b.
Click Add to configure the alarm actions to add to the notification policy. Click
Manage Actions to create alarm actions, or modify or remove existing alarm
actions on the StruxureWare Central server.
Note: You click Choose Thresholds to add user-created thresholds, for the
device groups or devices selected, to the Default notification policy .
Communication link status thresholds for monitored SNMP and Modbus devices
are added to the Default notification policy at device discovery.
c. Check-mark one or more actions to configure their notification options, check-
mark the actions you want to add to the notification policy, and click OK.
12. Create thresholds for sensor types supported by monitored devices.
a.
Select the sensor type on which you want to add a threshold from the Create
Thresholds option in the Alarm Configuration menu. Alternatively, select a
device group or device, and right-click to select the Create Thresholds option.
b. In the "Select Threshold Type" display, select the threshold type you want to add,
and click Next.
c. In the "Select Sensors" display, select the sensor or sensors for which you want
to add thresholds, and click Next.
d.
In the "Create Threshold" display, define the settings, and, if desired, click
Threshold Scheduling to configure when the StruxureWare Central server will
generate notifications if the threshold becomes active. Click Next.
e. In the "Select Notification Policies" display, select the notification policies to
which you want to add the alarm threshold, and click Finish to exit the wizard.
13. Define any or all the alert actions you want available to any NetBotz Appliances
discovered during step 9, to associate with the alert profiles used for alert notifications.
Each NetBotz Appliance has its own unique profiles it can use for alarm conditions at
the devices it monitors.
Note: An alert action must be available to the StruxureWare Central server, and to
each monitored NetBotz Appliance, for use with their alert profiles.
a.
Select Alert Actions, a NetBotz Appliance Configuration > Alert Settings
option in the Device menu.
b. In the "Select Alert Action Type" display, select an action.
c.
In the "Select Next Action" display, select Create a new alert action.
d. In the "Select Next Action Devices" display, select the devices for which the
action can be used.
e. Define the action settings.
f. In the "Choose Next Action" display, select Configure another alert action to
repeat steps b through e, as needed, to finish defining all the alert actions for
your StruxureWare Central server and monitored NetBotz Appliances.
14. Add at least one alert action to the one of the alert profiles used by each NetBotz
Appliance for alert notifications.
Note: The profiles at a NetBotz Appliance may have been defined already using its
NetBotz Advanced View. You can edit it to make sure someone in your organization
is notified when problems occur.
a.
Select Alert Profiles, a NetBotz Appliance Configuration > Alert Settings
option in the Device menu.
b. In the "Select Parent Device" display, select the parent device (the individual
NetBotz Appliance) associated with the profile you want to configure.
c. In the "Select Alert Profile" display, select the alert profile you wish to modify,
and click Next.
d. Configure the alert profile to include at least one of the alert actions available to
the selected parent device.
e. Repeat steps a through d to add at least one alert action to the alert profile used
by each monitored NetBotz Appliance.