Square D Company 9013-FSG2-J21 User manual

Type
User manual
1
Data Bulletin
9013DB0701
12/2007
Raleigh, NC USA
Preventive Maintenance and Troubleshooting Guidelines for
Class 9013F and 9013G Pressure Switches
Retain for future use.
Introduction This data bulletin describes how to identify and correct the most common
maintenance issues for the Class 9013F and 9013G Pressure Switches.
Ensure that all maintenance recommended by the original equipment
manufacturer (OEM) is performed. If the equipment fails to operate properly,
refer to the instructions and recommendations provided by the OEM, and
ensure that the instructions were correctly followed. If the operating
problems persist and a pressure switch is the suspected cause, use the
information in this bulletin to assist in troubleshooting the issues.
Inspecting the Pump System
Before the Initial Operation Inspect the following items before operating the pump system:
1. Check the pump’s yield and flow rate.
2. Check the well water level, drawdown, and recovery.
3. Check the line voltage with the pump on and off.
4. Verify that the running current does not exceed the motor nameplate
data.
Before Maintenance Inspect the following items before performing maintenance to the pump
system:
1. Visually inspect the pump system for leakage.
2. Check the pressure switch using a pressure gauge.
3. Record the pressure switch setting if available.
4. Review any system discrepancies or perceived problems in operation.
5. Confirm that electrical power is available and that circuit breakers (or
fuses) are operational.
Providing Routine Maintenance During the normal maintenance period for the pump system, ensure that the
following steps are followed to for all pressure switches.
1. Disconnect the power.
2. Remove the cover.
3. Visually inspect the pressure switch for leakage. Verify that:
No liquid is leaking from the diaphragm or flange area.
The flange is not corroded.
The area is free of standing water and wet spots.
Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches 9013DB0701
Providing Routine Maintenance 12/2007
© 2007 Schneider Electric All Rights Reserved2
4. Check all plumbing connections. Verify that:
The flange is not corroded.
The fittings are secure and without white residue (lime deposits).
5. Check all electrical connections. Verify that:
The wires are not pinched or frayed, and the insulation is not
cracked.
There are no insects, contamination, or nests. If found, remove.
NOTE: Contacts may appear pitted. Do not sand or file the contacts. Do
not use chemicals to clean the contacts.
6. Check the system pressure using a pressure gauge.
7. Replace the cover.
8. Restore the power and confirm pump system operation.
9. Open a tap or spigot to confirm water flow.
10. For devices with low pressure cut-out (Form M4), hold the lever to Run
until the pressure is within 10 psi of the cut-in pressure.
Adjusting the Pressure Switch 1. Monitor the pressure gauge during operation to determine the points
where the pressure switch turns on and off.
2. Determine whether to adjust the cut-in, cut-out, or both.
3. If using a tank with an air bladder, determine what air pressure is
required in the bladder.
NOTE: Follow the manufacturer's instructions for setting air pressure to
the required level for the new adjusted pressure switch setting. When
instructions are not available, always set the air pressure in the bladder
to 2 psi below the new desired cut-in pressure. Perform the following
steps to set the air pressure:
a. Turn off the power to the pump.
b. Drain the water from the pressure tank.
c. Using a pressure gauge, take a pressure reading of the tank.
d. Using the air valve, add or remove air from the tank bladder until the
correct pressure is reached.
4. Perform Steps 1–6 of “Providing Routine Maintenance” on page 1.
5. To increase or decrease the cut-in and cut-out settings (while
maintaining the same differential) adjust the pressure switch with a
3/8 inch nut driver or socket as follows:
a. Turn the range nut clockwise for higher cut-in pressure, or counter-
clockwise for lower cut-in pressure. See Figure 1.
NOTE: Adjusting the cut-in setting does not change the differential.
As the cut-in value changes, the cut-out value changes by the same
amount and in the same direction. For example, increasing the cut-in
pressure by 10 psi will also result in an increase in the cut-out
pressure by 10 psi.
When lowering the pressure setting, remember that most bladder
tank water systems are designed for the bladder pressure to be 2 psi
below the cut-in point when there is no water in the tank.
Figure 1: 9013F/9013G Pressure Switches
With Adjustable Differential
Range nut
Types FTG and FHG
Types FSG, FYG, and FRG
Type G
Range nut
Range nut
Differential
nut
Differential
nut
9013DB0701 Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches
12/2007 Providing Routine Maintenance
© 2007 Schneider Electric All Rights Reserved
3
b. Use the table below as a guideline for setting range nut R.
c. Complete Steps 7 and 8 of “Providing Routine Maintenance” on
page 2.
6. To increase or decrease the cut-out setting (while maintaining the same
cut-in pressure) adjust the pressure switch with a 3/8 inch nut driver or
socket as follows:
a. Complete Steps 1–6 of “Providing Routine Maintenance” on page 1.
b. Turn differential nut D clockwise for higher cut-out pressure, or
counter clockwise for lower cut-out pressure. See Figure 1 on
page 2.
NOTE: Adjusting the differential changes the cut-out setting. The
cut-in does not change.
c. Complete Steps 7–9 of “Providing Routine Maintenance” on page 2.
7. Monitor the system to ensure that the pressure setting is as desired.
a. Open a faucet and drain water from the system until the pump turns
on.
b. Turn off the faucet.
c. Monitor the system pressure to identify the point where the pump
turns off.
d. Repeat Steps 5–7 as required.
Renewal Parts
Original Setting New Setting
Turn Range Nut R
Clockwise
20-40 30-50 3-1/2 Turns
20-40 40-60 8 to 8-1/2 Turns
30-50 40-60 3-1/2 Turns
Table 1: Renewal Parts
Description Part Number
9013F 9013G
Contact kit with contact block, contacts, and
diaphragm
9998PC241 9998PC205
Replacement cover
1
1
Include the complete part number of the pressure switch to be used with, including all forms.
65076 605 50 665133 559 50
Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches 9013DB0701
Troubleshooting 12/2007
© 2007 Schneider Electric All Rights Reserved4
Troubleshooting
Table 2: Troubleshooting Tips
Condition Possible Causes Description/Corrective Action
Corrective Procedure for
Qualified Service Personnel
No water flow
Power is off Confirm that the power is on.
No water in pressure
system
Confirm the pressure tank pressure reading.
A. If the pressure is below cut-in, and the switch has low pressure cut-
out (Form M4), hold lever in the Run position.
Marginal or low producing well
The pump may exceed well
capacity. Restrict pump output or
install smaller pump.
Check the pumping water level.
1. The pump should turn on and run.
2. When you release the lever, if the M4 feature cuts out the pump
again (within 10 psi of cut-in), the water source is low.
3. Do not actuate the M4 lever again until source has recharged
(the well has water in it).
B. Where Form M4 is not present, check the water source. The well
may be low. Turn off the power to the pump until source has
recharged (the well has water in it).
C. The line to the pressure switch may be plugged, so that the switch
cannot read tank pressure. Check the tank pressure. If it is below
cut-in pressure setting, complete Steps 1–6 of “Providing Routine
Maintenance” on page 1. Look at the contacts to confirm that the
contacts are closed. Complete remaining steps in “Providing
Routine Maintenance” on page 1.
1. Remove the pressure switch from the
pipe and confirm that the entry to the
diaphragm is free of silt and
obstructions.
2. Confirm that any check valves in the
system between the source and the
pressure tank are functioning properly.
3. Confirm that pressure reading at the
pressure switch accurately reflects the
pressure in the pressure tank.
Switch contacts severely
burned
Insects or objects may have entered the space between the contacts.
Remove nests or other havens for insects or vermin near the switch.
Replace the contacts.
The pump is too large. Add a contactor designed for the load.
The application requires a switch with heavy duty contacts.
Replace the switch. Use higher hp
rating.
Rapid cycling
(erratic
operation)
Tank waterlogged
For pre-charged tanks, check the bladder or air valve for leaks and
check tank pressure. If it is below cut-in pressure setting, complete
Steps 1–5 of “Providing Routine Maintenance” on page 1.
Drain some air from the compressed air valve stem. If water comes out,
the bladder is leaking. Completely drain the bladder and recharge with
air as required. Complete the remaining procedures in “Providing
Routine Maintenance” on page 1.
Replace or repair the pressure tank.
Tank not charged
For pre-charged tanks, check the bladder or air valve for leaks and
check the tank pressure. If it is below cut-in pressure setting, complete
Steps 1–5 of “Providing Routine Maintenance” on page 1.
Drain some air from the compressed air valve stem. If water comes out,
the bladder is leaking. Completely drain the bladder and recharge with
air as required. Complete the remaining procedures in “Providing
Routine Maintenance” on page 1.
1. Replace or repair the pressure tank.
2. For conventional tanks, check air
volume control for proper operation.
Drain and recharge tank. Clean or
replace any faulty parts.
Diaphragm damaged
During routine maintenance (see “Providing Routine Maintenance” on
page 1) water is found leaking around diaphragm.
Replace the diaphragm.
Undersized tank
Restrict water usage. Limit the number of devices in operation at any
one time.
Install a larger tank.
Major leak in service lines
Visible water or wet spots may be present. The pump runs, but the tank
is slow to fill.
Check for leaks. Replace damaged
pipes or repair leaks.
Faulty check valve (open) In some systems, water can flow back into the well, emptying the tank.
Check for leaking or open check valve.
Replace if defective.
Foreign material
(calcium deposits)
The line to the pressure switch may be plugged and the switch cannot
read the tank pressure.
Check the tank pressure. If it is below cut-in pressure setting, complete
Steps 1–5 of “Providing Routine Maintenance” on page 1. Look at the
contact plate to confirm that the contacts are closed. Complete the
remaining procedures in “Providing Routine Maintenance” on page 1.
There may be a block in the line
allowing the pressure switch to see high
pressure all the time.
No holding tank Install a properly sized holding tank.
9013DB0701 Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches
12/2007 Troubleshooting
© 2007 Schneider Electric All Rights Reserved
5
Pump cycles
each time water
is used
Tank waterlogged
For pre-charged tanks, check the bladder or air valve for leaks and
check tank pressure. If it is below cut-in pressure setting, complete
Steps 1–5 of “Providing Routine Maintenance” on page 1.
Drain some air from the compressed air valve stem. If water comes out,
the bladder is leaking. Completely drain the bladder and recharge with
air as required. Complete the remaining steps under “Providing Routine
Maintenance” on page 1.
1. Replace or repair the pressure tank.
2. For conventional tanks, check air
volume control for proper operation.
Drain and recharge tank. Clean or
replace any faulty parts.
Pressure switch
chattering
(contact chatter
or bounce)
Incorrect air pressure in the
bladder
Adjust the air pressure in the bladder to manufacturer's specification.
See the procedures for waterlogged tank.
For conventional tanks, check the air
volume control for proper operation.
Drain and recharge tank. Clean or
replace any faulty parts.
Excessive vibration
The pressure switch may be mounted on rigid pipe and secured by
brackets to the structure. If the pump is also tightly secured, vibration
may be amplified.
Mount the pressure switch to a less rigid
pipe, and shock mount any brackets.
Isolate the switch from other sources of vibration by shock mounting.
Pump shuts off
immediately after
startup
High pressure pump or a
new pump
Add a surge reducer. Order 1530S6G1 for a bag of 50.
Long pump run,
or pump will not
shut off
Too many water outlets
Limit the number of devices running at any one time.
Increase the size of the pump and/or storage tank Replace the components as desired
Worn pump parts
Check the pump for worn impellers,
casing, or other close fitting parts.
Water leaks
Check for leaks in service lines. Repair the leaks as required
Plugged discharge pipes
Check for plugged discharge pipes
resulting in reduced flow. Replace the
damaged pipes or repair the leaks.
Switch contacts
burn up
Pump electrical rating is
too high
Ensure that the electrical rating of the
switch corresponds to the pump’s
electrical rating.
Add a contactor.
The switch may be replaced by one with
heavy duty contacts.
Switch will not
trip (cut-in/cut-
out) at desired
pressure
Incorrect pressure settings
Adjust to correct pressure settings. See procedures for waterlogged
tank on page 4.
Defective pressure gauge Test the pressure gauge. Replace the pressure gauge.
Damaged diaphragm
actuator
Replace the diaphragm.
Cannot adjust
switch to desired
pressure
Settings outside the
pressure range limits of the
switch
Replace the switch with one that has
the correct range and differential
Table 2: Troubleshooting Tips (continued)
Condition Possible Causes Description/Corrective Action
Corrective Procedure for
Qualified Service Personnel
Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches 9013DB0701
Troubleshooting 12/2007
© 2007 Schneider Electric All Rights Reserved6
Switch operates
mechanically,
but not
electrically
No power to switch
Apply power to the switch.
Check the circuit breaker and/or disconnect switch. If the breaker is
tripped on a new installation, check the switch wiring. Reset the breaker
(disconnect).
Apply power to the switch.
Confirm the wiring of the switch.
Damaged or improperly
installed wiring
Wired to the wrong contact.
Complete Steps 1–5 of “Providing Routine Maintenance” on page 1.
Wire to the correct contacts.
Corroded or loose connections
Make new connections or tighten the
existing connections.
Damaged switch contacts
Replace the switch contacts or entire
switch.
Contacts overloaded (welded)
Complete Steps 6–10 of “Providing Routine Maintenance” on page 1.
Remove the pressure switch from
the pipe and confirm that the entry
to the diaphragm is free of silt and
obstructions.
Confirm that any check valves in the
system between the source and the
pressure tank are functioning
properly.
Confirm that pressure reading at the
pressure switch accurately reflects
the pressure in the pressure tank.
Low pressure cut-out (M4) has cut-
out.
Repair or replace the switch if
defective.
Clean plumbing and pressure port
(replace if defective).
Table 2: Troubleshooting Tips (continued)
Condition Possible Causes Description/Corrective Action
Corrective Procedure for
Qualified Service Personnel
9013DB0701 Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches
12/2007 Frequently Asked Questions
© 2007 Schneider Electric All Rights Reserved
7
Frequently Asked Questions
Table 3: Frequently Asked Questions about Square D Class 9013F and 9013G Pressure Switches
Questions Answers
Can I use a 9013F water pump switch on an air compressor—or a
9013FHG air compressor switch on a water system?
Yes, but not you cannot use a 9013FSG water pump switch on a compressor requiring
Form X.
Is Form M4 (low pressure cut-out) available on the 9013GSG•••
pressure switches?
No, it is not available on the 9013GSG••• pressure switches. It is only available on the
9013FSG••• and the 9013FYG••• pressure switches.
Where can we find information about the 9213 pressure switch?
The information can be found in the 1947 Digest under Pressure Switches. For
information, contact Product Support.
Are 9013FRG pressure switches available in NEMA 3R? No, reverse action 9013F pressure switches are available only in NEMA 1 enclosures.
Are 9013 pressure switches DC voltage rated? Yes, the 9013 pressure switches are rated for DC as noted in Digest 174.
Do the 9013F and 9013G pressure switches accept both solid and
stranded wire?
Yes, the 9013F and 9013G pressure switches accept both solid and stranded wire.
Are the 9013FSG pressure switches CSA approved? Yes, these switches are CSA Approved, File #LR25490.
How can I connect a 9013G pressure switch to control a 3-phase
motor with only a 2-pole set of contacts?
Wire two legs of the 3-phase motor through the two poles of the pressure switch.
Breaking two phases will start and stop the motor. Wire the third leg direct. Install a
disconnect upstream of the pressure switch.
How do I select an appropriate pressure switch?
Refer to the catalog Commercial Pressure Switches Types F and G Class 9013
(9013CT9701) or Industrial Pressure Switches (9012CT9701) located in the Technical
Library at www.us.SquareD.com.
Will a 9013G pressure switch handle 20 A at 230 V, 1-phase and
3 hp?
The 9013G pressure switches are not current rated devices. They are hp rated devices
only. To use on 3-phase circuits, wire 2 phases through the 2 poles of the switch and
direct wire the third phase to one of the motor leads. This makes the lead live when the
pressure switch is off.
Can a 9013FSG2J20 pressure switch be installed horizontally, rather
than the standard vertical mounting?
Yes. The 9013FSG2J20 pressure switch can be mounted horizontally and still work
properly.
Is the catalog number for the 9013 pressure switch valid without the
pressure code?
No. You must have the J code pressure setting to order this product. If a list of pressure
settings is not available, use J99 and include the setpoints desired. The setpoints must
fall within the range of the pressure switch selected.
Is 9013FSG120J20 a valid catalog number?
No. That number indicates that all 9013FSG1 through 9013FSG20 pressure switches
with Form M4 have a different pressure range than the standard pressure switches.
What is the difference between a series B and series C 9013
pressure switch?
Functionally, they are the same device. A series change could have been due to a minor
change in the device. When ordering, customers will receive the latest series available.
What is the temperature range for a 9013F and 9013G pressure
switches?
These temperature ratings apply to all the 9013F and 9013G pressure switches:
Fluid media: -30 to 125 °C (-22 to +257 °F).
Ambient temperature rating: -30 °C to 70 °C (-22 to +158 °F).
What is the maximum allowable pressure for a 9013FRG pressure
switch?
The maximum allowable pressure for a 9013 FRG, GHB, GHG, GSB and GSG pressure
switch is 300 psi.
What is the replacement contact kit for a 9013GHG5 pressure
switch?
The replacement contact kit is 9998 PC205.
Is the 9013GSG2J23R commercial pressure switch available with an
override switch?
No. The closest product with an override switch is the 9012GSG pressure switch with
Form E (On-Auto-Off lever).
Is the low pressure cut-off option on a 9013 pressure switch
adjustable?
The low pressure cutoff remains fixed at 10 psi below the low pressure cut-in for the
pressure switch. Although it is not independently adjustable, it will follow the low pressure
set point. However, the pressure switch will not be effective if the cut-in point is set below
10 psi.
How do I select an appropriate pressure switch?
Refer to the catalog Commercial Pressure Switches Types F and G Class 9013
(9013CT9701), Industrial Pressure Switches (9012CT9701), or Nautilus™ Electronic
Pressure Sensors, XMLE, XMLF, XMLG (9014CT0201).
Is 9998PC52 parts kit still available?
Parts kit 9998PC52 is no longer available.
This parts kit, and all pressure switches using a bellows assembly in their construction
are obsolete. Cross reference the old pressure switch to current products. The available
cross referenced products use diaphragms or pressure transducers.
What is the function of a pulsation plug in a 9013 pressure switch?
The pulsation plug slows the flow of fluid to the diaphragm of the pressure switch to
reduce the surge rate of change. The switch with the plug installed senses change over
longer intervals and does not respond to spikes.
Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches 9013DB0701
Data Bulletin 12/2007
Electrical equipment should be installed, operated, serviced, and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
© 2007 Schneider Electric All Rights Reserved
Schneider Electric USA
8001 Knightdale Boulevard
Knightdale, NC 27545 USA
1-888-SquareD (1-888-778-2733)
www.us.SquareD.com
Recommended Protection Install electrical surge protection at the service entrance and in the control
box at the wellhead.
The installer should provide motor circuit overload protection in the pump
motor or control box (if used).
For Additional Information For additional information about common product catalog numbers, visit:
www.us.SquareD.com/pumptrol
Schneider Electric's Pumptrol product manager strives to provide the best
value and service to our Pumptrol customers. For answers to your specific
questions or comments about pumping solutions or products:
e-mail: [email protected]neider-electric.com
Technical Support Technical support is provided Monday through Friday between the hours of
8:00 a.m. and 6:00 p.m. EST. For more information, write or call:
Mailing address:
Schneider Electric Pumptrol Product Line
8001 Knightdale Boulevard
Knightdale, NC 27545-9023
e-mail: [email protected]c.com
Telephone: 1-888-SquareD (1-888-778-2733)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Square D Company 9013-FSG2-J21 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI