Bimetal temperature switch, model TFS35
Bimetall-Temperaturschalter, Typ TFS35
Thermocontact bimétallique, type TFS35
Termostato bimetálico, modelo TFS35
ES
FR
DE
EN
2 WIKA operating instructions model TFS35
11610115.04 11/2019 EN/DE/FR/ES
Operating instructions model TFS35
Page 3 - 16
Betriebsanleitung Typ TFS35
Seite 17 - 30
Mode d'emploi type TFS35
Page 31 - 44
Manual de instrucciones modelo TFS35
Página 45 - 57
© 11/2010 WIKA Alexander Wiegand SE & Co. KG
All rights reserved. / Alle Rechte vorbehalten.
WIKA
®
is a registered trademark in various countries.
WIKA
®
ist eine geschützte Marke in verschiedenen Ländern.
Prior to starting any work, read the operating instructions!
Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Lire le mode d'emploi avant de commencer toute opération !
A conserver pour une utilisation ultérieure !
¡Leer el manual de instrucciones antes de comenzar cualquier trabajo!
¡Guardar el manual para una eventual consulta!
WIKA operating instructions model TFS35
11610115.04 11/2019 EN/DE/FR/ES
3
EN
Contents
Contents
1. General information 4
2. Design and function 5
3. Safety 6
4. Transport, packaging and storage 9
5. Commissioning, operation 10
6. Maintenance and cleaning 12
7. Dismounting, return and disposal 13
8. Specifications 15
11610115.04 11/2019 EN/DE/FR/ES
4 WIKA operating instructions model TFS35
EN
1. General information
The bimetal temperature switch described in the operating instructions has been
designed and manufactured using state-of-the-art technology. All components
are subject to stringent quality and environmental criteria during production. Our
management systems are certified to ISO 9001 and ISO 14001.
These operating instructions contain important information on handling the
instrument. Working safely requires that all safety instructions and work instructions
are observed.
Observe the relevant local accident prevention regulations and general safety
regulations for the instrument's range of use.
The operating instructions are part of the product and must be kept in the immediate
vicinity of the instrument and readily accessible to skilled personnel at any time. Pass
the operating instructions on to the next operator or owner of the instrument.
Skilled personnel must have carefully read and understood the operating instructions
prior to beginning any work.
The general terms and conditions contained in the sales documentation shall apply.
Subject to technical modifications.
Further information:
- Internet address: www.wika.de / www.wika.com
- Relevant data sheet: TV 35.01
- Application consultant: Tel.: +49 9372 132-0
Fax: +49 9372 132-406
info@wika.de
1. General information
WIKA operating instructions model TFS35
11610115.04 11/2019 EN/DE/FR/ES
5
EN
2. Design and function
2.1 Overview
Electrical connection
Process connection
Thermowell
2.2 Description
The model TFS35 bimetal temperature switch consists of a thermowell with integrated
switching element and a permanently mounted connector. The bimetal temperature
switch is screwed directly into the process.
All electrical components are protected against splash water. The electrical connection
is via the connector.
2.3 Scope of delivery
Cross-check scope of delivery with delivery note.
2. Design and function
11610115.04 11/2019 EN/DE/FR/ES
6 WIKA operating instructions model TFS35
EN
3. Safety
3.1 Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in serious
injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in light injuries
or damage to property or the environment, if not avoided.
DANGER!
... identifies hazards caused by electric power. Should the safety
instructions not be observed, there is a risk of serious or fatal injury.
WARNING!
... indicates a potentially dangerous situation that can result in burns,
caused by hot surfaces or liquids, if not avoided.
Information
... points out useful tips, recommendations and information for efficient
and trouble-free operation.
3.2 Intended use
The model TFS35 bimetal temperature switches are used to limit temperatures within a
wide variety of industrial applications. The TFS35 are temperature limiting instruments.
They are not intended to provide any safety or protective functionality. They are
designed for use in environments up to pollution degree 2.
They monitor the temperature of machinery and equipment during normal operation
and, for example, switch off machinery if it overheats.
Bimetals form the basis of the model TFS35 temperature switches. Temperature
sensing is carried out by a bimetal disc, which snaps over when the Nominal Switching
Temperature (NST) is reached. After cooling back down to the reset switching
temperature (RST), the switch returns to its original state, so that the monitored
equipment can again work normally.
3. Safety
WIKA operating instructions model TFS35
11610115.04 11/2019 EN/DE/FR/ES
7
EN
The instruments are not approved for use in hazardous areas!
The bimetal temperature switch has been designed and built solely for the intended use
described here, and may only be used accordingly.
The technical specifications contained in these operating instructions must be
observed. Improper handling or operation of the bimetal temperature switch outside
of its technical specifications requires the instrument to be taken out of service
immediately and inspected by an authorised WIKA service engineer.
The manufacturer shall not be liable for claims of any type based on operation contrary
to the intended use.
3.3 Improper use
WARNING!
Injuries through improper use
Improper use of the instrument can lead to hazardous situations and
injuries.
Refrain from unauthorised modifications to the instrument.
Do not use the instrument within hazardous areas.
Do not use the instrument with abrasive or viscous media.
Any use beyond or different to the intended use is considered as improper use.
Do not use this instrument in safety or emergency stop devices.
3.4 Responsibility of the operator
The instrument is used in the industrial sector. The operator is therefore responsible for
legal obligations regarding safety at work.
The safety instructions within these operating instructions, as well as the safety, accident
prevention and environmental protection regulations for the application area must be
maintained.
The operator is obliged to maintain the product label in a legible condition.
To ensure safe working on the instrument, the operating company must ensure
that suitable first-aid equipment is available and aid is provided whenever required.
that the operating personnel are regularly instructed in all topics regarding work
safety, first aid and environmental protection and know the operating instructions and
in particular, the safety instructions contained therein.
that the instrument is suitable for the particular application in accordance with its
intended use.
that personal protective equipment is available.
3. Safety
11610115.04 11/2019 EN/DE/FR/ES
8 WIKA operating instructions model TFS35
EN
3.5 Personnel qualification
WARNING!
Risk of injury should qualification be insufficient
Improper handling can result in considerable injury and damage to
property.
The activities described in these operating instructions may only be
carried out by skilled personnel who have the qualifications described
below.
Keep unqualified personnel away from hazardous areas.
Skilled personnel
Skilled personnel, authorised by the operator, are understood to be personnel
who, based on their technical training, knowledge of measurement and control
technology and on their experience and knowledge of country-specific regulations,
current standards and directives, are capable of carrying out the work described and
independently recognising potential hazards.
Special operating conditions require further appropriate knowledge, e.g. of aggressive
media.
3.6 Labelling, safety marks
Product label (example)
Model
Contact version and switching temperature
Number of production order
Approval logos
Before mounting and commissioning the instrument, ensure you read the
operating instructions!
TFS135
NC 60 °C
12345678
3. Safety
WIKA operating instructions model TFS35
11610115.04 11/2019 EN/DE/FR/ES
9
EN
4. Transport, packaging and storage
4.1 Transport
Check the instrument for any damage that may have been caused by transport.
Obvious damage must be reported immediately.
CAUTION!
Damage through improper transport
With improper transport, a high level of damage to property can occur.
When unloading packed goods upon delivery as well as during
internal transport, proceed carefully and observe the symbols on the
packaging.
With internal transport, observe the instructions in chapter 4.2
“Packaging and storage”.
If the instrument is transported from a cold into a warm environment, the formation of
condensation may result in instrument malfunction. Before putting it back into operation,
wait for the instrument temperature and the room temperature to equalise.
4.2 Packaging and storage
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change
in installation site, sending for repair).
Permissible conditions at the place of storage:
Storage temperature: -40 ... +85 °C
Humidity: 35 ... 85 % relative humidity (no condensation)
Avoidance of exposure to the following factors:
Direct sunlight or proximity to hot objects
Mechanical vibration, mechanical shock (putting it down hard)
Soot, vapour, dust and corrosive gases
Hazardous environments, flammable atmospheres
Store the bimetal temperature switch in its original packaging in a location that fulfils
the conditions listed above. If the original packaging is not available, pack and store the
temperature switch as described below:
1. Wrap the temperature switch in an antistatic plastic film.
2. Place the temperature switch, along with shock-absorbent material, in the packaging.
3. If stored for a prolonged period of time (more than 30 days), place a bag containing a
desiccant inside the packaging.
4. Transport, packaging and storage
11610115.04 11/2019 EN/DE/FR/ES
10 WIKA operating instructions model TFS35
EN
5. Commissioning, operation
WARNING!
Physical injuries and damage to property and the environment
caused by hazardous media
Upon contact with hazardous media (e.g. oxygen, acetylene, flammable
or toxic substances), harmful media (e.g. corrosive, toxic, carcinogenic,
radioactive), and also with refrigeration plants and compressors, there is a
danger of physical injuries and damage to property and the environment.
Should a failure occur, aggressive media with extremely high temperature
and under high pressure or vacuum may be present at the instrument.
For these media, in addition to all standard regulations, the appropriate
existing codes or regulations must also be followed.
CAUTION!
Damage to the instrument
When working on open electric circuits (printed circuit boards) there is a
risk of damaging sensitive electronic components through electrostatic
discharge.
The correct use of grounded working surfaces and personal armbands
is required.
5.1 Mounting
When the temperature switch is mounted, the temperature must neither drop below the
allowed operating temperature (environment, medium) nor exceed it, even when taking
convection and heat radiation into account.
The installation site must be protected from weather influences and permanent UV
exposure/sun radiation.
Depending on the type of application, the electrical connection must be protected from
mechanical damage.
5.2 Electrical connection
DANGER!
Danger to life caused by electric current
Upon contact with live parts, there is a direct danger to life.
The instrument may only be installed and mounted by skilled
personnel.
Operation using a defective power supply unit (e.g. short circuit from
the mains voltage to the output voltage) can result in life-threatening
voltages at the instrument!
Only connect in an unpowered state!
Only disconnect the mating connector with the voltage disconnected.
Use suitable mating connectors for the current and voltage ranges.
5. Commissioning, operation
WIKA operating instructions model TFS35
11610115.04 11/2019 EN/DE/FR/ES
11
EN
Fine-stranded leads must be finished with end splices.
Cables used must comply with the respective requirements in terms of stability and
temperature.
Connection cables must be run so that any mechanical damage is prevented.
Only connect circuits with the same voltage and type of protection to the switch
contacts and connecting cables.
Size the connecting cables for the largest current strength in the circuits.
Only connect the TFS35 with extra-low voltage circuits, or with safety extra-low
voltage circuits (SELV) or protected extra-low voltage circuits (PELV).
Do not connect circuits simultaneously with low-voltage circuits.
Pin assignment
Circular connector M12 x 1AMP Junior Power Timer connector
Rectangular connector per DIN EN 175301-803
5. Commissioning, operation
11610115.04 11/2019 EN/DE/FR/ES
12 WIKA operating instructions model TFS35
EN
6. Maintenance and cleaning
For contact details see chapter 1 “General information” or the back page
of the operating instructions.
6.1 Maintenance
The bimetal temperature switch is maintenance-free.
Repairs should only be carried out by the manufacturer or, following prior consultation,
by correspondingly qualified skilled personnel.
6.2 Cleaning
CAUTION!
Physical injuries and damage to property and the environment
Improper cleaning may lead to physical injuries and damage to property
and the environment. Residual media in the dismounted instrument can
result in a risk to persons, the environment and equipment.
Carry out the cleaning process as described below.
1. Prior to cleaning, switch off and disconnect the instrument from the voltage supply.
2. Clean the instrument with a moist cloth.
Electrical connections must not come into contact with moisture!
CAUTION!
Damage to the instrument
Improper cleaning may lead to damage to the instrument!
Do not use any aggressive cleaning agents.
Do not use any hard or pointed objects for cleaning.
3. Wash or clean the dismounted instrument, in order to protect persons and the
environment from exposure to residual media.
For information on returning the instrument see chapter 7.2 “Return”.
6. Maintenance and cleaning
WIKA operating instructions model TFS35
11610115.04 11/2019 EN/DE/FR/ES
13
EN
7. Dismounting, return and disposal
7.1 Dismounting
WARNING!
Physical injuries and damage to property and the environment
through residual media
Upon contact with hazardous media (e.g. oxygen, acetylene, flammable
or toxic substances), harmful media (e.g. corrosive, toxic, carcinogenic,
radioactive), and also with refrigeration plants and compressors, there is a
danger of physical injuries and damage to property and the environment.
Before storage of the dismounted instrument (following use) wash or
clean it, in order to protect persons and the environment from exposure
to residual media.
Observe the information in the material safety data sheet for the
corresponding medium.
Wash or clean the dismounted instrument, in order to protect persons
and the environment from exposure to residual media.
WARNING!
Risk of burns
During dismounting there is a risk of dangerously hot media escaping.
Let the instrument cool down sufficiently before dismounting it!
DANGER!
Danger to life caused by electric current
Upon contact with live parts, there is a direct danger to life.
The dismounting of the instrument may only be carried out by skilled
personnel.
Only disconnect the bimetal temperature switch once the system has
been isolated from power sources!
WARNING!
Physical injury
When dismounting, there is a danger from aggressive media and high
pressures.
Observe the information in the material safety data sheet for the
corresponding medium.
Only disconnect the bimetal temperature switch once with the voltage
disconnected!
7. Dismounting, return and disposal
11610115.04 11/2019 EN/DE/FR/ES
14 WIKA operating instructions model TFS35
EN
7.2 Return
Strictly observe the following when shipping the instrument:
All instruments delivered to WIKA must be free from any kind of hazardous substances
(acids, bases, solutions, etc.) and must therefore be cleaned before being returned.
WARNING!
Physical injuries and damage to property and the environment
through residual media
Residual media in the dismounted instrument can result in a risk to
persons, the environment and equipment.
With hazardous substances, include the material safety data sheet for
the corresponding medium.
Clean the instrument, see chapter 6.2 “Cleaning”.
When returning the instrument, use the original packaging or a suitable transport
packaging.
To avoid damage:
1. Wrap the instrument in an antistatic plastic film.
2. Place the instrument, along with shock-absorbent material, in the packaging.
Place shock-absorbent material evenly on all sides of the transport packaging.
3. If possible, place a bag containing a desiccant inside the packaging.
4. Label the shipment as carriage of a highly sensitive measuring instrument.
Information on returns can be found under the heading “Service” on our
local website.
7.3 Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an environmentally
compatible way and in accordance with the country-specific waste disposal regulations.
Do not dispose of with household waste. Ensure a proper disposal in
accordance with national regulations.
7. Dismounting, return and disposal
WIKA operating instructions model TFS35
11610115.04 11/2019 EN/DE/FR/ES
15
EN
8. Specifications
Specifications
Temperature ranges
Reset Switching Temperature
(RST)
Typically 15 ... 40 K below the switching temperature
To ensure a safe reset of the switch at low switching
temperatures, care must be taken that the temperature
difference between the measuring point and environment
is high enough; since otherwise the switch cannot cool
back down to the reset switching temperature and thus the
instrument will not be able to return to its normal state.
Ambient temperature Note:
Due to short installation length there is a risk that
the temperature at the connector will rise up to an
inadmissibly high value. This absolutely must be taken
into account when designing the measuring point. The
temperature at the connector must not exceed the above
mentioned temperature range.
- Rectangular connector per
EN 175301-803
-40 ... +100 °C
- AMP Junior Power Timer
connector
-40 ... +130 °C
- Circular connector M12 x 1 -40 ... +90 °C
Static operating pressure Max. 50 bar
Max. switching voltage Resistive load (cos ϕ = 1):
AC 48 V, 50/60 Hz, 3 A
DC 24 V, 3 A
DC 12 V, 4 A
Electrical connection
Rectangular connector per EN 175301-803, form A
AMP Junior Power Timer connector
Circular connector M12 x 1
Ingress protection
1)
The ingress protection depends on the electrical connection.
Rectangular connector per EN 175301-803: IP65
AMP Junior Power Timer connector: IP66, IP67
Circular connector M12 x 1: IP66, IP67
1) The stated ingress protection only applies when plugged in using mating connectors that have the appropriate ingress
protection.
For further specifications see WIKA data sheet TV 35.01 and the order documentation.
8. Specifications
11610115.04 11/2019 EN/DE/FR/ES
16 WIKA operating instructions model TFS35
EN
11610115.04 11/2019 EN/DE/FR/ES
58 WIKA operating instructions model TFS35
WIKA operating instructions model TFS35
11610115.04 11/2019 EN/DE/FR/ES
59
60
11610115.04 11/2019 EN/DE/FR/ES
WIKA operating instructions model TFS35
WIKA Alexander Wiegand SE & Co. KG
Alexander-Wiegand-Straße 30
63911 Klingenberg • Germany
Tel +49 9372 132-0
Fax +49 9372 132-406
info@wika.de
www.wika.de
WIKA subsidiaries worldwide can be found online at www.wika.com.
WIKA-Niederlassungen weltweit finden Sie online unter www.wika.de.
La liste des filiales WIKA dans le monde se trouve sur www.wika.fr
Sucursales WIKA en todo el mundo puede encontrar en www.wika.es.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50