ABB COM600 series 5.0 Technical Reference Manual

Type
Technical Reference Manual
—
COM600 series 5.0
Slave Protocols (Ethernet) and Applications
Technical Reference Manual
Contents:
1. About this manual .................................................................................. 7
1.1. Copyright ........................................................................................ 7
1.2. Disclaimer ..................................................................................... 7
1.3. Conformity ..................................................................................... 8
1.4. Trademarks .................................................................................... 8
1.5. General information ....................................................................... 8
1.6. Document conventions .................................................................. 8
1.7. Use of symbols .............................................................................. 9
1.8. Terminology .................................................................................. 10
1.9. Abbreviations ............................................................................... 11
1.10. Related documents ...................................................................... 12
1.11. Document revisions ..................................................................... 12
2. Introduction ........................................................................................... 13
2.1. General information about the COM600 series ........................... 13
2.2. COM600 product series variants and rationale ........................... 13
2.3. Functional overview ..................................................................... 14
3. IEC 61850 Proxy server ........................................................................ 16
3.1. ACSI conformance statement ...................................................... 16
3.1.1. ACSI conformance statement ....................................... 16
3.1.2. ACSI basic conformance statement .............................. 16
3.1.3. ACSI models conformance statement ......................... 17
3.1.4. ACSI service conformance statement ........................... 18
3.2. SCL conformance ........................................................................ 22
3.2.1. SCL conformance statement ........................................ 22
3.3. PICS - protocol conformance statement ...................................... 22
3.3.1. Profile conformance ...................................................... 22
3.3.2. MMS Conformance ....................................................... 23
4. IEC 104 OPC slave ................................................................................ 25
4.1. About this section ......................................................................... 38
4.2. IEC 61850 data modeling ............................................................ 25
4.2.1. General information about IEC 61850 data modeling .... 25
4.2.2. Single point status (SPS) .............................................. 25
4.2.3. Double point status (DPS) ............................................ 26
4.2.4. Integer controlled step position information (ISC) ......... 32
4.2.5. Enumerated Status (ENS) ............................................ 39
4.2.6. Protection activation information (ACT) ........................ 27
4.2.7. Directional protection activation information (ACD) ...... 27
4.2.8. Binary counter reading (BCR) ....................................... 28
4.2.9. Measured value (MV) .................................................... 28
4.2.10. Complex measured value (CMV) .................................. 29
3
COM600 series 5.01MRS758692
Slave Protocols (Ethernet) and Applications Technical
Reference Manual
Issued: 24.5.2017
Version: A/24.5.2017
4.2.11. WYE .............................................................................. 29
4.2.12. Delta (DEL) ................................................................... 30
4.2.13. Controllable single point (SPC) ..................................... 30
4.2.14. Controllable double point (DPC) ................................... 30
4.2.15. Controllable integer status (INC) ................................... 31
4.2.16. Controllable Enumerated Status (ENC) ........................ 31
4.2.17. Binary controlled step position information (BSC) ........ 32
4.2.18. Integer controlled step position information (ISC) ......... 32
4.2.19. Analogue set point (APC) ............................................. 32
4.3. Status codes ................................................................................ 33
4.3.1. Introduction ................................................................... 33
4.3.2. Link layer status codes ................................................. 33
4.3.3. Application layer status codes ...................................... 33
4.4. Attributes ...................................................................................... 34
4.4.1. General information about attributes ............................ 34
4.4.2. Client attributes ............................................................. 35
4.4.3. Channel attributes ......................................................... 35
4.4.4. Device attributes ........................................................... 36
5. DNP3 LAN/WAN OPC slave ................................................................. 38
5.1. About this section ......................................................................... 38
5.2. IEC 61850 data modeling ............................................................ 38
5.2.1. General information about IEC 61850 data modeling .... 38
5.2.2. Single point status (SPS) .............................................. 38
5.2.3. Double point status (DPS) ............................................ 39
5.2.4. Integer controlled step position information (ISC) ......... 45
5.2.5. Enumerated Status (ENS) ............................................ 39
5.2.6. Protection activation information (ACT) ........................ 40
5.2.7. Directional protection activation information (ACD) ...... 40
5.2.8. Binary counter reading (BCR) ....................................... 41
5.2.9. Measured value (MV) .................................................... 41
5.2.10. Complex measured value (CMV) .................................. 41
5.2.11. WYE .............................................................................. 41
5.2.12. Delta (DEL) ................................................................... 42
5.2.13. Controllable single point (SPC) ..................................... 43
5.2.14. Controllable double point (DPC) ................................... 43
5.2.15. Controllable integer status (INC) ................................... 44
5.2.16. Controllable Enumerated Status (ENC) ........................ 44
5.2.17. Binary controlled step position information (BSC) ........ 44
5.2.18. Integer controlled step position information (ISC) ......... 45
5.2.19. Analogue set point (APC) ............................................. 45
5.3. Status codes ................................................................................ 45
5.3.1. Introduction ................................................................... 45
5.3.2. Link layer status codes ................................................. 45
5.3.3. Application layer status codes ...................................... 46
5.4. Attributes ...................................................................................... 47
5.4.1. General information about attributes ............................ 47
4
1MRS758692
COM600 series 5.0
Slave Protocols (Ethernet) and Applications Technical
Reference Manual
5.4.2. DNP LAN Slave OPC Client attributes .......................... 47
5.4.3. DNP LAN Channel attributes ........................................ 48
5.4.4. DNP LAN IED attributes ................................................ 49
6. Modbus TCP slave ................................................................................ 51
6.1. About this section ......................................................................... 51
6.2. IEC 61850 data modeling ............................................................ 51
6.2.1. General information about IEC 61850 data modeling .... 51
6.2.2. Single point status (SPS) .............................................. 51
6.2.3. Double point status (DPS) ............................................ 52
6.2.4. Integer status (INS) ....................................................... 52
6.2.5. Enumerated Status (ENS) ............................................ 52
6.2.6. Protection activation information (ACT) ........................ 53
6.2.7. Directional protection activation information (ACD) ...... 53
6.2.8. Binary counter reading (BCR) ....................................... 54
6.2.9. Measured value (MV) .................................................... 54
6.2.10. Complex measured value (CMV) .................................. 54
6.2.11. WYE .............................................................................. 55
6.2.12. Delta (DEL) ................................................................... 55
6.2.13. Controllable single point (SPC) ..................................... 56
6.2.14. Controllable double point (DPC) ................................... 56
6.2.15. Controllable integer status (INC) ................................... 57
6.2.16. Controllable Enumerated Status (ENC) ........................ 57
6.2.17. Binary controlled step position information (BSC) ........ 57
6.2.18. Integer controlled step position information (ISC) ......... 58
6.2.19. Analogue set point (APC) ............................................. 58
6.3. Attributes ...................................................................................... 58
6.3.1. General information about attributes ............................. 58
6.3.2. Modbus TCP Slave OPC Client attributes .................... 59
6.3.3. Channel attributes ......................................................... 60
6.3.4. IED attributes ................................................................ 61
7. Appendix 1 ........................................................................................... 63
7.1. Interoperability list for IEC104 Slave OPC Client ......................... 63
8. Appendix 2 ........................................................................................... 77
8.1. Device profile ............................................................................... 77
Index ............................................................................................................ 103
5
COM600 series 5.0
1MRS758692
Slave Protocols (Ethernet) and Applications Technical
Reference Manual
6
About this manual1.
Copyright1.1.
This document and parts thereof must not be reproduced or copied without written per-
mission from ABB, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
Disclaimer1.2.
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must satisfy
themselves that each intended application is suitable and acceptable, including that any
applicable safety or other operational requirements are complied with. In particular, any
risks in applications where a system failure and/ or product failure would create a risk
for harm to property or persons (including but not limited to personal injuries or death)
shall be the sole responsibility of the person or entity applying the equipment, and those
so responsible are hereby requested to ensure that all measures are taken to exclude or
mitigate such risks.
This product is designed to be connected and to communicate information and data via
a network interface, which should be connected to a secure network. It is sole responsib-
ility of person or entity responsible for network administration to ensure a secure connec-
tion to the network and to establish and maintain any appropriate measures (such as but
not limited to the installation of firewalls, application of authentication measures,
encryption of data, installation of anti virus programs, etc) to protect the product, the
network, its system and the interface against any kind of security breaches, unauthorized
access, interference, intrusion, leakage and/or theft of data or information. ABB is not
liable for damages and/or losses related to such security breaches, unauthorized access,
interference, intrusion, leakage and/or theft of data or information.
This document has been carefully checked by ABB but deviations cannot be completely
ruled out. In case any errors are detected, the reader is kindly requested to notify the
manufacturer. Other than under explicit contractual commitments, in no event shall ABB
7
COM600 series 5.0
1MRS758692
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
be responsible or liable for any loss or damage resulting from the use of this manual or
the application of the equipment.
Conformity1.3.
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity
is the result of tests conducted by ABB in accordance with the product standards EN
50263 and EN 60255-26 for the EMC directive, and with the product standards EN
60255-1 and EN 60255-27 for the low voltage directive. The product is designed in
accordance with the international standards of the IEC 60255 series.
Trademarks1.4.
ABB is a registered trademark of ABB Group. All other brand or product names men-
tioned in this document may be trademarks or registered trademarks of their respective
holders.
General information1.5.
This manual provides thorough information on all the Ethernet-based Slave protocols
supported by the COM600 and and their central concepts. You will find instructions on
how to configure the related objects belonging to the different Ethernet-based slave
protocol servers. The basic operation procedures are also discussed.
Information in this user’s manual is intended for application engineers.
As a prerequisite, you should understand the basic principles of the different Ethernet-
based slave protocols and the IEC 61850 standard.
Document conventions1.6.
The following conventions are used for the presentation of material:
•
The words in names of screen elements (for example, the title in the title bar of a
window, the label for a field of a dialog box) are initially capitalized.
•
Capital letters are used for the name of a keyboard key if it is labeled on the keyboard.
For example, press the ENTER key.
•
Lowercase letters are used for the name of a keyboard key that is not labeled on the
keyboard. For example, the space bar, comma key, and so on.
•
Press CTRL+C indicates that you must hold down the CTRL key while pressing
the C key (to copy a selected object in this case).
8
1MRS758692
COM600 series 5.0
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
•
Press ESC E C indicates that you press and release each key in sequence (to copy
a selected object in this case).
•
The names of push and toggle buttons are boldfaced. For example, click OK.
•
The names of menus and menu items are boldfaced. For example, the File menu.
•
The following convention is used for menu operations: MenuName > Menu-
Item > CascadedMenuItem. For example: select File > New > Type.
•
The Start menu name always refers to the Start menu on the Windows taskbar.
•
System prompts/messages and user responses/input are shown in the Courier font.
For example, if you enter a value out of range, the following message is displayed:
Entered value is not valid. The value must be 0 - 30 .
•
You can be asked to enter the string MIF349 in a field. The string is shown as follows
in the procedure:
MIF349
•
Variables are shown using lowercase letters:
sequence name
Use of symbols1.7.
This publication includes warning, caution, and information icons that point out safety-
related conditions or other important information. It also includes tip icons to point out
useful information to the reader. The corresponding icons should be interpreted as follows.
The electrical warning icon indicates the presence of a hazard
which could result in electrical shock.
The warning icon indicates the presence of a hazard which
could result in personal injury.
The caution icon indicates important information or warning
related to the concept discussed in the text. It may indicate
the presence of a hazard which could result in corruption of
software or damage to equipment or property.
The information icon alerts the reader to relevant facts and
conditions.
9
COM600 series 5.0
1MRS758692
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
The tip icon indicates advice on, for example, how to design
your project or how to use a certain function.
Terminology1.8.
DescriptionTerm
An abnormal state of a condition.Alarm
An OPC service for providing information about alarms and
events to OPC clients.
Alarms and Events; AE
COM600 as a generic name for COM600S IEC and COM600F
ANSI products
COM600 Series; COM600
An OPC service for providing information about process data to
OPC clients.
Data Access; DA
Part of a logical node object representing specific information,
for example, status, or measurement. From an object-oriented
point of view, a data object is an instance of a class data object.
DOs are normally used as transaction objects; that is, they are
data structures.
Data Object; DO
The data set is the content basis for reporting and logging. The
data set contains references to the data and data attribute val-
ues.
Data Set
A physical device that behaves as its own communication node
in the network, for example, protection relay.
Device
Change of process data or an OPC internal value. Normally, an
event consists of value, quality, and timestamp.
Event
A physical IEC 61850 device that behaves as its own commu-
nication node in the IEC 61850 protocol.
Intelligent Electronic Device
Representation of a group of functions. Each function is defined
as a logical node. A physical device consists of one or several
LDs.
Logical Device; LD
The smallest part of a function that exchanges data. An LN is
an object defined by its data and methods.
Logical Node; LN
Series of standards specifications aiming at open connectivity
in industrial automation and the enterprise systems that support
industry.
OPC
Representation of a connection to the data source within the
OPC server. An OPC item is identified by a string <object
path>:<property name>. Associated with each OPC item are
Value, Quality, and Time Stamp.
OPC item
Named data item.Property
10
1MRS758692
COM600 series 5.0
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
DescriptionTerm
The report control block controls the reporting processes for
event data as they occur. The reporting process continues as
long as the communication is available.
Report Control Block
ABB proprietary communication protocol used in substation
automation.
SPA
Protection and/or Control Product supporting the SPA protocol
version 2.5 or earlier.
SPA device
XML-based description language for configurations of electrical
substation IEDs. Defined in IEC 61850 standard.
Substation Configuration Lan-
guage; SCL
Abbreviations1.9.
The following is a list of abbreviations associated with COM600 that you should be
familiar with. See also 1.8, Terminology.
DescriptionAbbreviation
Alarms and EventsAE
Application Service Data UnitASDU
Buffered Report Control BlockBRCB
Data AccessDA
Data Message Code DefinitionDMCD
Data ObjectDO
Gateway, component connecting two communication networks togetherGW
Web Human Machine InterfaceWebHMI
International Electrotechnical CommissionIEC
Intelligent Electronic DeviceIED
Local Area NetworkLAN
Logical DeviceLD
Logical NodeLN
Network Control CenterNCC
Norwegian User ConventionNUC
Object Linking and EmbeddingOLE
OLE for Process ControlOPC
Protection & ControlP&C
Programmable Logic ControllerPLC
Program Organization UnitPOU
Request To SendRTS
11
COM600 series 5.0
1MRS758692
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
DescriptionAbbreviation
Substation AutomationSA
Substation Configuration DescriptionSCD
Substation Configuration LanguageSCL
Sequential Function ChartSFC
Single Line DiagramSLD
Simple Network Management ProtocolSNMP
Simple Network Time ProtocolSNTP
Report Control BlockRCB
Unbuffered Report Control BlockURCB
eXtended Markup LanguageXML
Related documents1.10.
MRS numberName of the manual
1MRS756125COM600 User’s Manual
Document revisions1.11.
HistoryProduct revisionDocumentversion/date
Document created1.0A/24.5.2017
12
1MRS758692
COM600 series 5.0
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Introduction2.
General information about the COM600 series2.1.
The COM600 product series are versatile Substation Management Units that help realize
smart substation and grid automation solutions in industrial and utility distribution net-
works.
They get deployed together with protection and control IEDs, substation devices such
as RTUs, meters and PLCs in dedicated cabinets and switchgear.
The COM600 product is an all-in-one unit that functions as:
•
Communication gateway
•
Web Human Machine Interface (WebHMI)
•
Automation controller
•
Real-time and historical data management unit
The COM600 product series use process information and device data, acquired over
Ethernet or serial communication protocol interfaces to execute specific substation
functions and applications. Thus, they are critical building blocks to realize substation
secondary system solutions and in the process solving diverse customer needs.
COM600 product series variants and rationale2.2.
To facilitate substation and grid automation solutions in IEC and ANSI market areas, a
variant-based system similar to Relion
®
615 and 620 series is being followed from
COM600 5.0 release.
The main reasons for such an approach are the following:
•
To ensure all COM600 product series features are advantageously used in end-cus-
tomer projects in the medium voltage substation automation domain.
•
To ensure an optimum feature set to be bundled together to realize specific applica-
tions required in IEC and ANSI market areas.
•
To ensure a future-proof product approach.
This release then comprises of two variants, based on the primary intent or application
are defined as follows:
•
COM600S IEC – COM600 for substation automation, analysis and data management
(for IEC markets)
•
COM600S IEC is a substation automation, analyzer and data management unit
that integrates devices, facilitates operations, manages communication and runs
analysis applications pertinent to equipment or operations in utility or industrial
distribution substations.
•
COM600F ANSI – COM600 as distribution automation controller (for ANSI markets)
13
COM600 series 5.0
1MRS758692
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
•
COM600F is a dedicated distribution automation controller unit that runs dis-
tributed grid and feeder applications for ANSI power networks and inherits all
core features of the COM600 series.
Functional overview2.3.
COM600 supports multiple slave communication protocols by which it exchanges data
with field devices such as protection and control IEDs, meters or other devices such as
station controllers, Ethernet switches and WebHMIs. The data communication can be
accomplished using Ethernet or serial interfaces such as RS 232 or RS 485. The following
slave protocols are supported by the COM600:
1. Ethernet-based protocols
•
IEC 61850-8-1
•
IEC 60870-5-104
•
DNP 3.0 LAN/WAN
•
Modbus
•
OPC
2. Serial interface-based protocols
•
IEC 60870-5-101
•
DNP 3.0 Serial
•
Modbus
COM600 converts all field data, acquired using the communication protocols listed
above, into OPC. An OPC server is dedicated to every supported protocol. This OPC
server enables other OPC clients (internal) to access process data from slave devices.
This manual specifically covers the above listed Ethernet based slave protocols.
14
1MRS758692
COM600 series 5.0
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
SysConf.bmp
Figure 2.3-1 System overview
The protocol handling, that is, configuration and operation aspects comprise of generic
and specific aspects. These generic and specific parts will be described separately in this
manual.
Handling in brief:
All slave protocols have two common aspects
•
An OPC server layer
•
Data modeling based on IEC 61850
15
COM600 series 5.0
1MRS758692
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
IEC 61850 Proxy server3.
ACSI conformance statement3.1.
ACSI conformance statement3.1.1.
ACSI conformance statements shall be used to provide an overview and details about a
device claiming conformance with ACSI:
•
3.1.2, ACSI basic conformance statement
•
3.1.3, ACSI models conformance statement
•
3.1.4, ACSI service conformance statement
These statements are used to specify the communication features mapped to an SCSM.
The following tables provide the ACSI conformance statements for the COM600 IEC
61850 Proxy Server. The tables are according to IEC 61850-7-2.
ACSI basic conformance statement3.1.2.
Table 3.1.2-1 Basic conformance statement
Value/CommentsServer/Pub-
lisher
Client/Sub-
scriber
Client-Server roles
SUPPORTEDc1-Server side (of TWO-PARTY-
APPLICATION-ASSOCIATION)
B11
-c1Client side of (TWO-PARTY-
APPLICATION-ASSOCIATION)
B12
SCSMs supported
SUPPORTEDSCSM: IEC 6185-8-1 usedB21
-SCSM: IEC 6185-9-1 usedB22
-SCSM: IEC 6185-9-2 usedB23
-SCSM: otherB24
Generic substation event
model (GSE)
SUPPORTEDO-Publisher sideB31
--OSubscriber sideB32
Transmission of sampled
value model (SVC)
-O-Publisher sideB41
--OSubscriber sideB42
16
1MRS758692
COM600 series 5.0
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
c1 – shall be ‘M’ if support for LOGICAL-DEVICE model has been declared.
O – Optional
M – Mandatory
ACSI models conformance statement3.1.3.
Table 3.1.3-1 ACSI models conformance statement
Value/CommentsServer/Pub-
lisher
Client/Sub-
scriber
If Server side (B1) supported
SUPPORTEDc2c2Logical deviceM1
SUPPORTEDc3c3Logical nodeM2
SUPPORTEDc4c4DataM3
SUPPORTEDc5c5Data setM4
-OOSubstitutionM5
-OOSetting group controlM6
Reporting
SUPPORTEDOOBuffered report controlM7
sequence-numberM7-1
report-time-stampM7-2
reason-for-inclusionM7-3
data-set-nameM7-4
data-referenceM7-5
buffer-overflowM7-6
entryIDM7-7
BufTmM7-8
IntgPdM7-9
GIM7-10
conf-revisionM7-11
SUPPORTEDOOUnbuffered report controlM8
sequence-numberM8-1
report-time-stampM8-2
reason-for-inclusionM8-3
data-set-nameM8-4
data-referenceM8-5
17
COM600 series 5.0
1MRS758692
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Value/CommentsServer/Pub-
lisher
Client/Sub-
scriber
BufTmM8-6
IntgPdM8-7
GIM8-8
conf-revisionM8-9
-OOLogging
-OOLog controlM9
IntgPdM9-1
-OOLogM10
SUPPORTEDMMControlM11
If GSE (B31/32) is supported
SUPPORTED (send)OOGOOSE
OOGSSEM13
If SVC (41/42) is supported
-OOMulticast SVCM14
-OOUnicast SVCM15
-MMTimeM16
-OOFile TransferM17
c1 – shall be ‘M’ if support for LOGICAL-DEVICE model has been declared.
c2 – shall be ‘M’ if support for LOGICAL-NODE model has been declared.
c3 – shall be ‘M’ if support for DATA model has been declared.
c4 – shall be ‘M’ if support for DATA-SET, Substitution, Report, Log Control, or Time
model has been declared.
c5 – shall be ‘M’ if support for Report, GSE, or SMV models has been declared.
M - Mandatory
ACSI service conformance statement3.1.4.
The ACSI service conformance statement shall be as defined in Table 3.1.4-1 (depending
on the statements in Table 3.1.3-1).
18
1MRS758692
COM600 series 5.0
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Table 3.1.4-1 ACSI service Conformance statement
Value/CommentsServer/Pub-
lisher
Client/Sub-
scriber
AA:
TP/MC
Services
Server
SUPPORTEDMTPServerDirectoryS1
Application association
SUPPORTEDMMAssociateS2
SUPPORTEDMMAbortS3
SUPPORTEDMMReleaseS4
Logical device
SUPPORTEDMMTPLogicalDeviceDirectoryS5
Logical node
SUPPORTEDMMTPLogicalNodeDirectoryS6
SUPPORTEDMOTPGetAllDataValuesS7
Data
SUPPORTEDMMTPGetDataValuesS8
SUPPORTEDOOTPSetDataValuesS9
SUPPORTEDMOTPGetDataDirectoryS10
SUPPORTEDMOTPGetDataDefinitionS11
Data set
SUPPORTEDMOTPGetDataSetValuesS12
-OOTPSetDataSetValuesS13
-OOTPCreateDataSetS14
-OOTPDeleteDataSetS15
SUPPORTEDOOTPGetDataSetDirectoryS16
Substitution
SUPPORTEDMMTPSetDataValuesS17
Setting group control
-OOTPSelectActiveSGS18
-OOTPSelectEditSGS19
-OOTPSetSGValuesS20
-OOTPConfirmEditSGValuesS21
-OOTPGetSGValuesS22
-OOTPGetSGCBValuesS23
Reporting
19
COM600 series 5.0
1MRS758692
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Value/CommentsServer/Pub-
lisher
Client/Sub-
scriber
AA:
TP/MC
Services
Buffered report control block
(BRCB)
SUPPORTEDc6c6TPReportS24
data-change (dchg)S24-1
qchg-change (qchg)S24-2
data-update (dupd)S24-3
SUPPORTEDc6c6TPGetBRCBValuesS25
SUPPORTEDc6c6TPSetBRCBValuesS26
Unbuffered report control
block (URCB)
SUPPORTEDc6c6TPReportS27
data-change (dchg)S27-1
qchg-change (qchg)S27-2
data-update (dupS27-3
SUPPORTEDc6c6TPGetURCBValuesS28
SUPPORTEDc6c6TPSetURCBValuesS29
Logging
Logging control block
-MMTPGetLCBValuesS30
-MOTPSetLCBValuesS31
Log
-Mc7TPQueryLogByTimeS32
-Mc7TPQueryLogByEntryS33
-MMTPGetLogStatusValuesS34
Generic substation event
model (GSE)
GOOSE-CONTROL-BLOCK
SUPPORTEDc8c8MCSendGOOSEMessageS35
-c9OTPGetReferenceS36
-c9OTPGetGOOSEElementNumberS37
-OOTPGetGoCBValuesS38
-OOTPSetGoCBValuesS39
GSSE-CONTROL-BLOCK
-c8c8MCSendGSSEMessageS40
-c9OTPGetReferenceS41
20
1MRS758692
COM600 series 5.0
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108

ABB COM600 series 5.0 Technical Reference Manual

Type
Technical Reference Manual