Sanyo KS1271 Technical & Service Manual

Category
Split-system air conditioners
Type
Technical & Service Manual

This manual is also suitable for

IMPORTANT
These air conditioners employ new
refrigerant R410A.
Pay special attention when
servicing the unit.
TECHNICAL & SERVICE MANUAL
KS0971 + C0971
+ CL0971
KS1271 + C1271
+ CL1271
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
Indoor Unit
FILE NO.
Destination: North America
Outdoor Model No.
C0971
C1271
CL0971
CL1271
Product Code No.
1 852 330 23
1 852 330 24
1 852 330 25
1 852 330 26
Outdoor Unit
KS0971
KS1271
C0971
C1271
CL0971
CL1271
REFERENCE NO. SM700655-01
Indoor Model No.
KS0971
KS1271
Product Code No.
1 852 099 81
1 852 099 82
A
I
R
C
O
N
DITIONER
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
SPECIAL PRECAUTIONS
This symbol refers to a hazard
or unsafe practice which can
result in severe personal
injury or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or
product or property damage.
CAUTION
CAUTION
WARNING
WARNING
Important!
Please Read Before Starting
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an
important part of your job to install or service the system so it
operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given
in this manual.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our sales/service outlet or
your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or thin
aluminum fins on the air conditioner can cut your fingers.
When Installing
In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s
weight. It may be necessary to construct a strong wood or
metal frame to provide added support.
In a Room
Properly insulate any tubing run inside a room to prevent
"sweating" that can cause dripping and water damage to walls
and floors.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents water
damage and abnormal vibration.
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of the
flare and union tubes before connecting them, then tighten
the nut with a torque wrench for a leak-free connection.
Check carefully for leaks before starting the test run.
When Servicing
Tu rn the power off at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
Others
Ventilate any enclosed areas when installing or testing the
refrigeration system. Escaped refrigerant gas, on contact
with fire or heat, can produce dangerously toxic gas.
Confirm upon completing installation that no refrigerant gas
is leaking. If escaped gas comes in contact with a stove,
gas water heater, electric room heater or other heat source,
it can produce dangerously toxic gas.
2
Table of Contents
1. OPERATING RANGE
2. SPECIFICATIONS
2-1. Unit Specifications
2-2. Major Component Specifications
2-3. Other Component Specifications
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
5. PERFORMANCE DATA
5-1. Temperature Charts
5-2. Air Throw Distance Charts
6. ELECTRICAL DATA
6-1. Electrical Characteristics
6-2. Electric Wiring Diagrams
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection
7-2. Recommended Wire Length and Diameter
7-3. Remote Control Unit Installation Position
7-4. How to Test Run the Air Conditioner
7-5. Remove the Grille to Install the Indoor Unit
8. MAINTENANCE
8-1. Address Setting of the Remote Control Unit
8-2. Disconnecting and Connecting Positive Connector for Outdoor Unit
9. FUNCTIONS
9-1. Operation Functions
9-2. Protective Functions
5
6
10
16
17
19
20
24
26
28
31
33
34
35
36
37
38
39
41
...................................................................................................................
.............................................................................................................
.......................................................................................
.......................................................................................
.....................................................................................................................
...................................................................................................
............................................................................................................
.................................................................................................
....................................................................................................
....................................................................................................
...................................................................................................
........................................................................
...........................................................................
...................................................................................
........................................................................
.......................................................................
..................................
...........................................................................................................
...........................................................................................................
Page
3
10. TROUBLESHOOTING
10-1. Precautions before Performing Inspection or Repair
10-2. Method of Self-Diagnostics
10-3. Checking the Indoor and Outdoor Units
10-4. Trouble Diagnosis of Fan Motor
10-5. Noise Malfunction and Electromagnetic Interference
11. CHECKING ELECTRICAL COMPONENTS
11-1. Measurement of Insulation Resistance
11-2. Checking Continuity of Fuse on PCB Ass'y
12. REFRIGERANT R410A:
SPECIAL PRECAUTIONS WHEN SERVICING UNIT
12-1. Characteristics of New Refrigerant R410A
12-2. Checklist before Servicing
12-3. Tools Specifically for R410A
12-4. Tubing Installation Procedures
12-5. In Case of Compressor Malfunction
12-6. In Case Refrigerant is Leaking
12-7. Charging Additional Refrigerant
12-8. Retro-Fitting Existing Systems
APPENDIX INSTRUCTION MANUAL
42
42
45
46
47
48
49
50
51
52
52
53
55
56
56
57
...........................................................
.................................................................................................
..............................................................................
..........................................................................................
..........................................................
...............................................................................
.........................................................................
.........................................................................
...................................................................................................
................................................................................................
............................................................................................
....................................................................................
............................................................................................
..........................................................................................
............................................................................................
............................................................................................
Page
4
95 °F D.B. / 71 °F W.B.
67 °F D.B. / 57 °F W.B.
1. OPERATING RANGE
Maximum
Minimum
115 °F D.B.
67 °F D.B.
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
95 °F D.B. / 71 °F W.B.
67 °F D.B. / 57 °F W.B.
Maximum
Minimum
115 °F D.B.
0 °F D.B.
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Models : KS0971 + C0971
KS1271 + C1271
Models : KS0971 + CL0971
KS1271 + CL1271
5
6
2. SPECIFICATIONS
2-1. Unit Specifications
Indoor Unit KS0971
Outdoor Unit C0971
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
( 3,000 to 9,000 )
Sensible Capacity
Latent Capacity
Air Circulation (High)
SEER
Height x Width x Depth
Height x Width x Depth
Shipping Volume
BTU/Wh
20
Voltage Rating
Pints/h
Total Capacity
Performance
%
Power Factor
Features
Compressor Locked Rotor Amperes
A
Fuse or Circuit Breaker Capacity
A
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Manual
Auto
Timer
Indoor / Outdoor
Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi, Me, Lo)
Airflow Direction (Indoor)
Horizontal
R410A / 2.09 (950)
Electric Expansion Valve
Washable, Anti-Mold
DC Rotary (Inverter)
Flare Type
25 (7.5)
34 / 31 / 28 / 23
46
1/4 (6.35)
3/8 (9.52)
Optional / Air Clean Filter
11-7/32 x 32-15/32 x 7-7/16
21-9/16 x 28-11/32 x 10-7/16
Moisture Removal (High)
W
Power Input
V
A
Available Voltage Range
Running Amperes
Electrical Rating
20
Dimensions & Weight
(*Qt = Quiet mode)
Refrigerant Tubing Connections
Refrigerant Tube Kit / Accessories
Refrigerant
Tube Diameter
Outdoor Unit
Indoor Unit
ft. (m)
lb. (kg)
lb. (kg)
Unit Dimensions
Package Dimensions
Weight
(mm)
Max. allowable tubing length at shipment
Outdoor : Hi
inch (mm)
inch (mm)
Wide tube
Vertical
dB-A
dB-A
Air Filter
Operation Sound
Compressor
Refrigerant / Amount charged at shipment
lb. (g)
Refrigerant Control
cu.ft (m
3
)
Indoor : Hi/Me/Lo/Qt*
Shipping
inch
(mm)
inch
Net
Narrow tube
16
Cooling
kW
BTU/h
115V Single-Phase 60Hz
282 (480)
3.4
Cooling
104 to 126
(285 x 825 x 189)
(548 x 720 x 265)
( 0.9 to 2.65 )
9,000
2.65
86
( 2.5 to 7.6 )
( 250 to 755 )
7.6
755
(255 x 900 x 350)
(600 x 856 x 362)
10-1/32 x 35-7/16 x 13-25/32
23-5/8 x 33-11/16 x 14-1/4
19.8
(9.0)
72.8
(33.0)
24.3
(11.0)
79.4
(36.0)
2.82
(0.08)
6.35
(0.18)
BTU/h
BTU/h
7,650
1,350
7
Indoor Unit KS1271
Outdoor Unit C1271
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
( 3,000 to 11,900 )
Sensible Capacity
Latent Capacity
Air Circulation (High)
SEER
Height x Width x Depth
Height x Width x Depth
Shipping Volume
81.6
cu.ft (m
3
)
2.82
(0.08)
6.35
Net
lb. (kg)
19.8
lb. (kg)
24.3
11-7/32 x 32-15/32 x 7-7/16
21-9/16 x 28-11/32 x 10-7/16
(mm)
(285 x 825 x 189)
(548 x 720 x 265)
inch
Indoor Unit
Outdoor Unit
16
Cooling
104 to 126
87
( 2.5 to 10.9 )
( 250 to 1,090 )
10.9
1,090
3.5
( 0.9 to 3.5 )
294 (500)
4.26
9,100
2,800
Cooling
BTU/h
115V Single-Phase 60Hz
Voltage Rating
Total Capacity
11,900
(mm)
Shipping
Narrow tube
Wide tube
Dimensions & Weight
Package Dimensions
inch
Weight
Operation Sound
Compressor
Refrigerant / Amount charged at shipment
lb. (g)
Refrigerant Control
Indoor : Hi/Me/Lo/Qt*
Unit Dimensions
20
(*Qt = Quiet mode)
Refrigerant Tubing Connections
Refrigerant Tube Kit / Accessories
Refrigerant
Tube Diameter
ft. (m)
Optional / Air Clean Filter
Flare Type
Electrical Rating
Moisture Removal (High)
W
Power Input
V
A
Available Voltage Range
Running Amperes
Pints/h
25 (7.5)
1/4 (6.35)
3/8 (9.52)
Max. allowable tubing length at shipment
Outdoor : Hi
inch (mm)
inch (mm)
dB-A
dB-A
Airflow Direction (Indoor)
Horizontal
R410A / 2.43 (1,100)
Washable, Anti-Mold
DC Rotary (Inverter)
Vertical
Air Filter
Timer
Indoor / Outdoor
Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi, Me, Lo)
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
%
Power Factor
Features
Compressor Locked Rotor Amperes
A
Fuse or Circuit Breaker Capacity
A
BTU/Wh
Performance
kW
BTU/h
BTU/h
20
36 / 33 / 29 / 25
47
Manual
Auto
Electric Expansion Valve
(37.0)
(0.18)
23-5/8 x 33-11/16 x 14-1/4
(255 x 900 x 350)
(600 x 856 x 362)
(9.0)
75.0
(34.0)
10-1/32 x 35-7/16 x 13-25/32
(11.0)
8
Indoor Unit KS0971
Outdoor Unit CL0971
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
( 3,000 to 9,000 )
Sensible Capacity
Latent Capacity
Air Circulation (High)
SEER
Height x Width x Depth
Height x Width x Depth
Shipping Volume
Features
Performance
Electrical Rating
Moisture Removal (High)
Pints/h
Total Capacity
kW
%
20
86
20
BTU/Wh
A
Power Factor
16
Timer
Indoor / Outdoor
Fan Speeds
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi and multi steps)
DC Rotary (Inverter)
Manual
Auto
Compressor Locked Rotor Amperes
A
Fuse or Circuit Breaker Capacity
Airflow Direction (Indoor)
Horizontal
Controls / Temperature Control
Control Unit
25 (7.5)
R410A / 2.09 (950)
Electric Expansion Valve
34 / 31 / 28 / 23
46
Flare Type
Power Input
V
A
Available Voltage Range
Running Amperes
W
Washable, Anti-Mold
Unit Dimensions
(*Qt = Quiet mode)
Refrigerant Tubing Connections
Refrigerant Tube Kit / Accessories
Refrigerant
Tube Diameter
Max. allowable tubing length at shipment
Outdoor : Hi
Narrow tube
Wide tube
Shipping
ft. (m)
inch (mm)
inch
(mm)
inch (mm)
Dimensions & Weight
Vertical
dB-A
dB-A
Air Filter
Indoor : Hi/Me/Lo/Qt*
Operation Sound
Compressor
Refrigerant / Amount charged at shipment
lb. (g)
Refrigerant Control
BTU/h
BTU/h
115V Single-Phase 60Hz
9,000
Voltage Rating
BTU/h
Cooling
104 to 126
Cooling
2.65
( 0.9 to 2.65 )
7,650
1,350
282 (480)
(255 x 900 x 350)
(600 x 856 x 362)
23-5/8 x 33-11/16 x 14-1/4
1/4 (6.35)
3/8 (9.52)
Optional / Air Clean Filter
Indoor Unit
Outdoor Unit
(36.0)
(0.18)
(9.0)
72.8
(33.0)
3.4
11-7/32 x 32-15/32 x 7-7/16
21-9/16 x 28-11/32 x 10-7/16
(mm)
(285 x 825 x 189)
(548 x 720 x 265)
( 2.5 to 7.6 )
( 250 to 755 )
7.6
755
Package Dimensions
inch
10-1/32 x 35-7/16 x 13-25/32
Weight
Net
lb. (kg)
19.8
lb. (kg)
24.3
(11.0)
79.4
cu.ft (m
3
)
2.82
(0.08)
6.35
9
Indoor Unit KS1271
Outdoor Unit CL1271
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
( 3,000 to 11,900 )
Sensible Capacity
Latent Capacity
Air Circulation (High)
SEER
Height x Width x Depth
Height x Width x Depth
Shipping Volume
BTU/h
Electrical Rating
Moisture Removal (High)
Pints/h
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
%
20
16
87
20
BTU/Wh
A
Power Factor
Features
Compressor Locked Rotor Amperes
A
Fuse or Circuit Breaker Capacity
Control Unit
Timer
Indoor / Outdoor
Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi and multi steps)
Washable, Anti-Mold
DC Rotary (Inverter)
Manual
Auto
Flare Type
25 (7.5)
R410A / 2.43 (1,100)
Electric Expansion Valve
36 / 33 / 29 / 25
47
1/4 (6.35)
3/8 (9.52)
Optional / Air Clean Filter
11-7/32 x 32-15/32 x 7-7/16
21-9/16 x 28-11/32 x 10-7/16
Refrigerant Tubing Connections
Power Input
V
A
Available Voltage Range
Running Amperes
W
Airflow Direction (Indoor)
Horizontal
Controls / Temperature Control
Vertical
dB-A
dB-A
Air Filter
Operation Sound
Compressor
Refrigerant / Amount charged at shipment
lb. (g)
Refrigerant Control
Shipping
Narrow tube
Wide tube
Refrigerant Tube Kit / Accessories
Refrigerant
Unit Dimensions
Package Dimensions
Tube Diameter
Indoor : Hi/Me/Lo/Qt*
inch
inch
(mm)
ft. (m)
Max. allowable tubing length at shipment
Outdoor : Hi
inch (mm)
inch (mm)
(*Qt = Quiet mode)
Cooling
115V Single-Phase 60Hz
Voltage Rating
Performance
294 (500)
4.26
Cooling
104 to 126
( 0.9 to 3.5 )
(37.0)
(0.18)
(9.0)
75.0
(34.0)
(255 x 900 x 350)
(600 x 856 x 362)
10-1/32 x 35-7/16 x 13-25/32
23-5/8 x 33-11/16 x 14-1/4
Total Capacity
BTU/h
11,900
kW
3.5
9,100
BTU/h
2,800
Dimensions & Weight
Indoor Unit
Outdoor Unit
( 2.5 to 10.9 )
( 250 to 1,090 )
10.9
1,090
(mm)
(285 x 825 x 189)
(548 x 720 x 265)
Weight
Net
lb. (kg)
19.8
lb. (kg)
24.3
(11.0)
81.6
cu.ft (m
3
)
2.82
(0.08)
6.35
10
2-2. Major Component Specifications
2-2-1. Indoor Unit
Indoor Unit KS0971
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Open
o
F (
o
C)
Close
o
F (
o
C)
Micro F
VAC
4.5
266 (130)
-
250
Thermal Fuse
Aluminum Plate Fin / Copper Tube
2
19.5
Face Area
ft
2
(m
2
)
2.02 (0.188)
Coil
Rows
Fins per inch
Heat Exchanger Coil
Microprocessor
250V 3A
Control Circuit Fuse
Controls
1 ... D3-11/16 / L24-31/32 (D94/L634)
RCS-4VPIS4U
Fan
Cross-Flow
Remote Control Unit
(Ambient Temp. 77
o
F (25
o
C ))
Each Pair of Terminal : 400 +/- 7%
Control PCB
CB-KS0971
Part No.
Fan Motor
BRN - WHT : 57.9
RED - WHT : 55.2
MP24Z3
DC 12V
Coil Resistance
Ohm
Safety Device
Rating
Type
Model
Operating Temp.
(Ambient Temp. 68
o
F (20
o
C))
Nominal Output
W
Coil Resistance
Ohm
Q'ty ... Dia. and Length
inch (mm)
Type
16
1,200
Model ... Q'ty
No. of Poles
IBH-884-076 ... 1
4
Flap Motor
Type
Stepping Motor
Rough Measure RPM (Cool)
Run Capacitor
Type
AC Motor
11
Indoor Unit KS1271
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Open
o
F (
o
C)
Close
o
F (
o
C)
Micro F
VAC
4.5
266 (130)
-
250
Thermal Fuse
Aluminum Plate Fin / Copper Tube
2
19.5
Face Area
ft
2
(m
2
)
2.02 (0.188)
Coil
Rows
Fins per inch
Heat Exchanger Coil
Microprocessor
250V 3A
Control Circuit Fuse
Controls
1 ... D3-11/16 / L24-31/32 (D94/L634)
RCS-4VPIS4U
Fan
Cross-Flow
Remote Control Unit
(Ambient Temp. 77
o
F (25
o
C ))
Each Pair of Terminal : 400 +/- 7%
Control PCB
CB-KS1271
Part No.
Fan Motor
BRN - WHT : 57.9
RED - WHT : 55.2
MP24Z3
DC 12V
Coil Resistance
Ohm
Safety Device
Rating
Type
Model
Operating Temp.
(Ambient Temp. 68
o
F (20
o
C))
Nominal Output
W
Coil Resistance
Ohm
Q'ty ... Dia. and Length
inch (mm)
Type
16
1,250
Model ... Q'ty
No. of Poles
IBH-884-076 ... 1
4
Flap Motor
Type
Stepping Motor
Rough Measure RPM (Cool)
Run Capacitor
Type
AC Motor
12
2-2-2. Outdoor Unit
Outdoor Unit C0971
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Pints (cc)
Ohm U - V : 0.81
V - W : 0.81
W - U : 0.81
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Model
Operation Temp.
Micro F
VAC
RED - WHT : 77.5
WHT - BLU : 77.5
BLU - RED : 77.5
Type
Over- Current Protection
Micro F
VAC
Coil Resistance (Ambient Temp. 68
o
F (20
o
C))
External Finish
Acrylic baked-on enamel finish
DC Rotary (Hermetic)
G4C090LU1ER / 900W
FV50S ... 0.68 (320)
Yes
Safety Device
Yes
-
Run Capacitor
CS-7L115
Open : 239
o
F(115
o
C), Close : 203
o
F(95
o
C)
Overload Relay
-
Yes
-
Internal Controller
Aluminum Plate Fin / Copper Tube
2
18.1
Face Area
ft
2
(m
2
)
3.10 (0.288)
Coil
Rows
Fins per inch
Heat Exchanger Coil
Microprocessor
125V 25A
Control Circuit Fuse
Controls
1 ... D15 -3/4 (D400)
Fan
Propeller
(Ambient Temp. 68
o
F (20
o
C))
DAJ12-55J71-CU ... 1
Control PCB
CB-C0971
Part No.
Fan Motor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount
-
-
Yes
8
Nominal Output
Coil Resistance
50
750 / 750
Safety Device
Rough Measure RPM (Cool)
Run Capacitor
Type
Model ... Q'ty
No. of Poles
W
Ohm
DC Motor
Q'ty ... Dia.
Compressor
inch (mm)
Type
Crankcase Heater
13
Outdoor Unit C1271
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Pints (cc)
Ohm U - V : 0.81
V - W : 0.81
W - U : 0.81
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Model
Operation Temp.
Micro F
VAC
RED - WHT : 77.5
WHT - BLU : 77.5
BLU - RED : 77.5
Type
Over- Current Protection
Micro F
VAC
Coil Resistance (Ambient Temp. 68
o
F (20
o
C))
External Finish
Acrylic baked-on enamel finish
DC Rotary (Hermetic)
G4C090LU1ER / 900W
FV50S ... 0.68 (320)
Yes
Safety Device
Yes
-
Run Capacitor
CS-7L115
Open : 239
o
F(115
o
C), Close : 203
o
F(95
o
C)
Overload Relay
-
Yes
-
Internal Controller
Aluminum Plate Fin / Copper Tube
2
18.1
Face Area
ft
2
(m
2
)
3.95 (0.367)
Coil
Rows
Fins per inch
Heat Exchanger Coil
Microprocessor
125V 25A
Control Circuit Fuse
Controls
1 ... D15 -3/4 (D400)
Fan
Propeller
(Ambient Temp. 68
o
F (20
o
C))
DAJ12-55J71-CU ... 1
Control PCB
CB-C1271
Part No.
Fan Motor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount
-
-
Yes
8
Nominal Output
Coil Resistance
50
750 / 750
Safety Device
Rough Measure RPM (Cool)
Run Capacitor
Type
Model ... Q'ty
No. of Poles
W
Ohm
DC Motor
Q'ty ... Dia.
Compressor
inch (mm)
Type
Crankcase Heater
14
Outdoor Unit CL0971
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Pints (cc)
Ohm U - V : 0.81
V - W : 0.81
W - U : 0.81
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Model
Operation Temp.
Micro F
VAC
RED - WHT : 77.5
WHT - BLU : 77.5
BLU - RED : 77.5
Type
Over- Current Protection
Micro F
VAC
DC Motor
Q'ty ... Dia.
Compressor
inch (mm)
Type
Crankcase Heater
Safety Device
Rough Measure RPM (Cool)
Run Capacitor
Type
Model ... Q'ty
No. of Poles
W
Ohm
8
Nominal Output
Coil Resistance
50
750 / 750
Control PCB
CB-CL0971
Part No.
Fan Motor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount
-
115V 20W
Yes
Heat Exchanger Coil
Microprocessor
125V 25A
Control Circuit Fuse
Controls
1 ... D15 -3/4 (D400)
Fan
Propeller
(Ambient Temp. 68
o
F (20
o
C))
DAJ12-55J71-CU ... 1
Face Area
ft
2
(m
2
)
3.10 (0.288)
Coil
Rows
Fins per inch
-
Yes
-
Internal Controller
Aluminum Plate Fin / Copper Tube
2
18.1
Run Capacitor
CS-7L115
Open : 239
o
F(115
o
C), Close : 203
o
F(95
o
C)
Overload Relay
Coil Resistance (Ambient Temp. 68
o
F (20
o
C))
External Finish
Acrylic baked-on enamel finish
DC Rotary (Hermetic)
G4C090LU1ER / 900W
FV50S ... 0.68 (320)
Yes
Safety Device
Yes
-
15
Outdoor Unit CL1271
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Pints (cc)
Ohm U - V : 0.81
V - W : 0.81
W - U : 0.81
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Model
Operation Temp.
Micro F
VAC
RED - WHT : 77.5
WHT - BLU : 77.5
BLU - RED : 77.5
Type
Over- Current Protection
Micro F
VAC
DC Motor
Q'ty ... Dia.
Compressor
inch (mm)
Type
Crankcase Heater
Safety Device
Rough Measure RPM (Cool)
Run Capacitor
Type
Model ... Q'ty
No. of Poles
W
Ohm
8
Nominal Output
Coil Resistance
50
750 / 750
Control PCB
CB-CL1271
Part No.
Fan Motor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount
-
115V 20W
Yes
Heat Exchanger Coil
Microprocessor
125V 25A
Control Circuit Fuse
Controls
1 ... D15 -3/4 (D400)
Fan
Propeller
(Ambient Temp. 68
o
F (20
o
C))
DAJ12-55J71-CU ... 1
Face Area
ft
2
(m
2
)
3.95 (0.367)
Coil
Rows
Fins per inch
-
Yes
-
Internal Controller
Aluminum Plate Fin / Copper Tube
2
18.1
Run Capacitor
CS-7L115
Open : 239
o
F(115
o
C), Close : 203
o
F(95
o
C)
Overload Relay
Coil Resistance (Ambient Temp. 68
o
F (20
o
C))
External Finish
Acrylic baked-on enamel finish
DC Rotary (Hermetic)
G4C090LU1ER / 900W
FV50S ... 0.68 (320)
Yes
Safety Device
Yes
-
2-3. Other Component Specifications
Indoor Unit KS0971
KS1271
Outdoor Unit C0971 C1271
CL0971 CL1271
0
32 50 68 86 104 122 140 158 176 194
(0) (10) (20) (30) (40) (50) (60) (70) (80) (90)
40
60
80
100
120
140
160
180
200
20
50
1
0
2
3
4
5
6
7
8
9
10
59 68 77 86 95 104
(10) (15) (20) (25) (30) (35) (40)
Indoor air temp sensor
(Model:PTM-D51H-S3 TH2)
Indoor heat exchanger sensor
(Model:PTM-D51H-S3 TH1)
Compressor temp sensor
(Model:DTN-TKS274Y TH2)
Resistance (k ohm)
Resistance (k ohm)
Temperature °F (°C)
Outdoor air temp sensor
(Model:DTN-TKS269B)
Outdoor heat exchanger sensor
(Model:DTN-TKS274Y TH1)
40
35
30
25
20
15
10
5
0
-
451423 32 41 50 59 68
(
-
20)(
-
15)(
-
10) (
-
5) (0) (5) (10) (15) (20)
Resistance (k ohm)
Temperature °F (°C)
Temperature °F (°C)
16
3. DIMENSIONAL DATA
Indoor Unit KS0971
KS1271
Unit: inch(mm)
17
10-13/16
3-19/32
ID:23/32
2-ID:15/16
21-3/16
6-3/32
4-9/32 2-5/32
Narrow tube service valve
dia.1/4" (6.35)
Wide tube service valve
dia.3/8" (9.52)
3-19/32
15/32
10-7/16(265)
11-13/32
12-7/16
Unit: inch(mm)
28-11/32 (720) 2-1/8
21-9/16 (548)
5/8
Outdoor Unit C0971 C1271
CL0971 CL1271
18
Compressor
Accumulator
Wide tube
service
valve
Wide tube
Narrow
tube
service
valve
Narrow tube
Heat exchanger
Heat exchanger
Muffler
Cooling cycle
Indoor unit Outdoor unit
Electric
expansion
valve
M
Muffler
*1
*1: 0nly for C1271/CL1271
O.D.
3/8"
(9.52 mm)
O.D.
1/4"
(6.35 mm)
H.P.
High pressure
switch
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
Indoor Unit KS0971
KS1271
Outdoor Unit C0971 C1271
CL0971 CL1271
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 5/16"(8 mm).
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Wide tube
Thickness:
Min. 5/16"(8 mm)
Insulation
Narrow tube
Thickness:
Min. 5/16"(8 mm)
IMPORTANT
CAUTION
19
5. PERFORMANCE DATA
5-1. Temperature Charts
Indoor Unit KS0971 Outdoor Unit C0971
Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
:Points of rating condition
Black dots in above charts indicate the following rating conditions.
NOTE
Cooling: Indoor air temperature 80 °F D.B. / 67 °F W.B.
Outdoor air temperature 95 °F D.B.
Cooling Characteristics
77
(25)
86
(30)
95
(35)
104
(40)
77
(25)
86
(30)
95
(35)
104
(40)
62.6(17)
60.8(16)
59.0(15)
57.2(14)
55.4(13)
53.6(12)
51.8(11)
50.0(10)
Outdoor inlet air D.B. temp.°F(°C)
Outdoor inlet air D.B. temp.°F(°C)
Outdoor inlet air D.B. temp.°F(°C)
Operating current (A)Indoor discharge air temperature °F(°C)
77
(25)
86
(30)
95
(35)
104
(40)
8
9
10
11
6
5
7
4
145
(1.0)
159
(1.1)
131
(0.9)
117
(0.8)
Low pressure at wide tube service valve
psig(MPaG)
80
°F(
27
°C)
75
°F(
24
°C)
Indoor Air Temp.86
°F(
30
°C)
Outdoor fan speed
HighLow
Outdoor fan speed
HighLow
Outdoor fan speed
HighLow
80
°F(
27
°C)
75
°F(
24
°C)
Indoor Air Temp.86
°F(30°C)
75
°F(
24
°C)
80
°F(
27
°C)
Indoor Air Temp.86
°F(
30
°C)
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81

Sanyo KS1271 Technical & Service Manual

Category
Split-system air conditioners
Type
Technical & Service Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI