide filters out (2) and replace with new filters.
Step 3:
Replace filter access panel and secure all screws.
BAROMETRIC RELIEF
Figure 7
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
4
Fresh air filter cleaning is recommended every 3
months.
Step 1:
Remove top section of fresh air hood to access washable
filters. (6 screws) See Figure 10.
Step 2:
Remove filter and clean with water and a mild detergent.
Step 3:
Taking note of "Air Flow Direction" marking on filter frame,
reinstall the filters and fresh air filter access cover,
securing all screws.
Figure 8
Figure 9
Figure 10
FRESH AIR FILTER
ACCESS PANEL
FILTER ACCESS
PANEL
FRESH AIR FILTER
PANEL REMOVED
FILTER ACCESS
PANEL REMOVED
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
5
AP PEN DIX A
User Interface
The user interface consists of an LCD display and a
4-button keypad on the front of the Economizer module.
The LCD is a 16 character by 2 line dot matrix display.
Power Up Cy cle
All setpoints and advanced settings are restored after any
power loss (a power loss is assumed if voltage falls below
18 Vac). Normal operation is restored when power returns
above 18 Vac.
Ini tial Menu Dis play
On initial startup, Honeywell displays on the first line and
Economizer W7220 on the second line. After a brief
pause, the revision of the software appears on the first line
(second line is blank). It then displays W7220 on the first
line and STATUS on the second line.
l Press the 8 button (Enter) to display the first item in the
currently displayed menu.
l Use the p and q buttons to scroll to the desired
parameter.
l Press the 8 button (Enter) to display the value of the
currently displayed item.
l Press the p button to increase (change) the displayed
parameter value.
a
l Press the q button to decrease (change) the displayed
parameter value.
a
l Press the 8 button to accept the displayed value and
store it in non-volatile RAM.
l When the value is accepted, CHANGE STORED is
displayed on the LCD.
l Press the 8 button (Enter) to return to the current menu
parameter.
l Press the Ó button (MenuUp/Exit) to return to the
previous menu.
a
When values are displayed, pressing and holding the p or
q button causes the display to automatically increment.
Menu Struc ture
The following tables illustrate the complete hierarchy of
menus and parameters for the JADE™ Economizer
system.
The Menus in display order are:
l STATUS
l SETPOINTS
l SYSTEM SETUP
l ADVANCED SETUP
l CHECKOUT
l ALARMS
IMPORTANT
Your menu parameters may be different depending on
your configuration.
For example if you do not have a DCV (CO2) sensor, then none of
the DCV parameters appear and only MIN POS will display. If you
have a CO2 sensor, the DCV MIN and DCV MAX will appear AND
if you have 2 speed fan DCV MIN (high and low speed) and DCV
MAX (high and low speed will appear).
SETUP AND CON FIG U RA TION
Before being placed into service, the JADE™ Economizer
module must be setup and configured for the installed
system. Use the System Setup menu, the Advanced Setup
menu (if necessary), and the Setpoints menu to
accomplish this.
Time-out and Screen saver
When no buttons have been pressed for 10 minutes, the
LCD displays a screen saver, which cycles through the
Status items. Each Status items displays in turn and cycles
to the next item after 5 seconds.
Figure 11
2 LINE LCD
MENU UP (EXIT) BUTTON
SELECT (ENTER) BUTTON
SCROLL (UP/DOWN) BUTTON
Key pad
The four navigation buttons illustrated in Figure 11 are
used to scroll through the menus and menu items, select
menu items, and to change parameter and configuration
settings.
Us ing the Key pad with Menus
To use the keypad when working with menus:
l Press the p button to move to the previous menu.
l Press the q button to move to the next menu.
l Press the 8 button (Enter) to display the first item in the
currently displayed menu.
l Press the Ó button (Menu up) to exit a menu’s item and
return to the list of menus.
Us ing the Key pad with Set tings and Pa ram e ters
To use the keypad when working with Setpoints, System
and Advanced Settings, Checkout tests, and Alarms:
l Navigate to the desired menu.
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
6
AP PEN DIX A
Pa ram e ter
Pa ram e ter
De fault
Value
Pa ram e ter
Range and
In cre ment
a
Notes
ECON AVAIL NO YES/NO
YES = econ o miz ing avail able; the sys tem can use Out door Air for free cool ing when re quired.
ECONOMIZING NO YES/NO
YES = Out door Air be ing used for 1st stage cool ing.
OCCUPIED NO YES/NO
YES = OCC signal received from space thermostat or unitary controller.
YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC.
HEAT PUMP COOL COOL/HEAT
Dis plays COOL or HEAT when SYS TEM is set to heat pump (non-conventional)
COOL Y1-IN OFF ON/OFF
Y1-I sig nal from space ther mo stat in put for cool ing stage 1 or heat pump heat ing stage 1.
ON = 24 Vac on ter mi nal Y1-I
OFF = 0 Vac on ter mi nal Y1-I
COOL Y1-OUT OFF ON/OFF
Cool Stage 1 Re lay Out put to stage 1 me chan i cal cool ing (Y1-OUT ter mi nal).
COOL Y2-IN OFF ON/OFF
Y2-I sig nal from space ther mo stat in put for sec ond stage cool ing or heat pump heat ing stage
2.
ON = 24 Vac on ter mi nal Y2-I
OFF = 0 Vac on ter mi nal Y2-I
COOL Y2-OUT OFF ON/OFF
Cool Stage 2 Re lay Out put to me chan i cal cool ing (Y2-OUT ter mi nal).
MA TEMP _ _._ºF -40 to 150ºF
Dis plays value of mea sured mixed air from MAT sen sor.
Dis plays -.- if not con nected, short, or out-of-range.
DA TEMP _ _._ºF -40 to 150ºF
Dis plays when Dis charge Air Sylk Bus sen sor is con nected and dis plays mea sured dis charge
air tem per a ture. Dis plays -.-°F if sen sor sends in valid value, if not con nected, short or
out-of-range.
OA TEMP _ _._ ºF -40 to 140ºF
Dis plays mea sured value of out door air tem per a ture. Dis plays -°F if sen sor sends in valid
value, if not con nected, short or out-of-range.
OA HUM _ _% 0 to 100%
Displays measured value of outdoor humidity from OA Sylkbus sensor. Displays -% if not
connected, short, or out-of-range.
RA TEMP _ _._ºF 0 to 140ºF
If field in stalled Dual Enthalpy sen sor is con nected, dis plays mea sured value of re turn air
tem per a ture. Dis plays -°F if sen sor sends in valid value, if not con nected, short or out-of-range.
RA HUM _ _% 0 to 100%
If field in stalled Dual Enthalpy sen sor is con nected, dis plays mea sured value of re turn air
hu mid ity. Dis plays -% if sen sor sends in valid value, if not con nected, short or out-of-range.
IN CO
2
_ _ _ ppm
"0 to 2000
(3500) ppm"
If field in stalled CO
2
sen sor is con nected, dis plays value of mea sured CO
2
. In valid if not
con nected, short or out-of-range. May be ad justed in Ad vanced menu by Zero off set and Span.
DCV STATUS n/a n/a
If field in stalled CO
2
sen sor is con nected, dis plays ON if above setpoint and OFF if be low
setpoint.
DAMPER OUT _ _% 0 to 100%
Dis plays out put po si tion to the damper ac tu a tor. When used with Honeywell com mu ni cat ing
ac tu a tor the damper out is in XX.X%
ACT POS. n/a 0 to 100%
Dis plays ac tual po si tion of ac tu a tor.
ACT COUNT n/a 1 to 65,535
Dis plays num ber of times ac tu a tor has cy cled. 1 Cy cle equals 180° of move ment in any
di rec tion.
ACTUATOR n/a OK/Alarm
Dis plays Er ror on ALARM MENU if volt age or torque is be low ac tu a tor range.
EXH1 OUT OFF ON/OFF
Output of EXH1 terminal. Displays ON when damper position reaches programmed
percentage setpoint.
ON = 24 Vac Output; OFF = No Output.
EXH2 OUT OFF ON/OFF
Output of AUX1 O terminal Displays ON when damper position reaches programmed
percentage setpoint
ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O = EXH2
ERV OFF ON/OFF
Output of AUX1 O terminal, ON = 24 Vac Output, OFF = No
Output; displays only if AUX1 O = ERV
MECH COOL ON 0 0, 1, or 2
Displays number of mechanical cooling stages that are active.
FAN SPEED n/a LOW/HIGH
Dis plays speed of fan on a 2-speed fan unit
W (HEAT IN) n/a ON/OFF
Dis plays sta tus of heat on a 2-speed fan unit.
a
When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
STATUS MENU
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
7
AP PEN DIX A
SETPOINTS MENU
Parameter
Parameter
Default
Value
Parameter
Range and
Increment
a
Notes
MAT SET 53ºF
38 to 70ºF;
increment by 1
The economizer will modulate the OA damper to maintain the mixed air temperature at the
setpoint.
LOW T LOCK 32ºF
-45 to 80ºF;
increment by 1
Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on.
Commonly referred to as the Compressor lockout. At or below the setpoint the Y1-O and Y2-O
will not be energized on the controller.
DRYBLB SET 63ºF
48 to 80ºF;
increment by 1
Setpoint determines where the economizer will assume outdoor air temperature is good for
free cooling; e.g.; at 63 ºF setpoint unit will economizer at 62 ºF and below and not economize
at 64 ºF and above. There is a a 2 ºF deadband.
ENTH CURVE ES3
ES1, ES2, ES3,
ES4, or ES5
Does not dis play if a field in stalled Dual Enthalpy kit is con nected. Enthalpy bound ary "curves"
for econ o miz ing us ing sin gle enthalpy com par i son be tween out door air enthalpy and setpoint.
DCV SET 1100 ppm
500 to 2000 ppm
increment by 100
Dis plays ONLY if field in stalled CO
2
sen sor is con nected. Setpoint for De mand Con trol
Ven ti la tion of space. Above the setpoint, the OA damp ers will mod u late open to bring in
ad di tional OA to main tain a space ppm level be low the setpoint.
MIN POS 2.8 V 2 to 10 Vdc
Dis plays ONLY if a CO
2
sen sor is NOT con nected.
With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan)
set tings are re quired. De fault for MIN POS L is 3.2V and MIN POS H is 2.8V
VENTMAX 2.8 V
2 to 10 Vdc
Displays only if a field installed CO
2
sensor is connected. Used for Vbz (ventilation max cfm)
setpoint. VENTMAX is the same setting as MIN POS would be if you did not have the CO
2
sensor.
100 to 9990 cfm
increment by 10
If OA, MA, RA and CO
2
sen sors are con nected and DCV CAL EN ABLE is set to AUTO mode,
the OA damp ers are con trolled by CFM and dis plays from 100 to 9990 cfm.
2 to 10 Vdc
With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H (high speed fan)
set tings are re quired. De fault for VENTMAX L is 3.2V and VENTMAX H is 2.8V.
VENTMIN 2.25 V
2 to 10 Vdc
Dis plays only if field in stalled CO
2
sen sor is con nected. Used for Va (ven ti la tion min cfm)
setpoint. This is the ven ti la tion re quire ment for less than max i mum oc cu pancy of the space.
100 to 9990 cfm
increment by 10
If OA, MA, RA and CO
2
sen sors are con nected and DCV CAL EN ABLE is set to AUTO mode,
the OA damp ers are con trolled by CFM and dis plays from 100 to 9990 cfm.
2 to 10 Vdc
With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H (high speed fan)
set tings are re quired. De fault for VENTMIN L is 2.5V and VENTMIN H is 2.25V.
ERV OAT SP
b
32ºF
0 to 50ºF;
increment by 1
Only when AUX1 O = ERV
EXH1 SET 50%
0 to 100%;
increment by 1
Setpoint for OA damper po si tion when ex haust fan 1 is pow ered by the economizer. With
2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) set tings are re quired.
De fault for Exh1 L is 65% and Exh1 H is 50%.
EXH2 SET 75%
0 to 100%;
increment by 1
Setpoint for OA damper position when exhaust fan 2 is powered by the economizer. Only used
when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) settings are
required. Default for Exh2 L is 80% and Exh2 H is 75%.
a
When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
b
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized. In the Heating mode the ERV terminal will be
energized when the OA is below the ERV OAT setpoint in the setpoint menu.
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
8
AP PEN DIX A
SYSTEM SETUP MENU
Parameter
Parameter
Default
Value
Parameter
Range and
Increment
a
Notes
INSTALL 01/01/2011
Display order = MM/DD/YY. Setting order = DD, MM, then YY.
UNITS DEG ºF ºF or ºC
Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT
CONV
CONV
HP
CONV = conventional.
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump input from thermostat or
controller.
AUX2 I N/A
Shutdown (SD)
Heat (W1)
HP(O)
HP(B)
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must pro-gram CONV mode for W. Shutdown
is not available in the two-speed fan mode.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
FAN TYPE 1 speed
1 speed/
2 speed
Sets economizer controller for operation of 1 speed or 2 speed supply fan. The controller
does not control the fan but positions the OA and RA dampers to the heating or cooling
mode.
NOTE: 2-speed fan option also needs Heat (W1) pro-grammed in AUX 2 In.
FAN CFM 5000cfm
100 to 15000
cfm;
increment by
100
This is the capacity of the RTU. The value is found on the label from the RTU manufacturer.
The cfm of the fan is only used with DCV CAL ENABLE AUO
AUX1 OUT NONE
NONE
ERV
EXH2
SYS
l NONE = not configured (output is not used)
l ERV= Energy Recovery Ventilator
l EXH2 = second damper position relay closure for second exhaust fan.
l SYS = use output as an alarm signal
OCC INPUT
INPUT or
ALWAYS
When using a setback thermostat with occupancy out (24 Vac), the 24 Vac is input "INPUT"
to the OCC terminal. If no occupancy output from the thermostat then change program to
"ALWAYS" OR add a jumper from terminal R to OCC terminal.
FACTORY
DEFAULT
NO NO or YES
Resets all set points to factory defaults when set to YES. LCD will briefly flash YES and
change to NO but all parameters will change to factory default values.
a
When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
9
AP PEN DIX A
Parameter
Parameter
Default
Value
Parameter
Range and
Increment
a
Notes
MA LO SET 45ºF
35 to 55ºF
increment by 1º
Temp to activate Freeze Protection (close damper or modulate to MIN POS if temp falls
below set value)
FREEZE POS CLO
CLO
MIN
Damper position when freeze protection is active (closed or MIN POS).
CO
2
ZERO
0 ppm
0 to 500 ppm
increment by 10
Displays only if field installed CO
2
sensor is connected. CO
2
ppm level to match CO
2
sensor
start level.
CO
2
SPAN
2000 ppm
1000 to 3000
ppm;
increment by 50
Displays only if field installed CO
2
sensor is connected. CO2 ppm span to match CO2
sensor; e.g.; 500-1500 sensor output would be 500 CO2 zero and 1000 CO2 span. See note
on page 6 for C7632 CO2 sensor.
STG3 DLY 2.0h
0 min, 5 min, 15
min, then 15
min intervals.
Up to 4h or OFF
Delay after stage 2 for cool has been active. Turns on 2nd stage of mechanical cooling when
economizer is 1st stage call and mechanical cooling is 2nd stage call. Allows three stages of
cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling.
SD DMPR POS CLO
CLO
OPN
Indicates shutdown signal from space thermostat. When controller receives 24 Vac input on
the SD terminal in conventional mode, the OA damper will open if programmed for OPN and
OA damper will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1,
etc. will shut off.
DCVCAL ENA MAN
MAN (manual)
AUTO
Turns on the DCV automatic control of the dampers. Resets ventilation based on the RA,
OA and MA sensor conditions. Requires all sensors (RA, OA, MA and CO2).
This operation is not operable with a 2-speed fan unit.
MAT T CAL 0.0 F° +/-2.5F°
Allows for the operator to adjust for an out of calibration mixed air temperature sensor.
OAS T CAL 0.0F° +/-2.5F°
Allows for the operator to adjust for an out of calibration outdoor air temperature sensor.
OAS H CAL 0% RH +/-10% RH
Allows for the operator to adjust for an out of calibration outdoor air humidity sensor.
RA T CAL 0.0F° +/-2.5F°
If field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an
out of calibration temperature sensor.
RA H CAL 0% RH +/-10% RH
If field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an
out of calibration humidity sensor.
DA T CAL 0.0 F° +/-2.5F°
Allows for the operator to adjust for an out of calibration Discharge Air Sylk Bus temperature
sensor.
2SP FAN DELAY 5 Minutes
0 to 20 minutes
in 1 minute
increments.
When in economizing mode this is the delay for the high speed fan to try to satisfy the call
for second stage cooling before the first stage mechanical cooling is enabled.
a
When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
ADVANCE SETUP MENU
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
10
AP PEN DIX A
CHECKOUT MENU
c
Parameter
Parameter
Default Value
Parameter Range
and Increment
a
Notes
DAMPER VMIN-HS n/a n/a
Positions damper to VMIN position
DAMPER VMAX-HS
n/a n/a
Positions damper to VMAX position.
DAMPER VMAX-LS
With 2-speed fan units the damper will position to VMAX low speed fan.
DAMPER OPEN n/a n/a
Positions damper to the full open position. Exhaust fan contacts enable during the
DAMPER OPEN test. Make sure you pause in this mode to allow for exhaust contacts
to energize due to the delay in the system.
DAMPER CLOSE n/a n/a
Positions outside air damper to the fully closed position.
CONNECT Y1-O n/a n/a
Closes the Y1-O relay (Y1-O). See CAUTION on below
CONNECT Y2-O n/a n/a
Closes the Y2-O relay (Y2-O). See CAUTION on below
CONNECT AUX1-O n/a n/a
Energizes the AUX1-O output. If AUX1-O setting is:
l NONE – no action taken
l ERV – 24 Vac out. Turns on or signals an ERV that the conditions are not good
for economizing but are good for ERV operation.
b
l SYS – 24 Vac out. Issues a system alarm.
CONNECT EXH1 n/a n/a
Closes the power exhaust fan 1 relay (EXH1)
a
When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
b
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized. In the Heating mode the
ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
c
After 10 minutes without a command or mode change, the controller will change to normal operation.
CHECK OUT
Inspect all wiring connections at the Economizer module’s
terminals, and verify compliance with the installation wiring
diagrams.
For checkout, review the Status of each configured
parameter and perform the Checkout tests.
Note: See "Interface Overview" on page 5. for
information about menu navigation and use of
the keypad.
Note: If power goes below 18 Vac, the W7220
controller module assumes a power loss and
the 5 minute power up delay will become
functional when power returns above 18 Vac.
a
All settings are stored in non-volatile flash memory.
Sta tus
Use the Status Menu to check the parameter values for
the various devices and sensors configured.
Checkout Tests
Use the Checkout Menu to test the damper operation and
any configured outputs. Only items that are configured are
shown in the Checkout menu.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using
the p and q buttons.
2. Press the 8 button to select the item.
3. RUN? appears on the display.
4. Press the 8 button to start the test.
5. The unit pauses and then displays TEST RUNNING.
6. Press the button Ó (Menu up) to end the test (e.g. turn
off the relay). Test stops automatically after 10 minutes
without a command or mode change, and will resume
normal operation.
The checkout tests can all be performed at the time of
installation or any time during the operation of the system
as a test that the system is operable.
WARNING:
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or
making wiring connections, to prevent electrical shock or
equipment damage.
If any wiring changes are required, first be sure to remove
power from the Economizer module before starting work.
Pay particular attention to verifying the power connection
(24 Vac).
Power Up
After the module is mounted and wired, apply power.
Power Up De lay
Upon power up (or after a power outage or brownout), the
W7220 controller module begins a 5 minute power up
delay before enabling mechanical cooling.
Power Loss (Out age or Brown out)
All setpoints and advanced settings are restored
a
after any
power loss or interruption.
CAUTION
Equipment damage may result.
Be sure to allow enough time for compressor startup and
shutdown between checkout tests so that you do not
short-cycle the compressors.
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
11
AP PEN DIX A
ALARM MENU
Alarms
The Economizer module provides alarm messages that display on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before checking for alarms. This allows time for all the
configured devices (e.g. sensors, actuator) to become operational. The exception is the MA sensor which
will alarm immediately.
If one or more alarms are present and there has been no keypad activity for at least 5 minutes, the Alarms menu displays
and cycles through the active alarms. You can also navigate to the Alarms menu at any time.
Clear ing Alarms
Once the alarm has been identified and the cause has been removed (e.g. replaced faulty sensor), the alarm can be
cleared from the display. To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the 8 button.
3. ERASE? displays.
4. Press the 8 button.
5. ALARM ERASED displays.
6. Press the button Ó (MenuUp/Exit) to complete the action and return to the previous menu.
NOTE: If an alarm still exists after you clear it, it redisplays within 5 seconds.
Parameter
Parameter Default
Value
Parameter Range
and Increment
a
Notes
MA T SENS ERR n/a n/a
Alarms display only when they are active. The menu title "ALARMS (_)"includes
the number of active alarms in parenthesis ().
CO
2
SENS ERR n/a n/a
OA T SENS ERR n/a n/a
DA ENTHL ERR n/a n/a
SYS ALARM n/a n/a
When AUX1 O is set to SYS and there is any alarm (e.g., failed sensors, etc.), the
AUX1 O terminal has 24 Vac out.
ACT UNDER V n/a n/a
Voltage received by Actuator is above expected range
ACT OVER V n/a n/a
Voltage received by Actuator is below expected range
ACT STALLED n/a n/a
Actuator stopped before achieving commanded position
a
When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
12
AP PEN DIX A
Dry Bulb Op er a tion No DCV (CO2 sen sor) - 1 Speed Fan.
DCV
OA Good to
econ o mize?
Y1-I Y2-I FAN SPD Y1-O Y2-O Oc cu pied Un oc cu pied
None No
Off Off High 0-v/Off 0-v/Off
MIN POS Closed
On Off High 24-v/On 0-v/Off
MIN POS Closed
On On High 24-v/On 24-v/On
MIN POS Closed
None Yes
Off Off High 0-v/Off 0-v/Off
MIN POS Closed
On Off High 0-v/Off 0-v/Off
MIN POS to Full-Open Closed to Full-Open
On On High 24-v/On 0-v/Off
a
MIN POS to Full-Open Closed to Full-Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
Dry Bulb Op er a tion With DCV (CO2 sen sor) - 1 Speed Fan.
DCV
OA Good to
econ o mize?
Y1-I Y2-I FAN SPD Y1-O Y2-O Oc cu pied Un oc cu pied
Below
CO2 set
No
Off Off High 0-v/Off 0-v/Off
VENTMIN Closed
On Off High 24-v/On 0-v/Off
VENTMIN Closed
On On High 24-v/On 24-v/On
VENTMIN Closed
Yes
Off Off High 0-v/Off 0-v/Off
VENTMIN Closed
On Off High 0-v/Off 0-v/Off
VENTMIN to Full-Open Closed to Full-Open
On On High 24-v/On 0-v/Off
a
VENTMIN to Full-Open Closed to Full-Open
Above
CO2 set
No
Off Off High 0-v/Off 0-v/Off
VENTMIN to VENTMAX Closed
On Off High 24-v/On 0-v/Off
VENTMIN to VENTMAX Closed
On On High 24-v/On 24-v/On
VENTMIN to VENTMAX Closed
Yes
Off Off High 0-v/Off 0-v/Off
VENTMIN to VENTMAX Closed
On Off High 0-v/Off 0-v/Off
VENTMIN to Full-Open Closed to Full-Open
On On High 24-v/On 0-v/Off
a
VENTMIN to Full-Open Closed to Full-Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
Enthalpy Op er a tion No DCV (CO2 sen sor) - 1 Speed Fan.
DCV
OA Good to
econ o mize?
Y1-I Y2-I FAN SPD Y1-O Y2-O Oc cu pied Un oc cu pied
None No
Off Off High 0-v/Off 0-v/Off
MIN POS Closed
On Off High 24-v/On 0-v/Off
MIN POS Closed
On On High 24-v/On 24-v/On
MIN POS Closed
None Yes
Off Off High 0-v/Off 0-v/Off
MIN POS Closed
On Off High 0-v/Off 0-v/Off
MIN POS to Full-Open Closed to Full-Open
On On High 24-v/On 0-v/Off
a
MIN POS to Full-Open Closed to Full-Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
SEQUENCE OF OPERATION
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
13
AP PEN DIX A
Dry Bulb Op er a tion No DCV (CO2 sen sor) - 2 Speed Fan.
DCV
OA Good to
econ o mize?
Y1-I Y2-I FAN SPD Y1-O Y2-O Oc cu pied Un oc cu pied
None No
Off Off Low 0-v/Off 0-v/Off
MIN POS L Closed
On Off Low 24-v/On 0-v/Off
MIN POS L Closed
On On High 24-v/On 24-v/On
MIN POS H Closed
None Yes
Off Off Low 0-v/Off 0-v/Off
MIN POS L Closed
On Off Low 0-v/Off 0-v/Off
MIN POS L to Full-Open Closed to Full-Open
On On High
DELAY
b
24-v/On
0-v/Off
a
MIN POS H to Full-Open Closed to Full-Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Dry Bulb Op er a tion With DCV (CO2 sen sor) - 2 Speed Fan.
DCV
OA Good to
econ o mize?
Y1-I Y2-I FAN SPD Y1-O Y2-O Oc cu pied Un oc cu pied
Below set
No
Off Off Low 0-v/Off 0-v/Off
VENTMIN L Closed
On Off Low 24-v/On 0-v/Off
VENTMIN L Closed
On On High 24-v/On 24-v/On
VENTMIN H Closed
Yes
Off Off Low 0-v/Off 0-v/Off
VENTMIN L Closed
On Off Low 0-v/Off 0-v/Off
VENTMIN L to Full-Open Closed to Full-Open
On On High 24-v/On 0-v/Off
a
VENTMIN H to Full-Open Closed to Full-Open
Above set
No
Off Off Low 0-v/Off 0-v/Off
VENTMIN L to VENTMAX Closed
On Off Low 24-v/On 0-v/Off
VENTMIN L to VENTMAX Closed
On On High 24-v/On 24-v/On
VENTMIN H to VENTMAX Closed
Yes
Off Off Low 0-v/Off 0-v/Off
VENTMIN L to VENTMAX Closed
On Off Low 0-v/Off 0-v/Off
VENTMIN L to Full-Open Closed to Full-Open
On On High
DELAY
b
24-v/On
0-v/Off
a
VENTMIN H to Full-Open Closed to Full-Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Enthalpy Op er a tion With DCV (CO2 sen sor) - 1 Speed Fan.
DCV
OA Good to
econ o mize?
Y1-I Y2-I FAN SPD Y1-O Y2-O Oc cu pied Un oc cu pied
Below set
No
Off Off High 0-v/Off 0-v/Off
VENTMIN Closed
On Off High 24-v/On 0-v/Off
VENTMIN Closed
On On High 24-v/On 24-v/On
VENTMIN Closed
Yes
Off Off High 0-v/Off 0-v/Off
VENTMIN Closed
On Off High 0-v/Off 0-v/Off
VENTMIN to Full-Open Closed to Full-Open
On On High 24-v/On 0-v/Off
a
VENTMIN to Full-Open Closed to Full-Open
Above set
No
Off Off High 0-v/Off 0-v/Off
VENTMIN to VENTMAX Closed
On Off High 24-v/On 0-v/Off
VENTMIN L to VENTMAX Closed
On On High 24-v/On 24-v/On
VENTMIN H to VENTMAX Closed
Yes
Off Off High 0-v/Off 0-v/Off
VENTMIN L to VENTMAX Closed
On Off High 0-v/Off 0-v/Off
VENTMIN to Full-Open Closed to Full-Open
On On High
DELAY (b)
24-v/On
0-v/Off
a
VENTMIN to Full-Open Closed to Full-Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
14
AP PEN DIX A
Enthalpy Op er a tion No DCV (CO2 sen sor) - 2 Speed Fan.
DCV
OA Good to
econ o mize?
Y1-I Y2-I FAN SPD Y1-O Y2-O Oc cu pied Un oc cu pied
NO CO2
SENSOR
No
Off Off Low 0-v/Off 0-v/Off
MIN POS L Closed
On Off Low 24-v/On 0-v/Off
MIN POS L Closed
On On High 24-v/On 24-v/On
MIN POS H Closed
Yes
Off Off Low 0-v/Off 0-v/Off
MIN POS L Closed
On Off Low 0-v/Off 0-v/Off
MIN POS L to Full-Open Closed to Full-Open
On On High
DELAY
b
24-v/On
0-v/Off
a
MIN POS H to Full-Open Closed to Full-Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Dry Bulb Op er a tion With DCV (CO2 sen sor) - 2 Speed Fan.
DCV
OA Good to
econ o mize?
Y1-I Y2-I FAN SPD Y1-O Y2-O Oc cu pied Un oc cu pied
Below set
No
Off Off Low 0-v/Off 0-v/Off
VENTMIN L Closed
On Off Low 24-v/On 0-v/Off
VENTMIN L Closed
On On High 24-v/On 24-v/On
VENTMIN H Closed
Yes
Off Off Low 0-v/Off 0-v/Off
VENTMIN L Closed
On Off Low 0-v/Off 0-v/Off
VENTMIN L to Full-Open Closed to Full-Open
On On High 24-v/On 0-v/Off
a
VENTMIN H to Full-Open Closed to Full-Open
Above set
No
Off Off Low 0-v/Off 0-v/Off
VENTMIN L to VENTMAX Closed
On Off Low 24-v/On 0-v/Off
VENTMIN L to VENTMAX Closed
On On High 24-v/On 24-v/On
VENTMIN H to VENTMAX Closed
Yes
Off Off Low 0-v/Off 0-v/Off
VENTMIN L to VENTMAX Closed
On Off Low 0-v/Off 0-v/Off
VENTMIN L to Full-Open Closed to Full-Open
On On High
DELAY
b
24-v/On
0-v/Off
a
VENTMIN H to Full-Open Closed to Full-Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
15
AP PEN DIX A
Single Enthalpy and Dual Enthalpy High Limit Curves
Enthalpy
Curve
Temp.
Dry-Bulb (°F)
Temp.
Dewpoint (°F)
Enthalpy
(btu/lb/da)
Point P1 Point P2
Temp. °F Humidity %RH Temp. °F Humidity %RH
ES1 80.0 60.0 28.0 80.0 36.8 66.3 80.1
ES2 75.0 57.0 26.0 75.0 39.6 63.3 80.0
ES3 70.0 54.0 24.0 70.0 42.3 59.7 81.4
ES4 65.0 51.0 22.0 65.0 44.8 55.7 84.2
ES5 60.0 48.0 20.0 60.0 46.9 51.3 88.5
HL 86.0 66.0 32.4 86.0 38.9 72.4 80.3
Enthalpy Set tings
When the OA temperature, enthalpy and dew point are
below the respective setpoints, the Outdoor Air can be
used for economizing. Fig. 18 shows the new single
enthalpy boundaries in the W7220. There are 5
boundaries (setpoints ES1 through ES5), which are
defined by dry bulb temperature, enthalpy and dew point.
Refer to Table above for the ENTH CURVE setpoint
values.
To use enthalpy the W7220 must have a C7400S Sylkbus
sensor for OA. The W7220 calculates the enthalpy and
dew point using the OA temperature and humidity input
from the OA sensor. When the OA temperature, OA
humidity and OA dew point are all below the selected
boundary, the economizer sets the economizing mode to
YES, economizing is available.
When conditions are above the selected boundary, the
conditions are not good to economize and the mode is set
to NO.
Figure ## shows the 5 current boundaries. There is also a
high limit boundary for differential enthalpy. The high limit
boundary is ES1 when there are no stages of mechanical
cooling energized and HL when a compressor stage is
energized.
The table above provides the values for each boundary
limit.
Two-Speed Fan Op er a tion
The later versions of the W7220 Jade controller have the
capability to work with a system using a 2-speed supply fan
The W7220 does not control the supply directly but uses
the following input status to determine the speed of the
supply fan and controls the OA damper to the required
position.
State Fan Speed
OCC Low
Y1 Low
Y2 High
W High
The W (heating mode) is not controlled by the W7220 but it
requires the status to know where to position the OA
damper for minimum position for the fan speed.
The 2 speed fan delay is available when the system is
programmed for 2 speed fan (in the System Setup menu
item). The 2 speed fan delay is defaulted to 5 minutes and
can be changed in the Advanced Setup menu item. When
the unit has a call for Y1 In and in the free cooling mode and
there is a call for Y2 In, the 2-speed fan delay starts and the
OA damper will modulate 100% open, the supply fan
should be set to high speed by the unit controller. After the
delay one of two actions will happen:
l The Y2 In call will be satisfied with the damper 100%
open and fan on high speed and the call will turn off
OR
l If the call for additional cooling in the space has not been
satisfied then the first stage of mechanical cooling will
be enabled through Y1 Out or Y2 Out.
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
16
AP PEN DIX A
Figure 12
Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS3103J or MS3105J communicating actuators.
Figure 13
2-position actuator
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
17
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
18
INSTALLATION
INSTRUCTION
HORIZONTAL ECONOMIZER #562534
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
19
HORIZONTAL ECONOMIZER
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
Notes:
1. Unit wiring shown as reference only. Check unit wiring for actual unit wiring.
2. Standard connection shown. When this economizer is used in conjunction with a commercial thermostat that has an OCC
connection, unplug white wire with insulated terminal from pin # 1 and plug into white wire from pin # 7. Connect the
thermostat OCC output to A1 terminal on the unit low voltage terminal board. (On older models without A1 terminal
connection a field supplied wire can be routed and connected to the unplugged white wire from Pin # 1 to JADE OCC)
3. Economizer pin location S1-2 connected to the following:
Package Gas/Electrics "W1" or Gas valve
Package Air Conditioners "W1"
Package Heat Pumps "O" for Cooling mode of operation
4. For mechanical cooling (compressor) to energize during economizer cooling mode of operation, a thermostat "Y2" call must
be present. A 2 stage cooling thermostat is required for this operation.
5. See unit low voltage wiring instruction changes required for economizers equipped with the Honeywell W7220 JADE control
module and Page 4 of these instructions.
WIRE COLOR CODE
BLK Black BLU Blue
BRN Brown GRN Green
GRY Gray ORG Orange
PNK Pink RED Red
TAN Tan VIO Violet
WHT White YEL Yellow
COMPONENT CODE
Re vi sion Change Date
HARNESS ENDS AT P1
Date: August 6, 2015
Su per sedes:
Drawn by: MGL
Unit #: 47-396-06
Di a gram#: 4739606W
Ap proved by:
Nordyne# Honey well# Description
622754 MS3105J3030 Damper Actuator 24v
626621 W7220A1000 Logic Module
626622 C7400S1000 Fresh Air Enthalpy Sensor
626623 C7250A1001 Mixed Air Temperature Sensor
---------- P1 Male Interface Unit Plug
---------- S1 Male Interface Unit Plug
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Unbranded R8GD Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI